Operation and Installation Guide | Appendix C: Fire Communicator Report
Summary
.
Bosch Security Systems, Inc. | 3/13 | F01U071094-0
7
59
Fault
Restoral
System
Trouble
Programming
IA 11
Equipment
Failure
Condition
1 300 aa
011
System
Trouble
FD
Equipment Fail Cond
= 011
Refer to
Note 1
through
Note 9
on page 56
* In Modem IIIa
2
, the D9068 uses Communications Fail to report a Data Lost event. The D9068 reports an
Equipment Fail and Equipment Fail Restore with Condition 006 to report an actual Communications
Fault.
Table 14: Reporting Summaries (Continued)
Point-Related Events
Report
Description
SIA
Code
SIA
Description
Contact
ID Code
Contact ID
Description
4/2
Code
Default
Values
Modem IIIa
2
Description
System
Restore
Programming
IR 11
Equipment Fail
Restoral
3 300 aa
011
System
Trouble
ED
Equipment
Restoral Cond = 011
Serial
Communication
Fault
YC
Communications
Fail
1 350 aa
000
Communication
Trouble
FD
Comm Fail, RG = 1
Serial
Communication
Restore
YK
Communications
Restoral
6 350 aa
000
Communication
Trouble
Restoral
ED
Comm Fail
Restr = RG1
Refer to
Note 1
through
Note 9
on page 56.
identifies equipment fail conditions. These conditions appear as a System
Trouble in Contact ID.
On a D9068 that is serially connected to a Bosch Analog FACP,
only applies
when the reported address
(C for Contact ID, SDI for Modem IIIa
2
) is less then 100. If the reported address
is more than 100, the reported event is a peripheral fault. Refer to
D8024/D10024/D10024A Analog FACP Operation
for more information.
Table 15: Equipment Fail Conditions
Code Event
Data in
Address Field
Generated
By
Description
2
Dialer Trouble
Input
Point
Dialer
A point configured for Fault on
Open or Fault on Short was
tripped.
5
System Trouble
Keypad
N/A
Dialer
The programming keypad was
connected to the D9068.
6
Comm Fault
N/A
Dialer
A Comm Fault occurred.
11
System Trouble
Programming
N/A
Dialer
Programming was entered on the
D9068.
12
Network Failure
Control panel
address
Control
panel
A control panel fail or restore
occurred.
13
FACP Programming
Control panel
address
Control
panel
The control panel was left in the
Programming Mode.
14
FACP Config RPS
Fail
Control panel
address
Control
panel
The RPS Config failed.
15
FACP Processor
Reset
Control panel
address
Control
panel
The processor reset.
16
FACP Unresolved
IRQ
Control panel
address
Control
panel
There is an unresolved interrupt
request (IRQ).
17
FACP Ground
Fault
Control panel
address
Control
panel
There is a ground fault.
18
FACP Loop Wiring
Fault
Control panel
address
Control
panel
There is a fault in wiring loop.