Release Notes for Firmware V2.07 | 7.0 

Fixed Items Since Firmware Version 1.08 

 

Bosch Security Systems | 8/06 | 36925V 

 

 

Manual Battery/NAC Test during AC Fail:

 

Manually initiating a battery test (Test Menu, 
Option 4) when AC has failed will now correctly 
display the current battery voltage. However, if 
a user at the control panel requests a manual 
battery test within five seconds after AC power 
fails, the system may shut down until AC power 
returns. Manual battery test while AC is present 
will correctly test and report the battery voltage, 
and a manual test when AC power has failed 
will report the current battery voltage. 

 

Improved Smoke Power Control 
Monitoring:

 When AC power fails, the control 

panel draws from the batteries to maintain 
operation. When the battery voltage falls below 
20 volts, the control panel will shut down. 
Panels with date codes after 9935 will power 
down, and control panels modified according to 
Technical Service Note P/N: 42363 will enter a 
low power idle state. To ensure that all attached 
smoke detectors are correctly powered up after a 
shutdown, the control panel will wait for the 
smoke power voltage to stabilize before applying 
smoke power and continuing operation. 
To ensure that power is applied cleanly to the 
smoke detectors, smoke power is now turned off 
if it falls below 15 volts and not restored until it 
reaches 20 volts. 

 

Improved Battery Monitoring:

 Processing of 

restored batteries has been improved so that a 
RESET operation is never required. 

 

Local Only Points Implemented:

 Central 

station reporting is now correctly suppressed for 
points programmed for “Local Only” operation. 

 

Response Time After Transients:

 Firmware 

prior to version 2.02 may allow an extended 
alarm response time after an electrical transient 
(e.g. lightning). In the worst case, an alarm 
occurring 10 minutes after a transient would 
take 10 minutes to be registered. After 10 
minutes, the response time returns to normal. 
With version 2.02 firmware, response time 
correctly remains at 500 ms for fast response, or 
at the desired programmed response time for 
programmed response points, regardless of 
possible prior transients on the line. This issue 
was observed during recent lab testing of the 
control panel and has not been reported from 
actual installations, but upgrading the firmware 
in installed control panels to version 2.02 will 
assure proper response time under all 
circumstances. 

 

Programming Access:

 Firmware version 2.02 

corrects a configuration problem found in 
control panels with prior firmware that 
improperly allows programming access to all 
valid user codes and not only “Level 
1/Maximum” codes. 

 

Phone Troubles:

 On a small number of 

DS9400 units, when using firmware prior to 
version 2.02, an interaction between normal 
hardware variations and firmware timing has 
been observed to cause the control panel to 
falsely report a disconnected phone line. On the 
small number of control panels with the affected 
hardware, the fault causes occasional phone 
trouble reports that are followed by an 
immediate restoral report. Replacing the ROM 
to upgrade the firmware to version 2.02 corrects 
the problem with no need for hardware 
modifications. 

 

User Interface Delay:

 Under unusual 

circumstances, the user interface in firmware 
prior to 2.02 would stop accepting input for up 
to three minutes if remote keypads were present 
on a system. This no longer occurs in version 
2.02. 

 

Relay Module Operation, Disabling:

 Remote 

relay modules may fail to activate properly 
under some circumstances in firmware versions 
prior to 2.02. Additionally, attempting to disable 
remote relays has caused the control panel to 
stop operating and freeze the display. The relay 
modules operate and can be disabled as 
expected in version 2.02. Note that when a 
remote relay module is disabled, all eight relays 
on the module are disabled with one operation. 

 

Auto Silence Clarification:

 When configuring 

points and NACs for auto silence, the setting on 
each NAC to enable or disable the auto silence 
feature is not implemented. Setting the timer to 
a value other than zero (0) enables the auto 
silence feature. Any NAC that can be silenced 
(based on which inputs are in alarm) will be 
silenced when the auto silence timer completes, 
regardless of the setting selected for the 
individual NACs. Additionally, a NAC activated 
by a non-latching point will not automatically 
turn off when the point restores if there is any 
other off-normal condition on the control panel. 
It must be manually reset. 

Summary of Contents for DS9400 Series

Page 1: ...EN Release Notes for Firmware V2 07 Fire Alarm Control Panel DS9400 Series ...

Page 2: ...grade Information If this firmware is installed in a control panel that has been running version 1 x software it is necessary to erase the old programming in the control panel and re select the control panel type when the control panel is first powered up Be careful to select 1 DS9400 an incorrect selection cannot be undone 3 0 Fixed Items in Firmware Version 2 05 Version 2 05 firmware for the DS9...

Page 3: ... two on board relays is programmed using Zone 62 General Trouble For this output the relay will be energized when there are no troubles present in the system When there is a trouble the relay will de energize For this relay to function properly Zones B C and D must be programmed with a value of 00 The General Trouble output function can not be combined with any other output function When communica...

Page 4: ...1 after installing firmware version 2 03 please contact Technical Support at 888 886 6189 DS9434 Four Point Expander Removal To prevent the accidental removal of the DS9434 a new message CALL FOR SERVICE is displayed If you wish to remove a previously installed DS9434 please contact Technical Support at 888 886 6189 7 0 Fixed Items Since Firmware Version 1 08 AC Failure during Automatic Battery Te...

Page 5: ...ents on the line This issue was observed during recent lab testing of the control panel and has not been reported from actual installations but upgrading the firmware in installed control panels to version 2 02 will assure proper response time under all circumstances Programming Access Firmware version 2 02 corrects a configuration problem found in control panels with prior firmware that improperl...

Page 6: ...emoval of DS9431 Multiplex Expansion Module Clears PINs If the DS9431 Multiplex Expansion Module is installed and then removed all Personal Identification Numbers PINs including the standard 16 PIN numbers will be erased when the DS9400 is re powered The PIN numbers can be re entered normally User ID Report for Drill and Walk Test As shown in Appendix C of the DS9400M Reference Guide P N 31499 or ...

Page 7: ...one number or account number for phone number 2 while routing reports to line 1 backup line 2 If only one phone number is available for reporting set report steering for all events to phone 1 only Comm fault may also be caused if one of the phone lines has Telco battery voltage but will not complete a call Make test calls to the receiver s on both phone lines listening for the receiver ACK tone 6 ...

Page 8: ... 2006 Bosch Security Systems 36925V Bosch Security Systems 130 Perinton Parkway Fairport NY 14450 9199 Customer Service 800 289 0096 Technical Support 888 886 6189 ...

Reviews: