Terminate Remote Accessories as indicated above (if required).

This is not a self-contained stand alone detector.

A U.L. Listed Analog Addressable Fire System is required.

ANALOG ADDRESSABLE

FIELD LOOP WIRING

REMOTE TEST

SWITCH

(Test function only.  does not reset.)

REMOTE

ALARM

LED

6

III. ELECTRICAL INSTALLATION, continued

OBSERVE POLARITY

INPUT VOLTAGE

24 V.D.C.

S (+)

SC (-)

UL LISTED

CONTROL PANEL

A.A.

CONTROL

PANEL

ADDRESSABLE

LOOP

1

2

+

-

REMOTE

PILOT LED

10 mA Standby

55mA Alarm

3

4

+

-

+

5

FAD-325-R/FAD-325-V2F-R WIRING DIAGRAM

FAD-325/FAD-325-V2F WIRING DIAGRAM

The FAD-325, FAD-325-V2F, FAD-325-R and

FAD-325-V2F-R are not self-contained sensors.

 

This product is compatible only with fire alarm

control panels that utilize BOSCH's Digital
Communications Protocol, DCP.
For example the FPA-1000 Family of Control Panels

D. WIRING DIAGRAMS, continued

U

LI

S

TE

D

C

O

N

TR

O

P

A

N

EL

LO

O

IN

TE

R

FA

C

E

S (+)

SC (-)

SUPPLY VOLTAGE

TO NEXT SENSOR

OR RETURN
TO CONTROL PANEL

ALARM CONTACTS

10.0A @ 250VAC

NC

ALARM CONTACTS

10.0A @ 250VAC

NO

NC

C

7

8

9

10

NO

C

12

11

THE D304 REMOTE ALARM LED
WIRING MUST HAVE POLARITY AS

SHOWN 24 VDC (8mA MAX.)

-R

+R

L2

L1

FAN SHUTDOWN EXAMPLE

4

2

1

3

(-)

FAN

TO

 N

EX

T

S

EN

S

O

R

(+)

FAD-325-DH/FAD-325-V2F-DH

ANALOG SENSOR

Remote common alarm indication, remote pilot indication, remote common reset, common shutdown and common visual indication.

*  

Common fault indication (when green pilot LED is extinguished) cannot be achieved on the FAD-325 Duct Units.  Individual Remote

Pilot LED's must be installed to monitor detector head or power source removal for each unit.

In the event of an alarm, the detector head and duct unit alarm (Red) LED's will be illuminated.  All remaining duct unit alarm LED's will
not be illuminated. All remote alarm LED's fitted to the duct units will be illuminated when any of the units go into alarm.  Only the duct
unit in alarm will permit resetting of the system from the built in test/reset switch on that particular duct unit.

A common Remote reset switch will reset all detectors.

Common functions include one or all of the following:

BOSCH Security Systems, Inc.  *  FAD-325 Installation Instructions (HA-06-184. P/N 1700-11140 Page 2 of 2)

Specifications subject to change without notice. * February 2017

The Bosch D304/D305 Remote Duct Annunciator and the Bosch
FAD-325-R/FAD-325-V2F-R Duct Detectors are compatible when
wired as the following.

STANDBY 350µA

ALARM 800µA