PR113B-PR114B Installer Reference Guide
4
Bosch Security Systems 12/13 PR113B-PR114BIRG FTR1.0
To have the reader control an area on the alarm system
you must assign the reader to a home area. See the
Devices-Keypads & Readers-Home Area menu option
in panel programming. If alarm system control is not
required then you should set the home area option to
No Area.
i
Note
When the reader has been configured to do alarm
area control only, the blue indicator will remain off
at all times.
To have the reader control an output (door) on the
system you must assign the reader to an access group.
See the Devices-Keypads & Readers-Access Group menu
option in panel programming.
Once assigned, the on-board Lock output and Egress in-
put are automatically assigned to the same access group
as the reader.
LED Operation For Door Control
Led
Condition
Meaning
Blue
On
Door Locked
Blue
Fast Flash
Door Unlocked
Blue
Continuous
Fast Flash
Door manually unlocked
or overridden.
Blue
2 Flashes
Door automatically
unlocked by schedule or
time zone.
Red &
Green
Alternate
Flashing
Reader initialising during
power up or LAN scan.
Blue
Off
Access Group not pro-
grammed or reader not
powered.
Table 4: Reader LED‘s - Access Group Door Control
If both alarm area and door control is required, you must
assign a home area and an access group to the reader.
i
Note
When the reader has been configured to do door
control only, the green and red indicators will re-
main off at all times.
Alert Tones
The reader emits several distinct tones to alert you to
particular system events. The volume level cannot be
adjusted on the external LAN readers however it can be
turned off via panel programming by setting the reader
volume to the lowest level. See the Devices-Keypads &
Readers-Commands menu in panel programming.
i
Note
Setting the reader volume to off will stop all audible
warning signals at the reader.
Reader Alert Tones
Event
Alert Tone Emitted
Fire
Alarm
If the system registers a fire alarm, the
reader will sound 3 short beeps fol-
lowed by a 1.5 second pause. This will
repeat until reset by the user or until
the siren run time expires.
Burglary
Alarm
If the system registers a burglary
alarm, the reader will sound a continu-
ous siren tone until reset by a user or
until the siren run time expires.
Trouble
If a system trouble condition occurs,
the reader will sound 4 x fast short
beeps followed by a 5 second pause
and will repeat this tone until the user
acknowledges the trouble
condition from a display keypad
Exit
Delay
The exit delay warning will sound 1
short beep every second when the
area the reader has been assigned to
is armed. During the last 10
seconds of exit time the warning tone
will speed up indicating that the time
has nearly expired.
Entry
Delay
The hi/lo entry delay warning tone will
sound once every second when an
entry delay zone in the area the reader
has been assigned to is triggered. If
the system is not disarmed before the
entry time expires then an alarm will
occur.
Error
If an invalid token is presented to the
reader the keypad will sound a 2 sec-
ond warning tone indicating that the
token was rejected for some reason.
See the panel log for more details.
Chime
Alert
If chime mode is active then the read-
er will sound fast short beeps to alert
the user when a zone programmed for
chime is opened. Chime mode is only
applicable when the area is disarmed.
Table 5: Reader Tones
i
Note
When readers are installed outside the premises,
you may prefer that the alert tones are disabled.
See the Devices-Keypads & Readers-Indicator Op-
tions menu in panel programming to disable these
features.