This Wiring Guide shows how peripheral devices are connected to the fire panel.
Peripheral devices that are no longer included in the product range are covered in "Part 2 -
Discontinued Products" of the Wiring Guide.
Notice!
The connections laid out in this document also apply to the FPA-1200 Fire Panel, provided
that the individual components are Bosch Sicherheitssysteme GmbH approved extensions of
the FPA-1200 Fire Panel.
Notice!
The LSN 0300 connections laid out in this document also apply to the LSN 1500 module.
Product Information
–
You can find installation instructions for the individual components of the fire panel in the
enclosed Installation Manual.
–
More information is available on the Internet at: www.boschsecurity.com
Important Notes
–
Only use installation materials as recommended by Bosch Security Systems.
–
Only perform conversion and soldering work wearing a grounding wrist strap.
–
Assembly and installation must only be performed by qualified personnel.
–
Note connection criteria of the regional authorities/institutions.
Danger!
Touching live components can be fatal.
Disconnect the power supply before carrying out installation.
Notice!
If a cable shield wire for the LSN cable has to be connected, then proceed according to LSN
specifications.
- Connect LSN cable shield on panel side to designated functional earth connector. The shield
of both sides (start and end) of the loop must be connected to the panel
- Loop through cable shield at all LSN peripheral devices using provided terminals
- No additional connection of LSN cable shield is permitted, neither to earth connectors at
any location nor to other electrical potential
User Notes
The wiring guide is structured as follows:
–
Chapter Wiring, page 18 is sorted by the device to which a peripheral device is
connected. A wiring shows the direct connection of one device to another device (no
cascading connections). Usually, shielding is not shown in the wirings. The sample wiring
below demonstrates the shielding.