Heatronic boiler control settings
Greenstar – 6721822579 (2021/01)
56
11.2
Overview of the service functions
11.2.1 First service level (press and hold the service button
until it lights up)
Table 26 Service functions, 1st level
11.2.2 Second service level (at first service level, service button
lights up, press ECO button and key pad lock button
simultaneously until 8.A appears)
Table 27 Service functions, 2nd level
11.3
Description of the service functions
11.3.1 First service level
Service function 1.A: Maximum space heating output
Some gas supply companies offer a performance-dependent basic
price.
The output can be limited in percent between the minimum and
maximum nominal output to suit the specific heat demand.
Even if the heating output has been limited, the maximum nominal
output is still available for DHW generation.
▶ Select service function 1.A.
▶ Select heat output in MBH (kW) and determine associated setting in
percent (%).
▶ Enter the setting (
Chapter 10.1).
▶ Save the setting (
Chapter 10.1).
▶ Record the set heat output in the commissioning log (
▶ Exit the service functions.
The display returns to the supply temperature.
The
factory setting
is the maximum nominal output:
100
(100 %).
Service function
Display
Page
1.A
Maximum space heating output
1.b
Maximum DHW output
1.E
Pump mode for space heating operation
1.F
Pump mode
2.A
Heating circuit pump lockout time
2.b
Maximum supply temperature
2.C
Purging function
2.d
Thermal disinfection
2.F
Operating mode
3.A
Automatic anti-cycle function
3.b
Set anti-cycle time
3.C
Switching differential (hysteresis)
3.d
Minimum output (heating and DHW)
3.E
Cycle time, keeping DHW hot
3.F
Constant DHW period
4.b
Maximum heat exchanger temperature
4.d
Audible fault warning tone
4.E
Appliance type
4.F
Condensate trap filling sequence
5.A
Reset inspection interval
5.b
Fan post purge time
5.E
Functionality of black plug in boiler
junction box
5.F
Set inspection interval
6.A
Display the latest fault code
6.b
Room temperature control, current voltage,
terminal 2
6.C
Supply temperature required by outdoor reset
control
6.d
Current DHW turbine flow rate
7.A
Indicator lamp for burner operation / faults
7.b
3-way valve in center position
7.d
Connecting an external supply or low-loss header
temperature sensor
7.E
Building drying function
0.A
Do not use this setting!
0.d
Altitude adjustment
0.E
Metric or US customary units
Service function
Display
Page
8.A
Software version
8.b
Code plug number
8.C
GFA Gas burner control status
a
a. GFA: Gas burner control unit
8.d
GFA fault
8.E
Restore boiler to factory settings
8.F
Permanent ignition
9.A
Constant mode
9.b
Current fan speed
9.C
Current boiler output
9.d
Set fan start speed
9.E
Turbine signal delay
9.F
Heating zone pump post purge
A.b
Display DHW temperature
A.C
Display DHW tank temperature
b.F
Solar DHW backup heating delay
C.d
Display current heat demand