D9412GV2/D7412GV2
|
Operation and Installation Guide | 9.0
Off-Board Points
.
Bosch Security Systems, Inc. | 7/09 | F01U003641-04
47
9.4.3 Installation
For the most effective installation, use the following
four-step process:
1. Set the OctoPOPIT switches. Refer to
Section
9.4.4
Setting the OctoPOPIT Switches.
2. Physically mount the OctoPOPIT in the enclosure.
Refer to
Section 9.4.5 Mounting OctoPOPITs,
page 48.
3. Wire the OctoPOPIT. Refer to
Section 9.4.6
Wiring OctoPOPITs
on page 48.
4. Wire the OctoPOPIT sensor loops. Refer to
Section 9.4.7 OctoPOPIT Sensor Loops
on page
51.
9.4.4
Setting the OctoPOPIT Switches
The D8128D OctoPOPIT has two sets of DIP
switches (
Figure 20
on page 46). Use the DIP
switches on the top of the unit (with the terminal strip
along the left edge) to set the address for the
OctoPOPIT. Use the DIP switches at the bottom of
the unit to enable or disable individual points
connected to the OctoPOPIT.
Address Switches
The switches on the D8128D OctoPOPIT set point
assignments and line termination. These switches are
easier to set before mounting the D8128D in the
enclosure.
Switches 1, 2, 3, and 4 assign the OctoPOPIT sensor
loops to point numbers on the control panel.
Table 15
shows the OctoPOPIT switch settings for point
assignments.
Switch 5 sets line termination. Refer to
Table 16
.
Table 15: D8128D OctoPOPIT Switch Settings
for D9412GV2 and D7412GV2
ZONEX 1
D8128D Address Switches
ZONEX 2
Points 9 to
127 1
2
3
4
5
Points 129
to 247
9 to 16
ON
ON
ON
ON
*
129 to 136
17 to 24
ON
ON
ON
OFF
*
137 to 144
25 to 32
ON
ON
OFF
ON
*
145 to 152
33 to 40
ON
ON
OFF
OFF
*
153 to 160
41 to 48
ON
OFF
ON
ON
*
161 to 168
49 to 56
ON
OFF
ON
OFF
*
169 to 176
57 to 64
ON
OFF
OFF
ON
*
177 to 184
65 to 72
ON
OFF
OFF
OFF
*
185 to 192
73 to 80
OFF
ON
ON
ON
*
193 to 200
81 to 88
OFF
ON
ON
OFF
*
201 to 208
89 to 96
OFF
ON
OFF
ON
*
209 to 216
97 to 104
OFF
ON
OFF
OFF
*
217 to 224
105 to 112
OFF
OFF
ON
ON
*
225 to 232
113 to 120
OFF
OFF
ON
OFF
*
233 to 240
121 to 127
OFF
OFF
OFF
ON
*
241 to 247
*
Line Termination Switch
For the D8128D OctoPOPITs assigned to
Points 121 to 127, 241, and 247, set Point
Input Switch 8 to the OPEN position.
D9412GV2 uses Points 9 to 127 on Zonex
1 and Points 129 to 247 on Zonex 2.
D7412GV2 uses Points 9 to 75 on Zonex 1
only.
Table 16: Switch 5 Settings for Line
Termination
Is a D8125 POPEX
Module connected?
Switch 5 Setting(s) on
D8128D OctoPOPIT(s)
No
Set Switch 5 of only
one
D8128D to
ON
Yes
Set Switch 5 of
all
D8128Ds to
OFF