48
en | Fault message
FPA-5000 | FPA-1200 | AVENAR panel 8000 |
AVENAR panel 2000 | AVENAR keypad 8000
2020-07 | 3.0 | F.01U.378.877
User Guide
Bosch Sicherheitssysteme GmbH
–
Date and time of the message
–
Physical and logical addressing of the element
–
Only for LSN detectors: specification of the detector type
–
Action text (depending on the configuration)
Select
OK
to return to the list of all fault messages.
Reset
, see
Block
Blocking an element, page 49. Select
Details
(if available) to go directly to the
respective
Diagnostics
window for troubleshooting, see
10.2.8
Signals
Optical signals
The
"fault" icon lights up yellow.
Depending on the type of fault, an additional yellow signal light lights up (see also
–
Fault system (LED steady)
–
Fault power (LED steady)
–
Fault detector (LED blinking)
–
Fault transmission device (LED blinking)
–
Fault signals (LED blinking)
–
Output to fire protection equipment fault (LED blinking)
Acoustic signal
An internal signal tone sounds on the system.
To temporarily silence the internal buzzer:
Press
.
10.3
Resetting fault message
!
Caution!
If a message does not have to be reset, it is removed from the display as soon as the fault has
been rectified.
Depending on the configuration, three different variants are offered for resetting; see
Resetting alarm message, page 43.
There are two ways to reset a fault message:
–
Select
Reset
in the message display or
–
Select the fault message and then press
Reset
in the detailed view
The selected element/element group is reset.
If a list field is marked with an "R", the process of resetting is not yet complete for this
element.
TEXT
R
If an element cannot be reset, it will continue to be displayed in the list.
After the successful resetting of all elements, the standby display is displayed.