Troubleshooting
63
Greentherm T9900 SE/i – 6 720 813 635 (2019/03)
8.12.2 Manual Gas and Air Adjustment
Gas and Air adjustment is also possible to perform manually.
This is only recommended if the automatic adjustment process
is not possible to complete successfully.
To perform MA Manual Adjust of Gas/Air flow;
▶ After enter
CA Combustion Adjust
menu,
▶ Touch symbols
or
to select
MA
menu.
▶ Touch the symbol
to enter
MA
menu.
Fig. 59
Manual Adjust - MA
Access P1 menu (maximum power)
L1 Gas Adjust
▶ Touch the symbol
to enter
P1
menu.
Display shows
L1 Gas Adjust
.
Fig. 60
L1 Gas Adjust - Open Taps
▶ Open hot water taps when the display shows
Open Taps
.
The appliance will display
Open Taps
whenever more flow
is required to continue the automatic adjustment process
(1 tub and 2 sinks are usually sufficient).
Display shows
Output Power (%)
when there is enough
water flow.
1)
▶ Change
L1 Gas Adjust
parameter until reaches 100% ± 2%
▶ Increase
L1 Gas Adjust
parameter to increase output
power, and vice-versa.
How to enter a new tuning parameter (i.e. L1, L2, A1, A2).
▶ Select the desired parameter.
▶ Touch the symbol
.
The symbols
appears in the display.
▶ Change to the desired value.
▶ Touch the symbol
when finished.
The symbols
disappear.
▶
L1 Gas Adjust
is now complete.
A1 Air Adjust
▶ Touch symbols
or
until display shows
A1 Air
Adjust - ION
.
Fig. 61
A1 Air Adjust - ION
▶ Change
A1 Air Adjust
parameter until
ION
value is
according to table 25.
▶ Increase
A1 Air Adjust
parameter to decrease
ION
value
and vice-versa.
A1 Air Adjust
is now complete.
Table 25 P1 ION values
1) More flow may be required if inlet water temperature is
high, i.e. applications with waste water recovery system,
preheated solar water.
P1 maximum power
1)
1) For information on unit’s configuration (gas type: NG/LPG
and capacity: 160 000BTU/199 000BTU), see rating plate
(
199 000 BTU
160 000 BTU
Natural Gas
ION (A1 Air Adjust)
200 - 300
200 - 290
LP Gas
ION (A1 Air Adjust)
185 - 285
200 - 295