23 / 50
ctrlX CORE
Housing dimensions
Bosch Rexroth AG
R911405645, Edition 05
Diagnosis history 10F3
hex
The object 10F3hex is implemented as ring memory in the "Overwrite mode". The latest 20 diagnostic
messages are stored. Older messages are deleted.
The following table shows the structure of a diagnostic message of the bus coupler for Ethercat.
Index (hex)
Subindex
Object name
Data type
Length
Rights
Meaning
10F3
Diagnosis history
Diagnostic statistics
01
Maximum messages
UINT8
1
R
Maximum number of messages
02
Newest message
UINT8
1
R
Latest message
03
Newest acknowledged mes-
sage
UINT8
1
R/W
Latest confirmed message. Writing "0"
deletes the messages in the ring memory.
04
New messages available
Boolean
0.1
R
New message available
05
Flags
UINT8
2
R/W
Setting of the object response. Refer to
ETG.1020
In case of overvoltage or undervoltage of U
L
, all modules connected to the segment circuit are
switched off.
10
Mounting, dismounting and electric installation
10.1 Housing dimensions
3.2
105
45
97.5
Fig. 5: Front view
Mounting, dismounting and electr
ic ins
tallation