PRAESENSA
Configure the system | en
43
Bosch Security Systems B.V.
Configuration manual
2020-09 | V1.20 | PRAESENSA 1.20
5.3
Device options
Each network device that has been added to the System composition can be functional
configured by using its own Device options page. A connected network device is automatically
recognized by its device hostname and added to the Device type category where it belongs to
(e.g. Amplifier). The Device type category is manufacturer pre-defined and cannot be changed.
The following Device type categories are pre-defined.
Click
on a link below to go to Device
options of the:
–
–
–
Multifunction power supply, page 53
–
–
5.3.1
System controller
1.
Below
Device options,
click
System controller:
–
A new screen appears listed the connected system controller(s).
–
Notice that a system controller is only listed when it is added to the System
composition.
–
See also
Logon the application, page 35, if required.
2.
Select and click
the System controller name to configure.
–
A new screen appears to configure General, Virtual control inputs, Virtual audio
inputs/outputs (Dante/AES67) and Unencrypted virtual audio inputs (Dante/AES67)
functionality:
General
1.
Select and click
the + of the General category row:
2.
Select
,
enable
or
disable
each of the following items:
Item
Value
Description
Supervision
Power supply input A
Power supply input B
Enable / Disable
Enable:
24-48 Vdc power supply A and B
input. Power supply faults and/or power
losses will be indicated on the system
controller front/rear panel (see indicators
tables at the end of this section),
page 105 and Optional: Using the Logging
Viewer, page 125.
Disable:
results in a system that does not
detect power supply input failures of the
system controller of the disabled input.
Network redundancy
The network cabling supports a closed loop, which allows redundancy to be achieved.
Single network (ports 1‑5)
Selection
Select
this option if only PRAESENSA
network devices are used and the network is
star and/or redundant (daisy‑chain) topology
connected.
The system controller supports Rapid
Spanning Tree Protocol (RSTP) to enable the
use of multiple connections simultaneously