PI - 32.15a
Product Documentation of the LSN Radio Fire Detection System
Seite 19 von 32
601-F.01U.002.708
A3.en / 28.12.2004
ST-FIR/ PRM1 / deh
⇒
The yellow LED on the RF expansion module
lights up briefly to acknowledge successful logon
of the DOW 1171 to the RF expansion module.
⇒
The green LED flashes slowly, indicating that
FK 100 LSN has started system configuration.
⇒
Following successful system configuration, the
green LED lights up permanently, indicating that
the radio cell is in standard mode.
.
The message “Detector exchange complete” is
displayed on WinPara!
D
Any detector faults that are shown on the con-
trol panel display after exchange should be re-
set!
6.3. Displaying the radio cell B - channel
The B - channel of a radio cell can only be displayed using the
programming software program WinPara.
D
In WinPara, enter “Model 10” in the input field under “Peripheral control” in the
“Read out dynamic data” menu under “Others”
⇒
The B - channel is specified under “Data” in the display .
.
Radio channels and assignment sequences for initial set - up of an FK 100 LSN:
79, 5, 9, 13, 17, 23, 59, 63, 65, 71, 75, 1, 47, 32, 38, 42.
.
If the same B - channel with different sub - channels is used by two
FK 100 LSNs, it is necessary to set up one FK 100 LSN again! In the event of
radio interference with FK 100 LSN, the sub - channels are selected
automatically as the alternative frequency; dual assignment of a B- channel
is therefore not possible!
6.4. Reducing a radio cell (removing RF detectors)
An RF smoke detector can only be removed from an existing config-
ured radio cell, e.g. to reduce the detection range, via WinPara.
.
When one or several RF detectors have been removed, the radio cell must be
set up again, i.e. the remaining RF detectors for the radio cell must be logged
on again!
LED yellow
LED green