background image

 

 

© 2011 Bosch Security Systems, Inc. 
130 Perinton Parkway, Fairport, NY  14450-9199 USA 
www.boschsecurity.com 

F01U252565-01 
Installation Guide 

9/11

DS150i/DS151i

Page 2 of 4

 

3.2 

EMF (Voltage) Spike-Protected Relay 

Pins 6 through 8 (wire colors gray, green, and orange) comprise the EMF 
spike-protected relay. Refer to 

Figure 3. 

Use this relay when connecting inductive loads to the detector. This relay 
protects the detector from inductive loads that might deliver damaging 
EMF spikes. 

3.3 

Non-EMF (Voltage) Spike-Protected Relay 

Pins 3 through 5 (wire colors yellow, violet, and blue) comprise the non-
EMF spike-protected relay. Refer to 

Figure 3. 

This relay is best used for non-inductive loads. When connecting an 
inductive load that is not spike-protected, such as a magnetic door lock, to 
the detector, use either a bridge rectifier (such as a KBL01) or a diode 
(such as a 1N4007). Failure to use a bridge rectifier/diode may reduce the 
lifetime of the relay. Refer to 

Figure 5.

 

 

Figure 5: Wiring the Bridge Rectifier 

S
S

DS150i

Relay Contact

(non-spike protected)

Inductive

Load

KBL01

Bridge Rectifier

Power

Supply

+

+

-

Power

Supply

Inductive

Load

1N4007

Diode

+

-

OR

DS150i

Relay Contact

(non-spike protected)

 

UL 1034 listed magnetic locks typically are already EMF 
spike-protected, and therefore do not require the bridge 
rectifier or diode as shown in 

Figure 5

. Adding a bridge 

rectifier/diode to an EMF spike-protected device can cause 
unwanted delays in response. Refer to the magnetic lock’s 
documentation for more information. 

 

4.0 Configuration 

Use the on-board DIP switches to configure the operation of the detector. 
Refer to 

Figure 6

 for proper switch positioning. 

 

Figure 6: DIP Switch ON/OFF Positions 

ON

DIP

ON

ON

ON

OFF

 

4.1 

Resettable/Non-resettable Timer Selection 

DIP Switch 1 determines if the relay resets at the end of latch time, or if 
latch time is extended by additional motion. Refer to 

Table 1

 and 

Figure 6 

for more information. 

 

Resettable: 

The relay activates when the detector first sees motion. 

Any additional motion restarts the latch timer so the relay deactivates 
only when the detector no longer sees motion and the latch time has 
expired. 

Hint: 

This setting works best when bypassing a 24-hour 

contact. 

 

Non-resettable: 

The relay activates when the detector first sees 

motion. It deactivates when the latch time ends, even if motion is still 
present. 

Hint: 

This setting works best when used with an access 

control system. 

 

Table 1: Resettable/Non-resettable DIP Switch Settings 

Switch 1 

Function 

OFF Non-resettable 

ON 

Resettable 

(Default)

 

4.2 Relay 

Mode 

DIP Switch 2 selects the relay mode. This allows you to select a fail safe 
by default, or a fail secure mode. Refer to 

Table 2

 and 

Figure 6 

for more 

information. 

 

Fail Safe:

 In the event of a power loss, the REX detector releases 

the device connected to it (for example, magnetic door lock or 
electric door strike). 

 

Fail Secure:

 In the event of a power loss, the REX detector does not 

release the device connected to it (for example, magnetic door lock 
or electric door strike). 

In Fail Secure mode, the REX detector shall be installed in a manner 
that does not impair the intended operation of panic hardware used 
in conjunction with the REX detector. 

Failure Secure mode must be authorized by the local Authority 
Having Jurisdiction (AHJ). 

 

Table 2: Relay Mode DIP Switch Settings 

Switch 2 

Function 

OFF Fail 

Secure 

ON  

Fail Safe 

(Default)

 

 

Refer to Figure 4 relay wiring options. 

4.3 Led 

Enable/Disable 

DIP Switch 3 selects whether the on-board LED is enabled or disabled. If 
enabled, the LED operates normally when motion is detected. 

 

Table 3: LED Enable/Disable DIP Switch Settings 

Switch 3 

Function 

OFF Disabled 

ON  

Enabled (Default) 

 

When LED is enabled, it will flash on and off when first 
powered up. Once the flashing LED stops, the REX is 
ready to be used. 

4.4 Latch 

Time 

DIP Switches 4, 5, and 6 set the relay latch time. Latch time is adjustable 
from 0.5 sec to 64 sec. It indicates the amount of time the relay can 
remain active after the detector first sees motion. 

 

Table 4: Latch Time DIP Switch Settings 

Time (sec) 

Switch 4 

Switch 5 

Switch 6 

0.5 (Default) 

OFF 

OFF 

OFF 

OFF 

OFF 

ON 

2 OFF 

ON 

OFF 

OFF 

ON 

ON 

ON 

OFF OFF 

16 

ON 

OFF 

ON 

32 

ON ON 

OFF 

64 

ON 

ON 

ON 

 

Summary of Contents for DS150I

Page 1: ...cover a single gang box Where aesthetics are important mount it using the optional trimplate TP160 or TP161 Refer to Figure 1 for additional instructions for mounting with the trimplate Figure 1 Optional Trimplate DOOR DOOR DS150i DS151i Optional Trimplate TP160 TP161 Gang box The arrows on the base indicate its correct mounting orientation relative to the door The mounting height range is from 7 ...

Page 2: ... additional motion restarts the latch timer so the relay deactivates only when the detector no longer sees motion and the latch time has expired Hint This setting works best when bypassing a 24 hour contact Non resettable The relay activates when the detector first sees motion It deactivates when the latch time ends even if motion is still present Hint This setting works best when used with an acc...

Page 3: ...efer to Figure 7 The masking wedges eliminate zones A B K and L Figure 7 Pattern Masking Testing Test the detector a minimum of once each year to ensure continued operation 7 0 Coverage Figure 8 and Figure 9 show the standard patterns for a wall mounted unit Figure 8 Standard Patterns for a Wall mounted Unit 3 0 1 5 0 3 0 1 5 Meters 0 5 Feet 10 5 0 5 10 Feet Meters 0 1 5 Pointed 14 D F H J I C E G...

Page 4: ...rference from foreign objects by masking out the inside zones K L on one detector A B on the other detector Refer to Figure 10 Figure 10 Masking a Dual Mount Push to Exit Alarm will Sound Push to Exit Alarm will Sound E F C D A B G H E F C D A B K L I J K L G H I J 8 4 Regulatory Notes The unit shall be installed in accordance with National Electrical Code ANSI NFPA 70 and part 1 of the Canadian E...

Reviews: