figure #3

step 5: 

Mount the self tapping saddle valve or code 

valve on either a cold or a hot water pipe. A side or 
top mount is best to avoid clogging from pipe 
sediment. Connect 1/4” O.D. tubing to the saddle 
valve. Copper tubing requires a brass compression 
nut and brass sleeve. Plastic tubing requires a brass 
insert inside the tubing, a plastic sleeve on the 
outside with a brass compression nut. See Figure 4.

Caution

Do not use plastic tubing on hot water or in 
contact with any hot plenum surface or duct. 
Installation of this saddle valve must meet or 
exceed local codes and ordinances.

1

2

2

3

4

5

COPPER

TUBING

PLASTIC

TUBING

figure #4

step 6: 

Connect 1/4” water supply tube to brass 

filter at inlet of solenoid. See Figure 5.

Caution

Do not use plastic tubing on hot water or in 
contact with any hot plenum surface or duct. If 
using plastic tubing, use tube support and plastic 
compression sleeve.

figure #5

sTeP 7: 

Replace the evaporator pad with the drain 

pan and distributor trough attached. Ensure that the 
drain pan is on the bottom and that the spout aligns 

with the outlet in the cabinet. The evaporator pad 

assembly can only be installed in one direction. 
Ensure that the notch at the top in the distributor 

trough goes in first. Do not force the evaporator pad 

assembly. If it does not go in easily, it might be 
backwards.

sTeP 8:

 Replace the humidifier cover, ensuring that 

both tabs snap into place.

step 9: 

Turn damper knob to the “winter” (open) 

position. Turn on water supply and check operation 

of humidifier. Set humidistat to a demand setting. 

(See Humidistat section for installation and 

settings) With the air handler off, the solenoid valve 

should be closed. Start the air handler, the solenoid 

valve should open when the blower motor is 
energized. Check flow of water through distributor 
trough and evaporator pad. The standard yellow 
orifice will supply approximately 3.5 GPH of water at 
a line water pressure of 60 psi. For low water 
pressures (20-40 psi) a larger orange orifice (P/N 
7738002989) is available to provide the same flow. 
Leave humidistat set at the recommended setting.
Connect drain hose to 1/2” spout on humidifier 
cabinet using hose clamp. Run 1/2” hose to suitable 
drain such as floor drain, sewer or laundry sink. Be 

sure hose has continuous slope and is not kinked at 
any point.

4  IaQ series 

Installation

Summary of Contents for HUMBLBP-17H6--A

Page 1: ...Installation and Maintenance Manual IAQ Series HUMBSBP 12H6 A HUMBLBP 17H6 A 6 720 220 343 Revised 07 12 FLOW THROUGH BYPASS HUMIDIFIER FOR INSTALLATION ON A VERTICAL PLENUM SURFACE OF ANY air Handler ...

Page 2: ... Air Wall Base 6 Duct Mounting on the Return Air Duct Base 6 HUM TST H A Calibration Instructions 7 Wiring 7 Checkout 7 Settings 7 Care and Maintenance 7 How the Humidifier Works 8 Humidifier Packaged Component Accessories 8 Contact your local Bosch Dealer or Installing Contractor for product support 8 Heat Pump Wiring Diagram 9 Alternate Electrical Control Connections 10 Parts List for Humidifier...

Page 3: ...abs on the top and bottom exposing the humidifier evaporator pad Remove the evaporator pad drain pan and distributor trough all of this should come out as one piece Step 2 The BOSCH humidifier may be installed on either the supply or return plenum of a forced air handling system Select a location for the humidifier that allows for service and maintenance Cut out a rectangle Extend horizontal cente...

Page 4: ...tom and that the spout aligns with the outlet in the cabinet The evaporator pad assembly can only be installed in one direction Ensure that the notch at the top in the distributor trough goes in first Do not force the evaporator pad assembly If it does not go in easily it might be backwards STEP 8 Replace the humidifier cover ensuring that both tabs snap into place Step 9 Turn damper knob to the w...

Page 5: ...se foam tape to prevent drafts from affecting the humidistat operation See Figure 6 3 Squeeze the top and bottom of the base to release the face of the humidistat 4 Mount the base horizontally over the wires Attach directly to the wall using the two screws provided in the slotted holes HUMIDITY CONTROL Humidistat HUMB TST A A n INSTALLER Leave owner s manual with home owner SAFETY n Improper elect...

Page 6: ...nting holes 4 Place the outer portion of the mounting gaskets on the plastic base and mount the base with four screws Low voltage wire may enter the humidistat under the gasket 5 Connect wires to terminals on the control assembly as shown in wiring diagrams Replace the face plate DUCT MOUNTING ON THE RETURN AIR DUCT BASE Humidistat dehumidistat versions recommended Caution Do not install the humid...

Page 7: ...ng s structure can cause loss of structural strength Condensation can also enable mold and mildew growth resulting in personal injury and damage to building structure and contents CARE AND MAINTENANCE Your humidifier is engineered to give helpful and trouble free humidification For maximum efficiency and to ensure the safe and proper operation of your humidifier the following cleaning procedures s...

Page 8: ... the warm air plenum through the humidifier and returned to the cold air plenum Moisture is evaporated to the air passing through the evaporator pad Minerals are not blown into the air stream as occurs in atomizing humidifiers they are left on the evaporator pad where a high percentage is carried off with the waste water When the humidifier is installed and operating no adjustments are necessary o...

Page 9: ...6 720 220 343 Revised 07 12 Subject to change without prior notice Primary Heat Pump Wiring Diagram IAQ Series 9 Primary Heat Pump Wiring Diagram ...

Page 10: ...SNSR 24V SOLENOID VALVE 24 V TRANSFORMER OUTDOOR TEMP SENSOR OUTDOOR TEMP SENSOR COMMON LEAD FURNACE C HI LO CURRENT SENSING RELAY MULTI SPEED BLOWER MOTOR HOT C 115v 60CY ON OFF SWITCH 24V SOLENOID VALVE 24V SOLENOID VALVE 24 V TRANSFORMER L1 C NO HOT L2 115v 60CY ON OFF SWITCH PRESSURE SWITCH 24 V TRANSFORMER HUMIDISTAT HUMIDISTAT WIRE JUMPER WIRE JUMPER 2 3 4 Manual Humidistat 1 To furnace cont...

Page 11: ...38002913 LBP 17 Pad Rail 7738002926 SBP 12 Pad Rail 7738002914 Distributor Trough 7738002915 Drain Pan 7738002917 LBP 17 Side Panel 7738002924 SBP 12 Side Panel 7738002918 Nozzle 7738002919 LBP 17 Cover 7738002925 SBP 12 Cover 7738002920 Spout 7738002921 Brass Insert Tube P102 Compression Sleeve Brass P101 Compression Nut Table 2 Bosch Humidifier Specifications Expected Humidity Performance Covera...

Page 12: ...ubject to change without prior notice Revised 07 12 12 IAQ Series Humidifier Dimensional Drawings Humidifier Dimensional Drawings Figure 6 HUMBSBP 12H6 A Dimensional Drawing Figure 7 HUMBLBP 17H6 A Dimensional Drawing ...

Page 13: ...r to CARE AND MAINTENANCE section of this manual to estimate a humidity setting for the home based on outside temperature No humidifier operation in ON position 1 Set thermostat to operate air handler in heating mode Operation may be necessary for system power 2 Check voltage at humidifier control terminals Voltage should be 20 30 VAC 3 Inspect humidifier wiring Refer to wiring diagrams DO NOT LEA...

Page 14: ...es not cover the following circumstances 1 Components or parts not provided by FHP 2 Components or parts on which the tags or nameplates have been removed altered or defaced 3 Scratches in or discoloration of finishes 4 Serviceable items and normal maintenance as required per the Installation and Maintenance Manual 5 The workmanship of any installer FHP disclaims and does not assume any liability ...

Page 15: ... PURPOSE FHP S SOLE OBLIGATION WITH RESPECT TO THE PRODUCT AND PURCHASER S EXCLUSIVE REMEDIES ARE SET FORTH IN THE FOREGOING LIMITED WARRANTY FHP SHALL NOT BE LIABLE FOR ANY INDIRECT PUNITIVE INCIDENTAL SPECIAL CONSEQUENTIAL OR SIMILAR DAMAGES INCLUDING WITHOUT LIMIITATION INJURY OR DAMAGE TO PERSONS OR PROPERTY OR DAMAGES FOR LOSS OF USE LOST PROFITS INCONVENIENCE OR LOSS OF TIME Caution Some sta...

Page 16: ...601 N W 65th Court Ft Lauderdale FL 33309 Phone 954 776 5471 Fax 954 776 5529 www bosch climate us ...

Reviews: