en | Installing

Access Modular

Controller 2

2019-11 | V02 |

Bosch Security Systems B.V.

4.6

Grounding and shielding

The main grounding point at the controller is connected to pin 2
of the power supply connector - see Connecting Diagrams.
It is good practice to shield all wires carrying low level signals.

The controller allows you to create a central ground or shielding
point, simply by setting certain jumpers. Set these jumpers only
if grounding or shielding is not achieved by other means.

Notice!

Risk of malfunction
Ensure that no ground loops are formed.

Notice!

In general the following apply:
If the devices have their own power supplies, the shielding is
applied to one side only. The free end should be insulated to
avoid inadvertent connections.
If one device is fed power by another, the cable shielding
should be applied to both sides.

4.6.1

Grounding for Host Interface

A 1:

A 2:

A 3:

Delivery status

JP1
JP2

JP1
JP2

A

Figure

 

4.5: Location of ground jumper RS-485 host interface

Summary of Contents for ADS?AMC2?2WCF

Page 1: ...Access Modular Controller 2 ADS AMC2 2WCF APC AMC2 2WCF en Installation manual ...

Page 2: ......

Page 3: ... 4 Closing the case 19 4 5 Cabling 20 4 5 1 Conductor data for powering the controller 20 4 6 Grounding and shielding 22 4 6 1 Grounding for Host Interface 22 4 6 2 Grounding for Extension Interface 23 4 7 Connecting the power supply to the controller 25 4 8 Ethernet Host Interface 26 4 9 RS 485 Host Interface 27 5 Operating 29 5 1 Configuring Ethernet interface 29 6 Troubleshooting 30 6 1 Resetti...

Page 4: ...fe mode so that doors will be released if power fails Install manual override switches such as break glass or lever stations to unlock doors in an emergency Warning Risk of explosion of lithium battery The battery can explode if replaced incorrectly Replace battery with the same type as recommended by Bosch Dispose used batteries according to the instructions of the manufacturer of the batteries C...

Page 5: ...ect mounting The controller can fall and break Mount the controller on the matching mounting rails This product is RoHS compliant See Technical data for the full table of hazardous components 1 1 Unpacking Check the packaging for visible damage If anything has been damaged during transport please inform the transport agency Unpack the unit carefully This is an electronic device that must be handle...

Page 6: ...ry information in a battery buffered memory and in a compact flash storage element Even when the unit is offline it is able to perform Independent status and authorization checks on access points Take access decisions Activate and deactivate connected peripheral elements Detect and register all relevant events The Access Modular Controller AMC is supported by the Access Professional Edition APE BI...

Page 7: ... consequential damages hence the above limitation or exclusion might not apply to you Bosch Security Systems retains all rights not expressly granted Nothing in this license constitutes a waiver of Bosch s rights under the U S Copyright laws or any other federal or state law If you need further assistance or have any questions contact Bosch Security Systems B V Torenallee 49 5617 BA Eindhoven Neth...

Page 8: ... direction and up to two doors with a reader in one direction only Figure 3 1 Access Modular Controller All necessary information for access verification is stored in a battery buffered on board memory and a Compact Flash CF memory card This guarantees autonomous access decisions and complete access registrations even if the management host system is offline The built in compact flash card provide...

Page 9: ...or example if a lock is closed or open The relay outputs can be used to activate lock mechanisms if access is granted or activate the burglar alarm system if an intrusion or system alert is detected If the four inputs and four outputs on board are not enough to configure the system up to three additional extension boards can be connected The extensions offer 8 or 16 additional inputs and outputs T...

Page 10: ...fe is estimated at 10 years nevertheless an error message is generated if the voltage sinks below a preset minimum level NOTICE In order to avoid an error message caused by an earlier voltage drop we suggest to replace the battery every 8 years Spare part VARTA CR 2032 PCB 3 Reset push button reachable through the casing using a screwdriver 4 Liquid Crystal Display 5 Push button available on top o...

Page 11: ...igurable RS 485 host interface 9 Docking port for compact flash memory 10 Configurable RS 232 host interface ribbon cable connector 11 Configurable 10 100 Mbit s Ethernet host interface Figure 3 3 Interfaces overview 12 RS 485 extension module bus 13 External tamper contact 14 Connector for power supply 15 Wiegand interfaces for card readers 16 Connectors for analog inputs 17 Connectors for relay ...

Page 12: ...ystems B V Figure 3 4 Jumper back 18 Jumper for setting either voltage free relay output dry mode or looped in voltage from the AMC internal power supply wet mode 19 Jumper Equalization of potential between different systems and earth ground shield for the extension interface ...

Page 13: ...der of the display pages is shown in the following table Push Display Example Description 0 V01 00 02 03 07 or LBUS or BG900 Software versions and date of the firmware every 5 sec alternating with the display of the reader interface 1a S N1 0910019212 Bosch serial number 1b S N2 00000001 2 02 06 15 35 15 S Current date and time S Summer W Winter 3 Dig IO Display of the digital contacts the input s...

Page 14: ...C Network device address MAC 5 N AMC 1234 5678 Network name of the controller 6 I 192 168 10 18 IP address of the controller 7 G 192 168 10 255 IP address of the gateway Version V 00 44 or higher 8 M 255 255 255 0 Subnetmask Version V 00 44 or higher 9 H 192 168 10 10 IP address of the host computer 10 DHCP 1 DHCP status 1 on 0 off 11 D 192 168 10 1 IP address of the DNS server 12 Host C Host acti...

Page 15: ...he two interfaces are available on the device by default With RS485 operation a maximum of eight access controllers can be connected to one party line 2 3 3 2 1 2 2 3 3 4 4 1 Host computer 2 Access Modular Controller 3 Card reader 4 Communication and power supply In the communication chain of a system the access controller is integrated between the host system and the peripheral devices It is poss...

Page 16: ...on a mounting rail The controller can be attached on a standard 35 mm 1 377 in mounting rail using a snap in mechanism Attach the controller into the upper edge of the mounting rail then push down the device and snap it onto the rail by pushing it towards the back 1 2 Figure 4 1 Mounting the controller on a mounting rail ...

Page 17: ...rom a mounting rail Notice To remove the controller from a mounting rail first remove all pluggable connectors Push down the controller until the lower edge snaps out of the mounting rail 1 Pull the lower end of the controller from the mounting rail 2 1 2 Figure 4 2 Unmounting the controller from a mounting rail ...

Page 18: ...case Notice To open the controller first remove all pluggable connectors The controller s case consists of a top cover mounted with a two point snap in closure on a chassis To open the case push down the two snap ins with a screwdriver then swing the cover down Figure 4 3 Opening the controller s case ...

Page 19: ...ide down The upper edge of the front cover now aligns with the two point snap in closures on the upper edge of the back cover 2 and may thus be clicked gently into place Hence the closing process is the reverse of the opening process 1 2 Figure 4 4 Closing the case Notice Risk of damage to equipment If excessive force is required to close the front cover then it is probably incorrectly hooked into...

Page 20: ...or powering the controller With the calculation below you can find out which cable type must be used If you connect the power supply and the controller with the delivered cable set from the enclosure the calculation is not necessary For distances below 25 m 75 ft use AWG18 conductors 1mm For longer distances install an additional power supply close to the controller Please calculate the voltage dr...

Page 21: ...sch Security Systems B V 2019 11 V02 Notice These specifications apply to power supply readers relay outputs and extension interface Regarding inputs specific voltage drop values need to be taken into account Refer to Connecting Analog Input Devices ...

Page 22: ...ing certain jumpers Set these jumpers only if grounding or shielding is not achieved by other means Notice Risk of malfunction Ensure that no ground loops are formed Notice In general the following apply If the devices have their own power supplies the shielding is applied to one side only The free end should be insulated to avoid inadvertent connections If one device is fed power by another the c...

Page 23: ...d the shield on the host are not connected and no party line exists the jumper JP1 is set A2 a party line exists the jumper JP1 is set at the first device only A2 Settings for jumper JP2 If the ground conductor and the shield on the host are not connected and no party line exists the jumper JP2 is set A3 a party line exists and signal ground is connected the jumper JP2 is set at the first device o...

Page 24: ...r 2 2019 11 V02 Bosch Security Systems B V Jumper B connects the internal ground of the controller to the RS 485 ground of the slave interface Only set jumper B B2 if the controller powers all other peripheral devices directly connected to it ...

Page 25: ...nector If an uninterruptible power supply UPS is used the relay output for power good signals from the UPS is connected to the following pins pin 4 and 7 for power good AC pin 5 and 7 for power good Battery pin 6 and 7 for power good DC Otherwise these pins must be short circuited Notice The battery status is checked every 5 minutes by the power supply unit APS PBC 60 or APS PSU 60 As the battery ...

Page 26: ... computer Notice Use a CAT5 or higher version to connect the controller with the network Figure 4 8 Location of the Ethernet interface Notice After connecting a new controller to a network using DHCP it can take some time before the new controller is recognized by the remote server You can accelerate this process by running the following command ipconfig flushdns This makes the controller immediat...

Page 27: ...ontrollers can be used on one host bus 1 3 2 RS 485 Figure 4 9 Configuration of a RS 485 host system Position Description 1 Host 2 RS 485 bus 3 Access Modular Controller The following conditions apply for a RS 485 bus system A bus system consists of a bus line and or one or more branch lines Cable lengths exceeding 100 m 300 ft must be installed as bus lines Branch lines are branching connections ...

Page 28: ...ich are connected to the host computer Maximum cable length of a bus line must not exceed 1200 m 4000 ft The cable length of branch lines must not exceed 100 m 330 ft To use RS 485 mode at the controller connect the data cables to the pluggable screw connector of the RS 485 host interface Figure 4 10 RS 485 host interface ...

Page 29: ...ine AC bin and in the Program Folder of the Access PE Start Programs Access Personal Edition AmcIpConfig This tool can be copied and used on every computer on the network Consult the online help of the AmcIpConfig for details on configuring the controller To ensure that the controller can communicate with the software follow these naming rules Use only alphanumeric characters plus the seperator mi...

Page 30: ...mal operation If you are unsure of the problem or if the problem persists contact After sales support page 34 Problem Cause Solution Display is not working Voltage is too low Power is off Make sure the power supply has enough voltage to power the controller Power up the controller Controller is not online Network connection is missing DIL switch 5 is set to OFF BPA protocol is selected Plug the Et...

Page 31: ...itch 5 to ON SDEB protocol is selected Controller does not work as expected Switch the power of the controller off and on again Check the configuration of the controller If necessary delete all configuration data by Resetting the Device to Factory Default Reset the controller as described in Resetting the software page 32 ...

Page 32: ...ving only its bootloader and network setting As soon as it is online again controller s bootloader will download a fresh copy of the application program and configuration If the problem persists contact after sales support 6 2 Resetting the device to factory default 1 Reset the controller as described in Resetting the software page 32 2 Open the upper case of the controller as described in Opening...

Page 33: ...hes back in the address state before resetting The controller now has the following network configuration DHCP 1 IP assigned by DHCP server or 0 0 0 0 if not available Subnet mask assigned by DHCP server or 0 0 0 0 if not available Password no password Create your password in the IP Config settings of the AMC ...

Page 34: ... controller from the main AC or DC power source and refer servicing to qualified service personnel under the following conditions If the power supply cord or plug is damaged If liquid has been spilled or an object has fallen into the controller If the controller has been exposed to water and or humid weather rain snow etc If the controller has been dropped or the cabinet damaged If the controller ...

Page 35: ...lectrical and electronic waste This product and or battery must be discarded separately from household waste Discard this product according to local laws and regulations to allow its reuse and or recycling This will help in conserving resources and in protecting human health and the environment ...

Page 36: ...ions H W D 232 mm 90 mm 63 mm 9 13 in 3 54 in 2 48 in Weight 503 g Color White System specifications Memory Serial EEPROM Pluggable 2 GB compact flash Reader interfaces 2 Wiegand Host interface RJ45 for TCP IP communication RS485 Outputs 4 relay outputs 30 V DC max switching voltage 1 25 A max switching current 30Vdc Inputs 4 4 State inputs Tamper switch 2 wire Reset button Yes Power 10 VDC to 30 ...

Page 37: ...ental impact of an installation take the most extreme values of all participating devices into account Notice To determine the vulnerability of an installation take the most restrictive values of all participating devices into account Access Modular Controller Series Hazardous substance table according to SJ T 11364 2014 Pb Pb Hg Hg Cd Cd Cr 6 Cr 6 PBB PBB PBDE PBD E Housing enclosures O O O O O O...

Page 38: ...ted according to the provisions of SJ T 11364 O The content of such hazardous substance in all homogeneous materials of such component is below the limit defined in GB T 26572 X The content of such hazardous substance in a certain homogeneous material is above the limit defined in GB T 26572 Notice The voltage drop from the power supply to the controller affects the interfaces of the controller Th...

Page 39: ...dices 10 1 Connecting diagrams RS485 Host RS232 Ethernet RJ45 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 8 4 1 Figure 10 1 Connectors on upper PCB 1 Shield 2 Data RxTx 2 wire Data Rx 4 wire 3 Data RxTx 2 wire Data Rx 4 wire 4 Ground PAG 5 Data Tx 4 wire 6 Data Tx 4 wire Tab 10 1 RS 485 host on upper PCB ...

Page 40: ...ler 2 2019 11 V02 Bosch Security Systems B V 8 4 1 1 TXD 2 TXD 3 RXD 4 Not connected 5 Not connected 6 RXD 7 Not connected 8 Not connected Tab 10 2 Ethernet Network socket RJ45 Figure 10 2 Interconnect diagram of the RS 232 serial interface ...

Page 41: ...er Interface 2 S2 S3 S4 S5 S6 S7 S8 S9 S10 S11 S12 S13 Analog Input 1 Analog Input 2 Analog Input 3 Analog Input 4 Relay Output 1 Relay Output 2 Relay Output 3 Relay Output 4 Tamper Contact RS485 Slave Bus 1 2 1 2 1 2 1 2 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 6 5 4 3 2 1 2 1 1 2 3 4 5 6 7 8 9 10 Figure 10 3 Connector blocks of the AMC2 2W ...

Page 42: ...power good signal Battery 6 UPS power good signal DC 7 UPS power good signal Common Tab 10 3 Power supply 1 red Reader Supply 12V 2 black Reader Supply 0V 3 green Data 0 4 white Data 1 5 drain Shield 6 orange green LED 7 brown red LED 8 yellow Beeper 9 blue Hold 10 violet Card Present Tab 10 4 Wiegand interface AMC Notice For reader settings refer to the respective reader manual ...

Page 43: ...t 1 Relay Output normally open 2 Relay Output common 3 Relay Output normally closed Tab 10 6 Relay output 1 Power supply for external devices 10V 30V 2 Power supply for external devices 0V 3 Shield 4 Data RxTx 5 Data RxTx 6 Ground PAG Tab 10 7 Host Extension interface 1 Tamper Contact in 2 Tamper Contact out Tab 10 8 External tamper contact ...

Page 44: ...44 Appendices Access Modular Controller 2 2019 11 V02 Bosch Security Systems B V ...

Page 45: ...Access Modular Controller 2 Appendices 45 Bosch Security Systems B V 2019 11 V02 ...

Page 46: ...46 Appendices Access Modular Controller 2 2019 11 V02 Bosch Security Systems B V ...

Page 47: ......

Page 48: ...Bosch Security Systems B V Torenallee 49 5617 BA Eindhoven Netherlands www boschsecurity com Bosch Security Systems B V 2019 ...

Reviews: