DS7461i Installation Guide

Remove the cover of the DS7461i. Press in and up with your thumb and nail directly above the lip of the DS7461i (refer to  

Figure 1

).

Figure 1: Removing the Cover

Remove the DS7461i circuit board from the base. Press the circuit board retainer tab and pull the circuit board up and out of the base
(refer to 

Figure 2

).

Wire

Entrance

Terminal Strip

Circuit Board
Retainer Tab

Reed Switch

Address

Switches

1  2  3  4  5  6  7  8

O
N

Tamper

Switch

Figure 2: Removing the PCB

Handle this and all circuit boards carefully. Hold the board by its edges.

Route the wiring through the wire entrance of the DS7461i base.

Mount the DS7461i base to the mounting surface using the supplied screws.

Return the DS7461i circuit board to the base.

5.0 Wiring

DS7461i Terminals 

Description 

Bus + 

Positive Multiplex Input 

Bus - 

Negative Multiplex Input 

Input Zone Positive Input 

G

Input 

Zone 

Ground

Table 1: DS7461i Terminal Descriptions

Connect wiring to the DS7461i as shown in 

Figure 3

 and 

Figure 4

.

Input zones are designed to monitor Normally Open or Normally Closed dry contacts. They are supervised using 47K ohm end-of-
line resistors.

The protection zone can be used as a magnetic contact by mounting a magnet iwith the reed switch and removing the EOL
resistor for the protection zone. The protection zone cannot be used as a magnetic contact and used to monitor other
contacts at the same time.

If the reed switch is not being used, cutting it from the DS7461i circuit board prevents possible tampering to override Zone 1
operation.

For fire installations, order Multiplex Fire Zone EOL P/N 28010 in the quantity needed.

The input zones are power limited and supervised.

When used in fire applications, Normally Open contacts must be used on the input zones.

Summary of Contents for DS7461i

Page 1: ...AWG 76 m 0 65 mm 193 m 1 02 mm Fire applications require 18 AWG Operating Temperature Range 32 F to 122 F 0 C to 50 C Relative Humidity 0 to 93 Signaling Line Circuit Class B Initiating Circuit Class B When used in a fire system NFPA 72 prohibits this product from sharing a communications bus with non fire devices 3 0 Programming Refer to the control panel s installation guide for multiplex zone p...

Page 2: ...461i Terminals Description Bus Positive Multiplex Input Bus Negative Multiplex Input 1 Input Zone Positive Input G Input Zone Ground Table 1 DS7461i Terminal Descriptions Connect wiring to the DS7461i as shown in Figure 3 and Figure 4 Input zones are designed to monitor Normally Open or Normally Closed dry contacts They are supervised using 47K ohm end of line resistors The protection zone can be ...

Page 3: ... D8125 Multiplex Module POWER A MUX BUS A POWER B MUX BUS B Either Bus A or Bus B or both may be used Refer to the panel s reference guide DS7461i Ground Zone 1 Multiplex Bus Multiplex Bus N C N O Use 47K ohm EOL P N 26069 for non fire applications Use 47K ohm EOL P N 28010 for fire applications Alarm Contact Normally Open or Normally Closed Figure 5 Wiring to a D8125MUX Multiplex Expansion Module...

Page 4: ... SWITCH NUMBER SWITCH ON CLOSED 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 1 2 3 4 5 6 7 8 ZONE POINT ADDRESS SWITCH NUMBER SWITCH ON CLOSED 193 194 195 196 197 198 199 200 201 202 203 20...

Reviews: