SystemModules
FlexibleAutomation
4−51
Protection
The outputs are protected against:
D
Polarity reversal (24V DC)
D
Short−circuit
D
Overload.
In all these cases, the LED error indicator lights. In case of a short−circuit
or overload the respective output is deactivated. After 2ms the output is
reactivated. If the short−circuit is still present, the output is deactivated
again after 40
m
s. This process is repeated after 2 ms.
Simultaneity
The following table shows that the simultaneity factor when driving the
outputs is dependent on ambient temperature and on the use of a fan
unit.
Ambient
Temperature
20C
_
55C
_
SimultaneityFactor
Without
WithFanin
theBasicUnit
WithFanin
theCardCage
80%
50%
100%
70%
100%
100%
EG
EG
EG
GG
GG
GG
Fan
Fan
Fan
Fan
Fig.4−25Simultaneity
Summary of Contents for CL300
Page 1: ...Automationstechnik Antriebs und Steuerungstechnik CL300 Manual CL300 101 Version ...
Page 4: ......
Page 6: ...Contents Flexible Automation 0 4 ...
Page 8: ...Preface Flexible Automation 0 6 ...
Page 9: ...General Information Flexible Automation 1 1 Contents Page 1 General Information 1 3 ...
Page 10: ...General Information Flexible Automation 1 2 ...
Page 12: ...General Information Flexible Automation 1 4 ...
Page 48: ...Operation Flexible Automation 3 4 Fig 3 1 Organizational Structure ...
Page 52: ...Operation Flexible Automation 3 8 ...
Page 122: ...System Modules Flexible Automation 4 70 ...
Page 152: ...Software Description Flexible Automation 5 30 ...
Page 153: ...Preparation for Use Flexible Automation 6 1 Contents Page 6 Preparation for Use 6 3 ...
Page 154: ...Preparation for Use Flexible Automation 6 2 ...
Page 162: ...Maintenance Flexible Automation 7 6 ...
Page 163: ...Specifications Flexible Automation 8 1 Contents Page 8 Specifications 8 3 ...
Page 164: ...Specifications Flexible Automation 8 2 ...
Page 167: ...1070 072 113 101 89 02 GB HB SP AT VSP Printed in Germany ...