background image

| PVA-CSK PAVIRO Call Station Kit 

 

 
 
 

Number

 

Component 

 

 

Connection cable for display (50 cm) 

 

 

10 

Euroblock connector 10-pole (Phoenix, MC 
1,5/10-STF-3,81, 1803659, F.01U.241.148) 

  

Euroblock connector 2-pole (Dinkle, 
EC381V-02P, F. 01U.066.918) 

 

Operation manual 

 

Important safety instructions 

  

* PMX-CSK Scope of Delivery 

 

 

Technical specifications 

 

Buttons (through screw-terminal  5 pre-programmed 
connectors) 

15 programmable zone/function 

 

buttons 

 

3 supervised programmable 

 

optional emergency buttons 

 

2 connections for each button; 

 

23 buttons share 6 common 

 

VCCs (3V3 - DC) 

 

Each button has short circuit 

 

protection 

 

 

LEDs connected to buttons 

This kit supports open drain 

(through screw-terminal 

outputs with max. 5 mA per 

connectors) 

output. Using the internal supply, 

 

a maximum of 100 mA can be 

 

sourced for all outputs. 

 

The kit also provides an external 

 

power supply for lighting LEDs of 

 

external normal buttons. 

 

2 connections (VCC & open 

 

collector) are available for each 

 

LED connected to a button. In 

 

total, 38 LEDs share 10 common 

 

MIX_PWR_LED. These LEDs are 

 

supplied with 5 V DC using the 

 

internal power supply. The 

 

connected LEDs are supplied with 

 

24 V DC using the external power 

 

supply. 

 

Each LED circuit has short-circuit 

 

protection. 

 

 

Power LED (through screw- 

Driven by MIX_PWR_LED (5 V DC 

terminal connectors) 

or 24 V DC) 

 

2 connections (VCC & open 

 

collector) 

 

 

Fault LED (through screw- 

Driven by MIX_PWR_LED (5 V DC 

terminal connectors) 

or 24 V DC) 

 

2 connections (VCC & open 

 

collector) 

 

 

Alarm LED (through screw- 

Driven by MIX_PWR_LED (5 V DC 

terminal connectors) 

or 24 V DC) 

 

2 connections (VCC & open 

 

collector) 

 

 

 
 

 

 

Included LCD display kit 

A flat ribbon cable connects the 

 

 

display to the call station kit 

 

 

mainboard. The ribbon cable 

 

 

length is +/- 300 mm 

 

 

Others (through screw-terminal  1 audio source (line in) 
connectors) 

1 supervised microphone input 

 

 

(LBB9081) capsule and PTT 

 

 

button connection (input & VCC) 

 

 

with short-circuit protection. 1 

 

 

loudspeaker connection, 1 

 

 

addi24 V DC power 

 

 

supply 

 

 

External connectors 

1 call station bus connector 

 

 

(control data + audio + power 

 

 

supply, RJ-45) 

 

 

1 EXT connector (RJ-12, e.g. for 

 

 

call station extension) 

 

 

Main power supply 

 

 

 

 

•  Nominal voltage 

24 V DC (-10%/+30%) 

 

 

 

•  Maximum voltage range  15–58 V DC 

 

 

Nominal current consumption for  < 100 mA 
main power supply 

 

 

 

Maximum supply current 

 

 

 

•  External power supply for  < 80 mA/24 V 

 

lighting, without 

< 110 mA/18 V 

 

extensions 

 

 

 

•  Internal power supply for  < 150 mA/24 V 

 

lighting, without 

< 200 mA/18 V 

 

extensions 

 

 

 

CAN interface 

10, 20, or 62.5 kbit/s 

 

 

Maximum mic input level 

-21 dBu 

 

 

Maximum line input level 

+4 dBu 

 

 

NF output 

Balanced 

 

 

 

•  Nominal level 

+6 dBu 

 

 

 

•  Maximum level 

+12 dBu 

 

 

Frequency response 

200

–16,000 Hz, +0/-3 dB 

 

 

Signal-to-noise ratio (Mic and 

≥ 60 dB 

Line input, NF output) 

 

 

 

Buttons 

 

 

 

 

•  Nominal voltage 

3.3 V DC 

 

 

 

•  Max current 

100 mA 

 

 

PTT input switch 

 

 

 

 

•  Nominal voltage 

3.3 V DC 

 

 

 

•  Max current 

100 mA 

 

 

 

LEDs 

 

 

 

 

 

Summary of Contents for PVA-CSK PAVIRO

Page 1: ...tons Possible to connect up to 15 function and selection buttons programmable button assignment Possible to connect up to three alarm buttons or key switches Possible to connect an external microphone or audio source Possible to connect a loudspeaker High resolution LC display Comprehensive parameter settings menu on the actual call station Microphone and line monitoring Error message via LED and ...

Page 2: ...or 24 V DC 2 connections VCC open collector Fault LED through screw Driven by MIX_PWR_LED 5 V DC terminal connectors or 24 V DC 2 connections VCC open collector Alarm LED through screw Driven by MIX_PWR_LED 5 V DC terminal connectors or 24 V DC 2 connections VCC open collector Included LCD display kit A flat ribbon cable connects the display to the call station kit mainboard The ribbon cable lengt...

Page 3: ...ional power supply for industrial buttons backlight Nominal voltage 24 V DC 10 30 Nominal current 300 mA consumption Maximum supply current 500 mA at 24 V External speaker Nominal resistance 8 Ω Power rating 1 5 W Maximum power 2 W Nominal operating voltage 3 5 V Normal microphone LBB9081 reference Sensitivity 3 1 mV Pa 4 dB Frequency response 280 14000 Hz Rated output impedance 500 Ω Polar patter...

Page 4: ...4 PVA CSK PAVIRO Call Station Kit Circuit diagram ...

Page 5: ...5 PVA CSK PAVIRO Call Station Kit 5 00mm 5 00mm 220 00mm 0 0 m m Installation Holes ø4mm Diameter X 4 5 1 60mm 5 00mm Dimensions Mainboard 150 00mm 5 00mm 5 00mm 5 00mm 5 00mm ...

Page 6: ...O Call Station Kit 1 6mm 5 0mm 5 0mm 85 0mm Installation Holes ø4mm Diameter X 4 5 0mm 5 0mm 5 0mm 5 0mm Dimensions LCD board Ordering information PVA CSK PAVIRO Call Station Kit Call station kit Order number PVA CSK ...