| Information for heating contractor
6720830560 (2015/06)
CR 10
4.5
Settings in the service menu
▶ A.1 = Set and confirm SC (zone controller).
-or-
▶ A.1 = Set and confirm Fb (remote control)
▶ Select and confirm heating circuit (HC = 1...8).
Setting
Adjustment range
1)
Description
A.1
CO
| Fb | SC
Controller (CO), remote control (Fb), zone
controller (SC)
HC
HC1
| HC2 | ... | HC7 |
HC8
Heating circuit/heating zone 1 to 8
2)
d.1
2 |
3
| 4
Control characteristics (reaction speed)
2: 2K P range = Quick reaction
3: 3K P range = Medium reaction
4: 4K P range = Slow reaction
E.1
– 3.0 ...
0.0
... 3.0
Correction value for the room temperature
displayed
P.1
4
| 5
Flow temperature control (4) or output
control (5)
L 1
1
| 0
Optimised running of the pump: in the case
of flow temperature control, the heating
pump runs as briefly as possible.
Switching-off if there is a buffer cylinder in
the system.
C.1
C
| F
Unit of displayed temperatures °C (C) or °F
(F)
Systems with several heating circuits (zone controller/remote control)
°C
°F
°C
°F
°C
°F
°C
°F