| Installation Guide | 2.0  Installation

2.0

Installation

 

Failure to follow the mounting instructions in this document can damage the FACP. 

 

 

The D7039 and D7024 have static sensitive components and must be handled with care. Follow the 
anti-static procedures when handling these modules. 

 

Before installing the D7039 Module, remove all AC and battery power to the FACP. 

 

1.

If the D7024 is already installed in an enclosure, remove it.

2. Place the FACP on a flat surface with the component side facing up (

Item 2

 in 

Figure 2

).

3. Insert the four plastic standoffs in the mounting holes (

Item 3

 in 

Figure 2

) without bending or flexing the FACP.

4. Align the standoff tabs so they do not touch the module components.

5. Firmly press the standoffs into the board, allowing the ears to expand out.

6. Mount the D7039 on the standoffs, ensuring the FACP connector pins (

Item 4

 in 

Figure 2

) are properly aligned.

7.

Install the FACP in the enclosure.

8. Use the mounting screw (

Item 5

 in 

Figure 2

) to secure the D7039’s ground wire (

Item 6

 in 

Figure 2)

 to the FACP.

2

1

3

4 5 6

7 8 9

#

Cmnd

0

Prog

*

Clear

Disable

Drill

Test

History

Reset

Silence

Trouble
Silenced

Power
Alarm

1

2

6

3

4

3

5

1 - D7039 Module

4 - FACP connector pins to align with the D7039

2 - D7024 FACP

5 - Mounting screw

3 - Standoff mounting holes (4)

6 - Ground wire

Figure 2:

Mounting the D7039 on the D7024

Summary of Contents for D7039

Page 1: ...D7039 EN Installation Guide Multiplex Expansion Module ...

Page 2: ...operly Bosch is not responsible for improperly installed tested or maintained devices For the D7039 with ROM version 1 04 to operate properly the D7024 FACP must be running version 2 05 or later firmware 1 0 Description The D7039 Figure 1 connects directly to the FACP for either two Class B multiplex buses or one Class A multiplex bus that allows up to 247 remote points When configured for Class A...

Page 3: ...s in the mounting holes Item 3 in Figure 2 without bending or flexing the FACP 4 Align the standoff tabs so they do not touch the module components 5 Firmly press the standoffs into the board allowing the ears to expand out 6 Mount the D7039 on the standoffs ensuring the FACP connector pins Item 4 in Figure 2 are properly aligned 7 Install the FACP in the enclosure 8 Use the mounting screw Item 5 ...

Page 4: ... 4 Do not use shielded wire Do not use shielded wire Twisted pair is acceptable but is not recommended 2 0 Installation Figure 4 Connecting the Mux Class A and Class B 1 I O module for the D7039 wired Class A 4 Mux B Addresses 129 through 255 2 Class A Addresses 9 through 128 5 Mux A Addresses 9 through 128 3 I O module for the D7039 wired Class B Note All terminals are supervised 2 1 3 4 5 6 7 8 ...

Page 5: ... on a D7024 Control Panel Lot 100 or later the D7039 implements Style 6 SLC Refer to the D7024 Operation and Installation Guide P N 31499 for programming When configured as a Class B loop and installed on a D7024 Control Panel before Lot 100 the D7039 implements a Style 3 5 SLC When installed on a D7024 Control Panel Lot 100 or later the D7039 implements a Style 4 SLC Refer to the D7024 Operation ...

Page 6: ...ge 24 VDC nominal from FACP Current Draw Standby and Alarm 150 mA maximum Current Draw Load 100 mA maximum for each bus Maximum Bus Voltage 8 5 V to 13 V Maximum Wiring Resistance 50 Ω Class A Style 6 or Class B Style 4 SLC Environment Indoor dry Note All Mux Bus terminals are power limited and supervised ...

Page 7: ...7 Bosch 09 05 38685F D7039 Installation Guide Notes Notes ...

Page 8: ...Bosch 130 Perinton Parkway Fairport NY 14450 9199 USA Customer Service 800 289 0096 Technical Support 888 886 6189 2005 Bosch 38685F ...

Reviews: