Operation without the outdoor unit (individual operation)
23
Compress 3000 AWES – 6720892204 (2020/06)
9
Operation without the outdoor unit (individual
operation)
The indoor unit can be started without the outdoor unit being connected,
for example if the outdoor unit is to be installed at a later date. This is
termed individual operation or stand-alone operation.
With individual operation, the indoor unit only uses the integrated or
external auxiliary heater for heating and DHW heating.
Commissioning in individual operation:
▶ In the «
Heat pump
» service menu, select the option «
Individual
operation
» (
instructions for the control unit).
10
Environmental protection and disposal
Environmental protection is a fundamental corporate strategy of the
Bosch Group.
The quality of our products, their economy and environmental safety are
all of equal importance to us and all environmental protection legislation
and regulations are strictly observed.
We use the best possible technology and materials for protecting the
environment taking account of economic considerations.
Packaging
Where packaging is concerned, we participate in country-specific
recycling processes that ensure optimum recycling.
All of our packaging materials are environmentally compatible and can be
recycled.
Used appliances
Used appliances contain valuable materials that can be recycled.
The various assemblies can be easily dismantled. Synthetic materials are
marked accordingly. Assemblies can therefore be sorted by composition
and passed on for recycling or disposal.
Old electrical and electronic appliances
This symbol means that the product must not be disposed
of with other waste, and instead must be taken to the waste
collection points for treatment, collection, recycling and
disposal.
The symbol is valid in countries where waste electrical and
electronic equipment regulations apply, e.g. "European Directive 2012/
19/EC on old electronic and electrical appliances". These regulations
define the framework for the return and recycling of old electronic
appliances that apply in each country.
As electronic devices may contain hazardous substances, it needs to be
recycled responsibly in order to minimize any potential harm to the
environment and human health. Furthermore, recycling of electronic
scrap helps preserve natural resources.
For additional information on the environmentally compatible disposal
of old electrical and electronic appliances, please contact the relevant
local authorities, your household waste disposal service or the retailer
where you purchased the product.
You can find more information here:
www.weee.bosch-thermotechnology.com/
11
Technical information
11.1
Specifications – Indoor unit with electric booster heater
Table 6 Indoor unit with electric booster heater
AWES
Unit
2-6
8
11-15
Electrical wiring specifications
Power supply
V
400
2)
/230
1)
1) 1N AC 50 Hz. The outdoor unit must have a separate power supply
400
2)
/230
1)
2) 3N AC 50 Hz, standard version for Germany
Recommended fuse size
3)
3) Fuse characteristic gL/C
A
3 x 16
2)
/50
1)
3 x 16
2)
/50
1)
Connected load
KW
2/4/6/9
2/4/6/9
Heating system
Connection type (heating flow)
1" male thread
1" male thread
Type of connection (heating return)
1" female thread
1" female thread
Connection type for the heat pump flow (gas)
5/8”
5/8”
Connection type for the heat pump return (liquid)
3/8”
3/8”
Maximum operating pressure
kPa/bar
300/3.0
300/3.0
Minimum operating pressure
kPa/bar
50/0.5
4)
4) Pressure depending on the pressure in the expansion vessel
50/0.5
4)
expansion vessel
l
8
8
Available external pressure
kPa/bar
56/0.56
73/0.73
58/0.58
Minimum flow (during defrosting)
5)
5) If the minimum flow rate in the system cannot be ensured, a buffer cylinder is essential.
l/s
0.34
0.34
0.47
Pump type
Grundfos UPM2K 25-75 PWM
Grundfos UPM GEO 25-85 pulse width modulation
General Information
Installation altitude
up to 2000 m over NN
IP rating
IPX1
Dimensions (width x depth x height)
mm
485 x 398 x 700
Weight
kg
41