Terminate Remote Accessories as indicated above (if required).
This is not a self-contained stand alone detector.
A U.L. Listed Analog Addressable Fire System is required.
ANALOG ADDRESSABLE
FIELD LOOP WIRING
REMOTE TEST
SWITCH
(Test function only. does not reset.)
REMOTE
ALARM
LED
6
III. ELECTRICAL INSTALLATION, continued
OBSERVE POLARITY
INPUT VOLTAGE
24 V.D.C.
S (+)
SC (-)
UL LISTED
CONTROL PANEL
A.A.
CONTROL
PANEL
ADDRESSABLE
LOOP
1
2
+
-
REMOTE
PILOT LED
10 mA Standby
55mA Alarm
3
4
+
-
+
5
FAD-325-R/FAD-325-V2F-R WIRING DIAGRAM
FAD-325/FAD-325-V2F WIRING DIAGRAM
The FAD-325, FAD-325-V2F, FAD-325-R and
FAD-325-V2F-R are not self-contained sensors.
This product is compatible only with fire alarm
control panels that utilize BOSCH's Digital
Communications Protocol, DCP.
For example the FPA-1000 Family of Control Panels
D. WIRING DIAGRAMS, continued
U
L
LI
S
TE
D
C
O
N
TR
O
L
P
A
N
EL
LO
O
P
IN
TE
R
FA
C
E
S (+)
SC (-)
SUPPLY VOLTAGE
TO NEXT SENSOR
OR RETURN
TO CONTROL PANEL
ALARM CONTACTS
10.0A @ 250VAC
NC
ALARM CONTACTS
10.0A @ 250VAC
NO
NC
C
7
8
9
10
NO
C
12
11
THE D304 REMOTE ALARM LED
WIRING MUST HAVE POLARITY AS
SHOWN 24 VDC (8mA MAX.)
-R
+R
L2
L1
FAN SHUTDOWN EXAMPLE
4
2
1
3
(-)
FAN
TO
N
EX
T
S
EN
S
O
R
(+)
FAD-325-DH/FAD-325-V2F-DH
ANALOG SENSOR
*
Remote common alarm indication, remote pilot indication, remote common reset, common shutdown and common visual indication.
*
Common fault indication (when green pilot LED is extinguished) cannot be achieved on the FAD-325 Duct Units. Individual Remote
Pilot LED's must be installed to monitor detector head or power source removal for each unit.
*
In the event of an alarm, the detector head and duct unit alarm (Red) LED's will be illuminated. All remaining duct unit alarm LED's will
not be illuminated. All remote alarm LED's fitted to the duct units will be illuminated when any of the units go into alarm. Only the duct
unit in alarm will permit resetting of the system from the built in test/reset switch on that particular duct unit.
*
A common Remote reset switch will reset all detectors.
Common functions include one or all of the following:
BOSCH Security Systems, Inc. * FAD-325 Installation Instructions (HA-06-184. P/N 1700-11140 Page 2 of 2)
Specifications subject to change without notice. * February 2017
The Bosch D304/D305 Remote Duct Annunciator and the Bosch
FAD-325-R/FAD-325-V2F-R Duct Detectors are compatible when
wired as the following.
STANDBY 350µA
ALARM 800µA