Information for heating contractor
4.4
Settings in the service menu
▶ A.1 = Set and confirm Fb (remote control)
▶ Select and confirm heating circuit (HC = 1...8).
Ventilation unit (OFF)
▶ Switch on the system / Reset CR 10 H.
Three dashes are displayed while the connection is being
established.
Only ventilation unit:
▶ A.1 = Set and confirm OFF
▶ U.1 = (1 ...4) Select and confirm ventilation zone.
Setting
Adjustment
range
1)
Description
A.1
CO | Fb | OFF
Controller (CO), remote control (Fb), only the
ventilation unit (OFF)
H.C
HC1
... HC8
Heating circuit 1 to 8
2)
U.1
OFF |
1
| 2 | 3 | 4
Ventilation zone
d.1
2 |
3
| 4
Control characteristics (reaction speed)
2: 2K P-range = Fast reaction
3: 3K P-range = Medium reaction
4: 4K P-range= Slow reaction
E.1
– 3.0 ...
0.0
... 3.0 Correction value for the room temperature
displayed
P.1
4
| 5
Flow temperature control (4) or output
control (5)
Systems with several heating circuits (remote control – Fb)
°C
°F
°C
°F
°C
°F
°C
°F
°C
°F
°C
°F