Bosch Conettix ITS-D6682-INTL Installation Manual Download Page 9

Conettix ITS-D6682-INTL 

|

 

Installation Guide | 3.0 Configuring and Programming the D6682 

Bosch Security Systems, Inc. | 2/09 | F01U126778-01 

 

Table 2: Netmask Address 

 

Number of Host Bits 

Netmask 

255.255.255.254 

2 255.255.255.252 

255.255.255.248 

255.255.255.240 

255.255.255.224 

255.255.255.192 

255.255.255.128 

255.255.255.0 

255.255.254.0 

10 

255.255.252.0 

11 

255.255.248.0 

12 

255.255.240.0 

13 

255.255.224.0 

14 

255.255.192.0 

15 

255.255.128.0 

16 

255.255.0.0 

17 

255.254.0.0 

18 

255.252.0.0 

19 

255.248.0.0 

20 

255.240.0.0 

21 

255.224.0.0 

22 

255.192.0.0 

23 

255.128.0.0 

24 

255.0.0.0 

25 

254.0.0.0 

26 

252.0.0.0 

27 

248.0.0.0 

28 

240.0.0.0 

29 

224.0.0.0 

30 

192.0.0.0 

31 

128.0.0.0 

 

18.

 

When you are prompted to change the telnet 
password, press [N] for 

No

 (default setting). 

The Setup Mode screen appears again. 
Refer to 

Figure 9 

on page 

8.

 

 

If you use a password, store it in a 
secure place. If the password is lost or 
forgotten you cannot connect to the 
telnet program on this unit again. The 
unit must be returned to the factory and 
reconditioned before it can receive 
another telnet session. 

 

19.

 

Press

 

 [1] [ENTER] to configure Channel 1. 

Baudrate 9600 appears. 

 

The D6682 must be set to a baud rate 
of 38400. 

 

20.

 

Type 

38400 

and press [ENTER] to change 

the baud rate. 
I/F Mode (4C) ? appears. 

21.

 

Press [ENTER] to accept 

4C

 (default setting) 

as the entry. 
If a different value appears in parentheses, 
type 

4C

 and press [ENTER] to change the 

value. 
Flow (00) ? appears. 

22.

 

Press [ENTER] to accept 

00

 (default setting) 

as the entry. 
If a different value appears in parentheses, 
type 

00

 and press [ENTER] to change the 

value. 
Port No (13257) ? appears. 

23.

 

For the Port number, type a number between 
2000 and 10000, and press [ENTER]. 

 

If using two channels, set different port 
numbers for Channel 1 and Channel 2 
(shown in the Telnet configuration 
screen). 

 

ConnectMode (CC) ? appears. 

24.

 

Press [ENTER] to accept 

CC

 (default setting) 

as the entry, or type 

CC

 and press [ENTER] 

to change the value. 
Datagram Type (00) ? appears. 

25.

 

 If all field devices are using the same port 
number as entered in 

Step 23

, type 

00 

and 

press [ENTER]. 

 

To use Datagram Type 02, Bosch 
firmware version 6.5.8.0 or later is 
required. Refer to the 

Device Installer 

Operation and Installation Guide

 

(P/N: 4998138688) for more 
information. 

 

26.

 

 If all field devices are using unique port 
numbers, type 

02

 and press [ENTER]. 

 

If Datagram Type 02 is used, enable it 
in the D6600 Receiver refer to the 

D6600 Program Entry Guide

 

(P/N: 4998122702). 

For more information on Datagram 
Types, refer to the 

Conettix

 

D6600 

System Guide 

(P/N: 4998122712). 

 

Summary of Contents for Conettix ITS-D6682-INTL

Page 1: ...EN Installation Guide Ethernet Network Adapter Conettix ITS D6682 INTL ...

Page 2: ...Installation 4 2 1 Mounting the D6682 4 2 2 Connecting the D6682 4 3 0 Configuring and Programming the D6682 5 3 1 Factory Default IP Address 5 3 2 Identifying the MAC Hardware Address 5 3 3 Obtaining an IP Address 5 3 4 Using ARP to Assign the IP Address 5 3 5 ARP Command Usage 6 3 6 Using Telnet to Finish the Configuration 7 3 7 Programming Overview for the D6600 10 4 0 Specifications 11 ...

Page 3: ...stic LEDs 2 Serial Port 2 DTE optional use supplied cable if required 3 Serial Port 1 DTE use supplied null cable 1 3 LEDs Table 1 D6682 LEDs LED Description Power Diagnostic Blue Steady On Power OK Blinking 2x No DHCP response Blinking 2x Setup Menu active RX Serial 1 Activity Green Off No data activity Blinking Data received by D6682 on Channel 1 TX Serial 1 Activity Yellow Off No data activity ...

Page 4: ... Refer to Figure 3 2 2 Connecting the D6682 Connect the D6682 as follows Power cable to an available electrical outlet Ethernet cable to network switch RS 232 serial cable to Serial 1 port Refer to the D6600 D6100i System Guide P N 4998122712 for applications using both serial ports Refer to Figure 3 Figure 3 D6682 Connections 1 Power cable 2 Ethernet cable 3 RS 232 serial cable Serial 1 port 4 Se...

Page 5: ...cting a private network to the Internet requires using registered IP addresses called Internet addresses to avoid duplicates 3 4 Using ARP to Assign the IP Address Bosch Security Systems Inc recommends that you read this entire section before proceeding Also ensure that power is applied to the D6682 and the Ethernet Network RJ45 connection is in place In order to access the configuration program e...

Page 6: ... Run to open an MS DOS window 2 At the Run dialog box type COMMAND and click OK A DOS window appears 3 Type the arp s command with the IP address and the MAC hardware address For this example the IP address is 190 220 128 219 and the MAC hardware address is 00 20 4a 01 b5 3d If the computer responds with the C WINDOWS prompt after you enter the ARP command the address is accepted Refer to Figure 6...

Page 7: ...ke several minutes To use Telnet you must log in as a user with Administrative privileges This example uses the IP address of 10 25 124 148 and the MAC Address of 00 20 4a 51 01 a7 To complete the IP address configuration of the D6682 launch a telnet session 5 Select Start Æ Run to open an MS DOS window 6 Type telnet and click OK A DOS window appears The colors are inverted here for clarity The no...

Page 8: ...rly program IP Address 190 200 128 220 press the following keys 1 9 0 ENTER 2 0 0 ENTER 1 2 8 ENTER 2 2 0 ENTER The IP and MAC addresses used in this example are not the same as the numbers you are using This procedure is for demonstration only 15 When asked to set the Gateway IP address Figure 10 type N and press ENTER to accept the default Figure 10 Telnet session Gateway Address The Gateway IP ...

Page 9: ...st be set to a baud rate of 38400 20 Type 38400 and press ENTER to change the baud rate I F Mode 4C appears 21 Press ENTER to accept 4C default setting as the entry If a different value appears in parentheses type 4C and press ENTER to change the value Flow 00 appears 22 Press ENTER to accept 00 default setting as the entry If a different value appears in parentheses type 00 and press ENTER to cha...

Page 10: ...haracters should match the bytes programmed in the D6682 Default value is 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 36 At Enable Enhanced Password N press ENTER After you make all the changes and verify them for accuracy you must save the information 37 Select 9 save and exit When the connection to host is lost press ENTER to continue 3 7 Programming Overview for the D6600 The D6600 Receiver...

Page 11: ...ta bits Stop bits 1 or 2 Parity Odd even none Modem Controls DTR DSR Flow Control Software XON XOFF Hardware CTS RTS Management HTTP internal web server SNMP read only Serial login Telnet login DeviceInstaller software System Software Flash ROM standard downloadable from a TCP IP host TFTP or over serial port Diagnostic LEDs Power 10 100 Mb Link on RJ45 10 100 Activity on RJ45 RX Serial 1 Activity...

Page 12: ... 2009 Bosch Security Systems Inc F01U126778 01 Bosch Security Systems Inc 130 Perinton Parkway Fairport NY 14450 9199 800 289 0096 ...

Reviews: