22
en | Rack installation
DIVAR IP 7000 (3U)
2016.08 | V2.1 | DOC
Installation Manual
Bosch Sicherheitssysteme GmbH
1
2
3
4
To install the outer rails to the rack:
1.
Press upward on the locking tab at the rear end of the middle rail.
2.
Push the middle rail back into the outer rail.
3.
Hang the hooks on the front of the outer rail onto the square holes on the front of the
rack. If desired, use screws to secure the outer rails to the rack.
4.
Pull out the rear of the outer rail, adjusting the length until it just fits within the posts of
the rack.
5.
Hang the hooks of the rear section of the outer rail onto the square holes on the rear of
the rack. Take care that the proper holes are used so the rails are level. If desired, use
screws to secure the rear of the outer rail to the rear of the rack.
6.
Repeat for the other outer rail.
4.3.5
Installing the chassis in the rack
!
Warning!
Stability hazard
Before sliding the unit out for servicing make sure that the rack stabilizing mechanism is in
place, or the rack is bolted to the floor. Failure to stabilize the rack can cause the rack to tip
over.
!
Warning!
Do not pick up the unit with the front handles. The handles are designed to pull the system
from a rack only.
Notice!
Mounting the chassis into the rack requires at least two people to support the chassis during
installation. Please follow safety recommendations printed on the rails.
Notice!
Figures are for illustrative purposes only. Always install chassis into racks from the bottom
up.