Conventional Automatic Detectors
Planning Notes | en
9
Bosch Sicherheitssysteme GmbH
Operation Guide
2019.11 | 5.0 | F.01U.003.962
2
Planning Notes
Notice!
The 500 Series detectors are approved for indoor use only.
–
Country-specific standards and guidelines must be observed during the planning phase.
–
The FCP‑OC
500, like the FCP‑O
500, is planned according to the guidelines for optical
detectors (refer also to EN
54 and VDS
2095).
–
A hemispherical space
(1)
with a radius of 50
cm must remain free below the detector
(2)
.
Care must be taken to ensure that no people, larger animals, plants, opening doors or any
objects intrude into this area and that no parts of the detector surface become covered.
1
5
0
c
m
2
Figure
2.1: Radius
–
The detector may only be installed in a position which is out of arm's reach.
Minimum installation height recommended: 2.70
m.
–
The 500 Series Detectors may not be installed in rooms with data transmission by means
of high-intensity infra-red light (e.g. in rooms with IR systems for interpreters).
–
The detectors must be mounted so that they are not exposed to any direct sunlight.
–
A minimum distance of 50
cm from lamps must be maintained.
The detectors may not be mounted in a cone of light from lamps.
–
Maximum permitted air speed: 20
m/s.