background image

Page 2

© 2004 Bosch Security Systems

MX938i Installation Instructions

Hint:

Mounting to removable ceiling tiles is not recommended
unless a sandwich is made of the base, ceiling tile and a
back plate behind the tile. Covers used for four-inch
octagonal and square boxes make a suitable back plate
(when used with bolts and wing nuts, as an example).

• Replace the enclosure on the base.

• Select an Optical Module (AR8-13 or AR13-18).

- For ceilings between 8 and 13 ft. (2.4 m and 4.0 m) from the

floor, use the optical module marked AR8-13. This marking
can be found next to the two optical module tabs. For ceilings
between 13 and 18 ft. (4.0 m and 5.5 m) high, use the optical
module marked AR13-18.

- To replace an optical module, push the optical module tabs

toward the center until the module snaps free of the circuit
board.  Holding the new module by the tabs, snap the new
module into place.

Avoid fingerprints on the mirrored surfaces. If  the mirrored
surfaces become soiled or otherwise marked, they can
be cleaned using a soft, clean cloth and any commonly
available mild window cleaner.

4.0

Wiring

Only apply power after all connections have been made
and inspected.

•  Connect wiring as shown.

NOTE:

Do not coil excess wiring
inside unit.

• Seal the Wire Entrance using the foam plug provided.

Terminal Descriptions

• 1 (B+) and 2 (B-): Connect to the Multiplex Bus of the control

panel. Use no smaller than #22 AWG (0.8 mm) wire between
the detector and the control panel.

• 3 (+) and 4 (-): Connect to the AUX Power of the control panel.

This connection is only required if LED operation (other than
during the walk test) is required. Use no smaller than #22 AWG
(0.8 mm) wire between the detector and the control panel.

5.0

Configuration Jumpers

Configure the detector using the appropriate Configuration Jumper
settings (refer to the following diagram for jumper locations).

Sensitivity

Jumper

Signal

Gain

Jumper

LED

Operation

Jumper

Address
Switches

(located under

the mirror)

5.1

LED Operation Jumper

• ON:

Allows the LED to operate when activated by alarm.

• OFF:

The LED will not operate on alarm.

If the detector is powered by the MUX Bus only,
the LED is for  Walk Test purposes only. 
 Disable
the LED when Walk Testing is complete.  To
disable the LED, place the jumper in the OFF
position.If the detector has AUX Power
supplied
, the LED operation may be left ON during normal
use.

5.2

Sensitivity Mode

• Standard Sensitivity:  Recommended setting for

maximum false alarm immunity. Tolerates
environment extremes on this setting, but requires the
largest amount of intruder motion to achieve an alarm.

• Intermediate Sensitivity:  Recommended setting for

any location where an intruder is expected to cover
only a small portion of the protected area. Tolerates
normal environments on this setting.  This setting
will improve your intruder catch performance.

• High Sensitivity:  Fast response to intruder signals.

For use in quiet environments where thermal and
illumination transients are not anticipated.

5.3

Signal Gain

NOTE:

The MX938i permits selection of the signal  gain
depending upon the environment to be protected. The
gain select jumper is located under the optical module.

• High Gain:  Recommended for large coverage

applications up to 60 ft. (18.3 m) in diameter. The
MX938i is shipped in this setting. If the gain jumper is
missing, it will default to high gain.

• Low Gain:  Recommended for applications where the

area to be covered is 40 ft. (12.2 m) or less in diameter
and for applications where the High Gain setting may
be too sensitive for environmental extremes.

 NOTE: Setting the MX938i for the LOW Signal Gain setting reduces

the Coverage area to 40 ft. (12.2 m) in diameter.

6.0

Address Switch Settings

• Set the address switch settings (see page 3) before connecting

the MX938i to the multiplex bus.

IMPORTANT

No two devices may be set to the same address. Having
two or more units set to the same address may prevent
fault detection or  cause  multiplex bus failure.

• You can find the Address Switch Settings using the chart on

page 3, or by calculating the decimal number of the address.

                                    

Binary Switch Values (Point 17 shown)

O
N

1

2

3

4

5

6

7

8

128 64 32 16

8

4

2

1

IMPORTANT

Zone (Point) Addresses 001 through 008 are reserved for
"on board" points on the DS7400(Xi) Series control panels.
Do not set any multiplex devices for Addresses 001-
008 when using a DS7400(Xi) Series control panel.

HI

LO

High Gain

HI

LO

Low Gain

ON

OFF

On

Off

ON

OFF

MUX

BUS

AUX

POWER

2

1

3

4

-

IN

+

IN

B-
IN

B+

IN

Standard

S

I

H

Intermediate

S

I

H

High

S

I

H

Summary of Contents for MX938I

Page 1: ...Control Communicators with D8125MUX Module installed Patents This device is covered under one or more of the following U S patents 4 764 755 5 268 668 and 5 302 941 2 0 Control Panel Programming Refer to the multiplex programming section of your Control Panel Reference Guide for information on programming multiplex zones for this device 3 0 Mounting Avoid Direct or reflected sunlight Moisture Movi...

Page 2: ... only Disable the LED when Walk Testing is complete To disable the LED place the jumper in the OFF position If the detector has AUX Power supplied the LED operation may be left ON during normal use 5 2 Sensitivity Mode Standard Sensitivity Recommended setting for maximum false alarm immunity Tolerates environment extremes on this setting but requires the largest amount of intruder motion to achiev...

Page 3: ...11 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 1 2 3 4 5 6 7 8 ZONE POINT ADDRESS SWITCH NUMBER SWITCH ON CLOSED 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 1 2 3 4...

Page 4: ...e test Performing a zone test on a regular basis assures an alarm output prior to arming the system Excessive handling of the mirror surfaces may lead to performance degradation 9 0 Coverage Patterns Refer to the mirror module and pattern drawings for masking information Before masking be sure the chosen mirror surface is the correct one When removing masking remember many adhesives will either de...

Reviews: