The coverage area is strongly dependent on the

material of the object to be monitored. Based on
practical experience, an effective radius of r = 5 m
applies to steel and iron-reinforced concrete.

F

r = 

F = 

r

r=

3/4

r= 4/4

r = 5m

2

1

1

Operating radius

2

Coverage area

Ideal coverage area

To achieve the ideal coverage, do the following:

• Install one detector for each plane (walls, floor, and

ceiling) of the protected area.

• Do not add the coverage from adjoining planes to the

comprehensive protection strategy.

Coverage area reduction

The operating radius and the coverage area can be

reduced by:

• Tightly sealed corners and edges

• Incorrect positioning

• Interstices

Parts included

Quanti

ty

Component

1

Seismic detector

1

Drilling template

3

Cable tie

Technical specifications

Electrical

Minimum operating voltage in

VDC

8

Maximum operating voltage in

VDC

16

Minimum current consumption in
mA

2.5

Maximum current consumption in
mA

3.5

Alarm current consumption in mA

5

Terminals

Alarm outputs, terminals 14, 15

Semiconductor relay

Opens on alarm and low voltage

Contact load in VDC/100 mA

30, ohmic load

Minimum series resistance in Ω

45

Alarm holding time in seconds

2.5

Electronic alarm output, terminal 12

Open collector alarm in VDC

0

Minimum short circuit strength in
VDC

16

Tamper surveillance, terminals 10, 11

Microswitch, cover and floor

Opens on sabotage

Contact load in VDC/100 mA

30

Anti-drilling foil in cover

Alarm when tamper

Test input, terminal 4

Low voltage in V

<1.5

High voltage in VDC

>3.5

Remote input, terminal 7

Low voltage in V

<1.5

High voltage in VDC

>3.5

Mechanical

Dimension in cm (H x W x D)

8.9 x 8.9 x 2.3

Color

White

Environmental

Minimum operating temperature

in °C

-40

Maximum operating temperature
in °C

+70

2 | ISC-SM-90 Seismic detector, 90m²