FMM-7045, FMM-7045-D 

|

 

Installation Instructions | 3.0 Specifications 

 

Bosch Security Systems, Inc. | 8/06 | F01U001402C 

 

2.3

 

Wiring 

 

Make sure all power is removed before 
making any electrical connections. Failure 
to do so may result in personal injury and/or 
damage to equipment. 

Run all wires and make all connections before 
mounting the FMM-7045/FMM-7045-D. All wiring is 
supervised and power limited. See 

Figure 2

 for details. 

 

 

Do not loop wire around each terminal. 
Break terminal wire connections for 
supervision. 

 

Figure 2: 

Wiring the FMM-7045 

4

L

o

o

p
+

L

o

o

p
-

HUNDREDS

0

1

2

X X X

TENS

ONES

0

5

1

2

3

4

6

7

8

9

0

5

1

2

3

4

6

7

8

9

1

2

3

2

3

2

0

1

1 -  Previous device or D7039/DS9431 

2 -  Loop (+) 

3 -  Loop (-) 

4 -  Other devices 

 

2.4  

Mounting 

The FMM-7045/FMM-7045-D mounts to a 3 in. x 2 in. 
x 3½ in. device box (like a Steel City CXW) or a 4 in. 
x 2 1/8 in. square box with a 5/8 in. mud ring (like the 
Steel City 52171 box and 52-C-14-5/8 mud ring) with 
the two provided screws. The multiplex single zone 
input module should easily fit inside.  

The back plate mounting holes on the FMM-
7045/FMM-7045-D can be accessed by opening the 
key lock on the unit. 

 

The FMM-7045/FMM-7045-D Pull Stations 
are for indoor use only. If a pull station is 
needed for outdoor use or in an unheated 
area, an FMM-100 Series Pull Station rated 
for the environment should be wired to a 
multiplex module within the interior of the 
building. 

3.0 Specifications 

Table 1: Specifications 

 

Panel 
Programming 
Type 

Single Point 

Control Panel 
Requirements 

D7024 or DS9400 Series FACP (with 
ROM version 2.0 or greater and a 
D7039 or DS9431 Multiplex Expansion 
Module installed). Refer to the 

D7024 

Operation and Installation Guide

 (P/N: 

31499) or the 

DS9400M/DS9400i 

Installation Guide

 (P/N: 44578) for 

specific programming information. Refer 
to the 

D7039 Installation Instructions

 

(P/N: 38685) or the 

DS9431 

Installation Instructions

             (P/N: 

41831) for multiplex wiring information. 

Multiplex Bus 
Average Current 
Draw 

Alarm: 0.55 mA 

Standby: 0.55 mA 

Optional 
Equipment 

Replacement Glass Break Rods (FMM-
100GR) 

Operating 
Temperature 

+32°F to +120°F (0°C to +49°C) non-
condensing RH 

Listings and 
Approvals 

UL864 

CSFM 

Nominal Bus 
Voltage 

12 VDC 

 

 

 