Access Controller 

AMC-4W 

 

 

Bosch Security Systems | V.3.1/2006-09

Summary of Contents for AMC-4W

Page 1: ...EN Access Controller AMC 4W Bosch Security Systems V 3 1 2006 09 ...

Page 2: ...tes do not allow the exclusion or limitation of implied warranties or limitation of liability for incidental or consequential damages so the above limitation or exclusion might not apply to you Bosch Security Systems retains all rights not expressly granted Nothing in this license constitutes a waiver of Bosch s rights under the U S Copyright laws or any other federal or state law If you have any ...

Page 3: ...acteristics 16 3 3 System Overview 17 4 Technical Data 18 5 Installing the AMC 4W 21 5 1 Mounting the AMC 4W 21 5 1 1 Mounting on rails 21 5 1 2 Demounting the AMC 4W from mounting rails 21 5 2 Opening the AMC 4W Case 22 5 3 Cabling 22 5 4 Grounding and Shielding 23 5 5 Connecting Power Supply 25 5 6 RS485 Host Interface 27 5 6 1 RS485 Two Wire Connection 28 5 6 2 RS485 Four Wire Connection 29 5 6...

Page 4: ...7 3 Proprietary burglar alarm access control power supply Fehler Textmarke nicht definiert 7 3 1 Overview Fehler Textmarke nicht definiert 7 3 2 Power Supply Voltage Output Selections Fehler Textmarke nicht definiert 7 3 3 LED Diagnostics Fehler Textmarke nicht definiert 7 3 4 Installation Instructions for the RK AL600ULX 4CB6 Fehler Textmarke nicht definiert 7 4 Legend 50 7 5 Product declaration ...

Page 5: ...ollowed for successful operation and programming Tips and shortcuts might also be included here Cross Reference Please refer to this document or chapter to obtain additional information about the issue 1 2 Internet If you are interested in further information on this product or information on other products please refer to our website at http www bosch security systems com 1 3 We Are Interested in...

Page 6: ... instructions provided with the unit Generally using a damp cloth for cleaning is sufficient Do not use liquid cleaners or aerosol cleaners 6 Service Do not attempt to service this unit by yourself Opening or removing covers may expose you to dangerous voltages or other hazards Refer all servicing to qualified service personnel 7 Damage Requiring Service Disconnect the unit from the main AC or DC ...

Page 7: ...12 VDC power supply to the unit must be in compliance with electrical codes Class 2 power levels Do not ground the 12 VDC supply at the terminals or at the unit s power supply terminals 11 Grounding If an outside cable system is connected to the unit ensure that the cable system is grounded U S A models only Section 810 of the National Electrical Code ANSI NFPA No 70 provides information regarding...

Page 8: ...the installer is encouraged to correct the interference by one or more of the following measures 1 Reorient the antenna of the radio television 2 Connect the AC power cord to a different outlet so the control panel and radio television are on different branch circuits 3 Relocate the control panel with respect to the radio television If necessary consult an experienced radio television technician f...

Page 9: ...sconnect plug connectors data cables or screw connectors while power is on Health and Safety Installation of the AMC 4W must comply with any local fire health and safety regulations A secured door that may be part of an escape route from an area must be installed with A fail safe lock A So that the door will be released if power fails Ideally a magnetic lock should be used as these are less likely...

Page 10: ...to the battery manufacturer s instructions 2 4 Unpacking Check the packaging for visual damage If anything has been damaged during transport make the transport agency aware of this Carefully unpack the unit This is an electronic device that must be handled with care to avoid damage Do not attempt to put the unit into operation if components are damaged If parts are missing inform your customer ser...

Page 11: ...n one direction only Figure 1 The Access Controller AMC 4W All necessary information for access verification is stored in a battery buffered on board memory and a Compact Flash CF memory card This guarantees autonomous access decisions and complete access registrations even if the management host system is offline The built in compact flash adapter provides adequate storage capability for cardhold...

Page 12: ...an external alarm system if an intrusion or system alert is detected The AMC 4W provides an IP protocol stack completely developed by Bosch There are no third party operating systems and there is no vulnerability by viruses The AMC 4W electronic is completely covered by a plastic housing The LC Display provides all important status information The setup procedure for an AMC 4W is very simple and e...

Page 13: ...S485 four wire depends on external wiring 4 DIL switch for RS485 address selection protocol and RS232 RS485 selection 5 Configurable RS232 host interface ribbon cable connector 6 Reset push button 7 Jumper Potential equalization between different mass systems and protective earth shield 8 Configurable RS485 host interface pluggable screw connector 9 Lithium battery for buffering of static RAM and ...

Page 14: ...escription of the AMC 4W Access Controller AMC 4W 14 Installation Guide Bosch Security Systems V 3 1 2006 09 10 Compact Flash optional size 11 LC Display 12 Configurable 10 100 Mbit s Ethernet interface ...

Page 15: ... tamper contact Pluggable screw connector 16 RS485 extension module bus Pluggable screw connector 17 Fuse RS485 extension module bus 6300mA time lag i e Schurter 7010 ggbg 125V DC T 6300mA 18 Wiegand interface for card readers Supply current max 200mA 19 Analog input Pluggable screw connector 20 Relay Output Pluggable screw connector max 1 25A at 12V DC 21 Fuse Power supply electronics 750mA time ...

Page 16: ...able host interfaces RS485 2 wire RS485 4 wire RS232 Ethernet 10 100 Mbit s Four peripheral input devices via Wiegand interface Eight relay outputs potential free or with internal power supply Eight analog inputs with internal power supply Battery buffered SRAM and real time clock RTC Pluggable Compact Flash from 64 MB to 1024 MB Connector for LC Display Transfer rate host interface RS485 38 4 kBi...

Page 17: ...ith mounted enclosure only 3 3 System Overview The Access Controller AMC 4W is connected between the management host system and different peripheral devices Figure 6 System overview By default a management host system is connected via Ethernet A management host connection via RS485 or RS232 is also possible In RS485 mode up to eight access controllers AMC 4W can be combined on one party line Via W...

Page 18: ...nsfer rate 38 4 kBit s No parity 8 Bit 1 Stop bit RS232 No parity 8 Bit 1 Stop bit Ethernet Wiegand interface for card readers Eight relay outputs using resistive load Maximum switching power 37 5VA Maximum switching voltage 30V AC DC Maximum switching current 1 25A 8 analog inputs with sabotage monitoring Tamper contact for enclosures Power supply Electronics 10V 35V DC Peripheral devices 12V Dis...

Page 19: ...to the AMC 4W Please calculate the voltage drop by checking the conductor specifications for characteristic resistance values The voltage drop shall not exceed 2V Example Length 100m 328 ft U 12V I 1A maximum VDrop 2V i e RAWG18 acc specs ft 1000 385 6 Ω or 20 948 km Ω VDrop 20 948 A km km 1 1 0 Ω 2 1V VDrop A ft ft 1 328 1000 385 6 Ω 2 1V Critical condition Install the power supply closer to the ...

Page 20: ...ty Systems V 3 1 2006 09 Conductor data RS485 slave Use AWG22 conductors Please calculate your voltage drop see above by checking conductor specifications for characteristic resistance values Note The voltage drop at the different cables add up Their sum shall be less than 2V ...

Page 21: ... AMC 4W into the lower edge of the mounting rail the lift the AMC 4W and snap it onto the rail by pushing it towards the back Figure 7 Mounting the AMC 4W on a mounting rail 5 1 2 Demounting the AMC 4W from mounting rails To remove the AMC 4W from a mounting rail first remove all pluggable screw connectors Lift up the AMC 4W until it snaps out of the mounting rail Pull the upper end of the AMC 4W ...

Page 22: ...rning Risk of damaging equipment Do not use screw drivers or any other sharp tools or objects to open the enclosure This might cause damage to the chassis A slight pressure with a finger is sufficient to open the enclosure Figure 9 Opening the AMC 4W case 5 3 Cabling The cables used in the AMC 4W access control system are not prone to electrical interference However you should avoid routing cables...

Page 23: ...lt in ground loops It is recommended that the unconnected end of the shield is insulated to prevent accidental connection The AMC 4W enables you to set up a central ground or shielding point simply by setting a couple of jumpers Set these jumpers only if ground or shield is not connected otherwise Warning Risk of damaging equipment When using multiple AMC 4W devices set the ground main jumper only...

Page 24: ...rface Set Jumper 3 only at the first AMC 4W of a party line The host system must not connect cable shield and protective ground If the AMC 4W is set to RS232 mode Jumper 3 must be set Figure 11 Location of ground jumpers bottom side circuit board Jumper 4 connects the internal ground of the AMC 4W to the RS485 ground of the slave interface Jumper 4 shall only be set if the AMC 4W powers all other ...

Page 25: ...this documentation Figure 12 Location of the power supply connector An external power supply 10 35V DC must be connected for internal electronics at pin 1 positive and pin 3 negative of the pluggable screw connector An additional power supply 12V DC for peripheral devices i e card readers and door openers must be connected at pin 6 positive and pin 7 negative Caution Risk of Damage Power supply fo...

Page 26: ...s and peripherals pin 1 and pin 6 resp pin 3 and pin 7 can be shortened If an uninterruptible power supply UPS is used the relay output for power good signals from the UPS is connected to pin 4 and pin 5 Otherwise these two pins must be short circuited 26 Installation Guide Bosch Security Systems V 3 1 2006 09 ...

Page 27: ... system A bus system consists of a bus line and or one or more branch lines Cable lengths exceeding 100m or 300ft must be installed as bus lines Branch lines are branching connections from a bus line If a branch line is used the spur line should be attached directly to the device Bus devices are the AMC 4W Peripheral devices are card readers door control units locks signals alarm devices etc which...

Page 28: ... multiple AMC MUX EXT To use RS485 mode at the AMC 4W connect the data cables to the pluggable screw connector of the RS485 host interface Then set the RS485 address via DIL switch or software and activate the RS485 two wire or four wire mode via jumper settings Figure 14 Location of the RS485 host interface 5 6 1 RS485 Two Wire Connection Figure 15 Connection scheme of an RS485 two wire connectio...

Page 29: ...nstallation Guide 29 Figure 16 Settings for RS485 two wire connection A complete connection diagram of the RS485 host interface is shown in chapter 7 1 Connecting Diagrams of this documentation 5 6 2 RS485 Four Wire Connection Figure 17 Connection scheme of an RS485 four wire connection ...

Page 30: ...s shown in chapter 7 1 Connecting Diagrams of this documentation 5 6 3 DIL Switch Address Selector The first four DIL switches for address selection define the RS485 address of the AMC 4W in a RS485 bus system Switch 5 selects on of the two different protocols SDEB and BPA according to DIN6619 Switch 6 sets the connection to the host system to either RS232 or RS485 Figure 19 Location of the RS485 ...

Page 31: ...ms V 3 1 2006 09 Installation Guide 31 DIL Switches Address 1 2 3 4 None Off Off Off Off 1 On Off Off Off 2 Off On Off Off 3 On On Off Off 4 Off Off On Off 5 On Off On Off 6 Off On On Off 7 On On On Off 8 Off Off Off On DIL Switches Mode 5 6 ON SDEB RS232 OFF BPA RS485 ...

Page 32: ...C 4W offers an RS232 serial interface to connect a host computer or serial modem Cable length between two RS232 COM serial interfaces must not exceed 15 meters 45 ft Figure 20 Location of the RS232 serial interface A complete connection diagram of the RS232 serial interface is shown in chapter 7 1 Connecting Diagram of this documentation ...

Page 33: ...e AMC 4W directly to a computer s network interface or a standard CAT5 patch cable to connect the AMC 4W to a network hub or network switch Figure 21 Location of the Ethernet interface A complete connection diagram of the Ethernet interface is shown in chapter 7 1 Connecting Diagram of this documentation 5 8 1 Removing Ethernet Plugs from Socket To remove an RJ45 network cable from socket use the ...

Page 34: ...Up to three expansion modules can be connected to provide additional in and outputs for example for elevator control Figure 22 Location of the RS485 extension module bus A complete connection diagram of the RS485 extension module bus is shown in chapter 7 1 Connecting Diagram of this documentation 34 Installation Guide Bosch Security Systems V 3 1 2006 09 ...

Page 35: ...ur Wiegand interfaces to integrate up to four card readers with Wiegand compatible interfaces Each interface is connected via a 10 pin pluggable screw connector S5 S9 S13 and S17 Figure 23 Location of the Wiegand interfaces for external devices A complete connection diagram of the Wiegand interface is shown in chapter 7 1 Connecting Diagram of this documentation ...

Page 36: ...e AMC 4W s internal 12V DC power supply for external devices or dry mode with potential free contacts for externally powered systems Figure 24 Wet mode and dry mode of the AMC 4W relay outputs Maximum switching power of each relay output using resistive load is 60 VA maximum switching voltage 30 V DC and maximum switching current 1 25 A If there is inductive load diodes should be installed across ...

Page 37: ...fications of the relay Using exceeding voltage or current on relay contacts in either mode can damage the AMC W Figure 25 Location of the relay output connectors A complete connection diagram of the relay output connectors is shown in chapter 7 1 Connecting Diagram of this documentation Each relay output has a separate jumper setting on the bottom side of the lower circuit board to activate wet or...

Page 38: ...t Devices The AMC 4W has eight analog inputs for example for potential free lock mechanisms or to detect if a lock is closed or open The AMC 4W can also detect the wiring conditions short circuit and broken and initiate an alarm if the appropriate devices are connected Figure 27 Operating modes of a lock using the analog input device ...

Page 39: ... Short circuit RS RP 0 The resistor values can vary and depend on the used lock system wire resistance negligible Default values are RS 2 2 kΩ RP 4 7 kΩ All input devices are connected by means of 4 pin pluggable screw connectors of the AMC 4W A complete connection diagram for analog input devices is shown in chapter 7 1 Connecting Diagram of this documentation ...

Page 40: ... the AMC 4W against unauthorized access and prevent the AMC 4W from tampering with sensitive data the AMC 4W offers an additional interface to connect external tamper contacts This interface is a potential free 2 pin pluggable screw connector marked with T If not using the tamper contact short circuit the contacts with a wire connection Figure 29 Location of the tamper protection contact ...

Page 41: ...e Dialog button as shown in figure 30 to switch between different modes Figure 30 Location of the Dialog button The display mode which has been set remains until the next operation of the Dialog button Push Display Description 0 V00 35 02 05 05 Software version of the downloader 1 99999876543210 A Bosch serial number and bus address A address 1 B address 2 C address 3 D address 4 E address 5 F add...

Page 42: ...AmcIpConfig provided in the tools directory on the provided CD ROM The installation and usage of the software application to configure the AMC 4W via Ethernet interface is described in an additional document AmcIpConfig Configuration Software for the AMC 4W 6 3 Resetting the AMC 4W When a problem occurs first try to fix the problem directly If this does not solve the problem resetting the AMC 4W m...

Page 43: ...d above in download program 2 Open the upper case of the AMC 4W 3 Set all six DIL switches of the RS485 selector to ON 4 Press the tamper switch on the upper left side of the board 5 The AMC 4W will now have the following network configuration a DHCP 0 b IP 127 0 0 1 Figure 31 Restarting the AMC 4W with the provided screw driver Figure 32 Resetting the AMC 4W to delivery state ...

Page 44: ...Appendix Access Controller AMC 4W 44 Installation Guide Bosch Security Systems V 3 1 2006 09 7 Appendix 7 1 Connecting Diagrams Figure 33 Connector blocks of the AMC 4W ...

Page 45: ...Access Controller AMC 4W Appendix Bosch Security Systems V 3 1 2006 09 Installation Guide 45 Figure 34 Power supply Figure 35 Relay outputs analog inputs and Wiegand interface ...

Page 46: ...dix Access Controller AMC 4W 46 Installation Guide Bosch Security Systems V 3 1 2006 09 Figure 36 RS485 Slave Interface and Tamper Contact Figure 37 Connectors on upper PCB Figure 38 RS485 Host on upper PCB ...

Page 47: ...Access Controller AMC 4W Appendix Bosch Security Systems V 3 1 2006 09 Installation Guide 47 Figure 39 Ethernet Network socket RJ45 Figure 40 Connecting diagram of the RS232 serial interface ...

Page 48: ...41 Jumpers location upper circuit board display board Jumper Setting JP1 Selects RS485 two wire mode or four wire mode JP2 Connects internal ground to RS485 host interface ground JP3 Connects internal ground to RS485 host interface shield DS1 DIL switch for transfer mode and RS485 host interface address selection ...

Page 49: ...al ground to the RS485 slave interface ground JP5 Relay output 6 wet dry mode selector JP6 Relay output 5 wet dry mode selector JP7 Relay output 8 wet dry mode selector JP8 Relay output 7 wet dry mode selector JP9 Relay output 3 wet dry mode selector JP10 Relay output 4 wet dry mode selector JP11 Relay output 1 wet dry mode selector JP12 Relay output 2 wet dry mode selector ...

Page 50: ...Appendix Access Controller AMC 4W 7 3 Legend Twisted pair connection Transmitter Receiver 50 Installation Guide Bosch Security Systems V 3 1 2006 09 ...

Page 51: ...000 534 AMC 4W NET CF With Ethernet Network Connector and additional Compact Flash Memory Card F 014 000 533 7 5 Listings and Approvals 7 5 1 FCC Notice This product is in conformance with subpart B of Part 15 of FCC rules for Field Disturbance Sensors 7 5 2 UL Listing UL 294 Access Control System Units 7 5 3 Safety EN60950 2000 The AMC 4W is in conformance with CE rules 7 6 Included in delivery A...

Page 52: ... 25 Figure 13 Configuration of an RS485 host system 27 Figure 14 Location of the RS485 host interface 28 Figure 15 Connection scheme of an RS485 two wire connection 28 Figure 16 Settings for RS485 two wire connection 29 Figure 17 Connection scheme of an RS485 four wire connection 29 Figure 18 Settings for RS485 four wire connection 30 Figure 19 Location of the RS485 address selector 30 Figure 20 L...

Page 53: ...cks of the AMC 4W 44 Figure 34 Power supply 45 Figure 35 Relay outputs analog inputs and Wiegand interface 45 Figure 36 RS485 Slave Interface and Tamper Contact 46 Figure 37 Connectors on upper PCB 46 Figure 38 RS485 Host on upper PCB 46 Figure 39 Ethernet Network socket RJ45 47 Figure 40 Connecting diagram of the RS232 serial interface 47 Figure 41 Jumpers location upper circuit board display boa...

Page 54: ... jumpers 22 Grounding 22 Hardware 17 Housing material 18 Humidity 18 Installing the AMC 4 20 Internet 5 Legend 49 Listings and Approvals 50 Mounting on rails 20 Opening the AMC 4 Case 21 Operating the AMC 4 38 Performance Characteristics 15 Power consumption 18 Power supply 17 Power Supply 23 Product declaration 50 Protection Class 18 Relay Outputs 34 Resetting the AMC 4 39 RS232 Host Interface 30...