background image

D7039

EN

Installation Guide

Multiplex Expansion
Module

Summary of Contents for D7039

Page 1: ...D7039 EN Installation Guide Multiplex Expansion Module ...

Page 2: ...operly Bosch is not responsible for improperly installed tested or maintained devices For the D7039 with ROM version 1 04 to operate properly the D7024 FACP must be running version 2 05 or later firmware 1 0 Description The D7039 Figure 1 connects directly to the FACP for either two Class B multiplex buses or one Class A multiplex bus that allows up to 247 remote points When configured for Class A...

Page 3: ...s in the mounting holes Item 3 in Figure 2 without bending or flexing the FACP 4 Align the standoff tabs so they do not touch the module components 5 Firmly press the standoffs into the board allowing the ears to expand out 6 Mount the D7039 on the standoffs ensuring the FACP connector pins Item 4 in Figure 2 are properly aligned 7 Install the FACP in the enclosure 8 Use the mounting screw Item 5 ...

Page 4: ... 4 Do not use shielded wire Do not use shielded wire Twisted pair is acceptable but is not recommended 2 0 Installation Figure 4 Connecting the Mux Class A and Class B 1 I O module for the D7039 wired Class A 4 Mux B Addresses 129 through 255 2 Class A Addresses 9 through 128 5 Mux A Addresses 9 through 128 3 I O module for the D7039 wired Class B Note All terminals are supervised 2 1 3 4 5 6 7 8 ...

Page 5: ... on a D7024 Control Panel Lot 100 or later the D7039 implements Style 6 SLC Refer to the D7024 Operation and Installation Guide P N 31499 for programming When configured as a Class B loop and installed on a D7024 Control Panel before Lot 100 the D7039 implements a Style 3 5 SLC When installed on a D7024 Control Panel Lot 100 or later the D7039 implements a Style 4 SLC Refer to the D7024 Operation ...

Page 6: ...ge 24 VDC nominal from FACP Current Draw Standby and Alarm 150 mA maximum Current Draw Load 100 mA maximum for each bus Maximum Bus Voltage 8 5 V to 13 V Maximum Wiring Resistance 50 Ω Class A Style 6 or Class B Style 4 SLC Environment Indoor dry Note All Mux Bus terminals are power limited and supervised ...

Page 7: ...7 Bosch 09 05 38685F D7039 Installation Guide Notes Notes ...

Page 8: ...Bosch 130 Perinton Parkway Fairport NY 14450 9199 USA Customer Service 800 289 0096 Technical Support 888 886 6189 2005 Bosch 38685F ...