Interbus 71/176
3 842 530 344/2014-05, MIT: ID 40,
Bosch Rexroth AG
8.3.3
Example: writing bytes to MDT
Six bytes with the values 1 through 6 are written to the MDT starting at the address
0x1234. The data is entered in the MDT once subindex 3 has been sent.
If the PDU size is set to 240 bytes, 231 bytes have to be assigned in subindex 3.
No.
Command-
oriented
data exchange
Index
Subin-
dex
Data1 Data2 Data3 Data4 Data5 …
Data55
1
Enter MDT address
5FF5-01 0x00
0x00
0x12
0x34
2
Enter byte count
5FF5-02 0x06
3
Enter byte values
5FF5-03 0x01
0x02
0x03
0x04
0x05
0x06
0x00