Installation and connection
en
23
Technical specifications
Refrigerant, cubic capacity and further
technical specifications can be found on
the rating plate.
"Getting to know your appliance"
Installing the appliance
Installation location
The more refrigerant an appliance
contains, the larger the room must be
in which the appliance is situated.
Leaking refrigerant can form
a flammable gas-air mixture in rooms
which are too small.
The room must be at least 1 m³ per 8 g
of refrigerant. The amount of refrigerant
in your appliance is indicated
on the rating plate inside the appliance.
"Getting to know your appliance"
The weight of the appliance may be up
to 40 kg depending on the model.
Permitted room temperature
The permitted room temperature
depends on the climatic class of the
appliance.
Information on the climatic class can be
found on the rating plate.
"Getting to know your appliance"
The appliance is fully functional within
the permitted room temperature.
If an appliance of climatic class SN is
operated at colder room temperatures,
the appliance will not be damaged up to
a room temperature of +5 °C.
Cavity depth
A cavity depth of 56 cm
is recommended for the appliance.
If the cavity depth is smaller – at least
55 cm – the energy consumption
increases slightly.
Side by-side installation
It is only possible to install appliances
side by side with a gap of at least
15 cm.
Over and under installation
You can install an additional refrigerator
above your appliance.
Climatic cate-
gory
Permitted room temperature
SN
+10 °C ... 32 °C
N
+16 °C ... 32 °C
ST
+16 °C ... 38 °C
T
+16 °C ... 43 °C