The sounder provides 11 different tones with additional second tone option (see table be-
low). The sound intensity is selectable in 4 steps via the software WinPara. The tone selection
follows also via WinPara.
Both tones can be activated separately, whereby a subsequently activation of the second tone
switches off the first tone.

Ton

Tone type,

Frequency,

2. Tone

Current

consump-

Sound in-

tensity at

24V

Ton

e

Tone type,

Description

Frequency,

Modulation

2. Tone

(not BZ 500)

consump

tion

[mA] at 24V

24V

[dB(A)]

±

2 dB

1

Sweeping,

DIN - tone

1200 - 500Hz

1Hz

970 Hz,

Continuous

max. 20

97

2

Sweeping (LF),

BS 5839, Teil 1, 1988

800 / 970Hz

1Hz

970 Hz,

Continuous

max. 20

96

3

Sweeping,

Australian tone, AS 2220

2400-2850Hz

7Hz

970 Hz,

Continuous

max. 20

92

4

Sweeping for 3,5s,

0,5s off, Dutch tone

500-1200Hz

3,5s On / 0,5s Off

970 Hz,

Continuous

max. 20

97

5

Continuous,

BS 5839, Part 1, 1988

970Hz

610 Hz,

Continuous

max. 20

97

6

Alternating tone,

French tone

554Hz / 100ms
440Hz / 400ms

970 Hz,

Continuous

max. 20

94

7

Continuous,

Schwedish tone

660Hz

970 Hz,

Continuous

max. 20

95

8

Alternating tone,

Low power

580Hz / 500ms

1000Hz / 500ms

610 Hz,

Continuous

max. 20

97

9

Pulsed tone,

Low power

580Hz

0,25s On / Off

610 Hz,

Continuous

max. 20

93

10

USA temporal 3 tone,

ISO 8201

610Hz

970 Hz,

Continuous

max. 20

95

11

USA temporal 3 tone,

ISO 8201

2850Hz

970 Hz,

Continuous

max. 20

96

Connection

Clamp

Description

+

interconnected

power

-

interconnected

power

supply

a1 / a2

LSN -

b1 , b2

LSN + (coming / going)

screen

wire

(has

to

be

isolated and as short as
possible)

b1

LSN+

b1 b2

b2

LSN+

a1 / a2

LSN-

Screen wire

+

-

+

+

-

-