6 720 644 942

Installation instructions

13

3.7

Measuring gas pressure

Connecting manometer

B

Shut off gas.

B

Remove  front  cover  and  locate  inlet  gas  pressure
measuring point on the left side, see Fig. 15.

B

Loosen  screw  from  test  point  on  the  left  side  and
connect manometer tube on test point.

Fig. 15 Gas pressure measuring point

1

Inlet tap

Static pressure test

B

Turn gas supply back on.

B

Record static gas pressure reading on back page of
manual.

Operating pressure test

B

Turn on all hot water taps served by the water heater.

B

Turn flow control (right knob) fully clockwise.

B

Turn power adjustment (left knob) fully counter-
clockwise.

B

Turn power adjustment knob fully clockwise.

B

Operate all other gas appliances on same gas piping
system at maximum output.

B

Record operating gas pressure reading on back 
page of manual.

Gas pressures lower than 5.7" W.C. for Natural Gas or
10.5" W.C. for LP Gas will result in insufficient degree
rise to the hot water being used and must be corrected.
See Gas Line Sizing under chapter 3.6.

3.8

Water connections

 

When facing the heater, the ½” cold water inlet is on the 
bottom right and the hot water outlet is on the bottom 
left.

B

Install  unions  and  shutoff  or  isolation  valves
when  connecting  plumbing  to  the  water
heater.    This  will  facilitate  any  necessary
cleaning and servicing.

Although water piping throughout the structure may be
other  than  copper,  we  require  that  copper  piping  or
suitably rated stainless steel flex line piping be used for
at  least  three  feet  before  and  after  the  heater  (follow
local  codes  if  more  stringent).  Never  sweat  any  rigid
piping directly to or beneath the water connections or
damage  can  occur  to  the  internal  water  valve  from
heating of the pipe. Plastics or other PEX type plumbing
line materials are not allowed for connecting directly to
the water heater. Keep water inlet and outlet pipes to no
less than  ½"  (12.7mm)  diameter to  allow the full  flow
capacity.
It is recommended that all hot water piping be properly
insulated to avoid heat loss.
If  the  cold  and  hot  connections  to  the  heater  are
reversed, the heater will not function. Be certain there
are no loose particles or dirt in the piping. Blow out or
flush  the  lines  before  connecting  to  the  water  heater.
Full port valves must be installed on both the cold water
supply and hot water outlet lines to facilitate servicing
the heater (see Fig. 16). For installation on a private well
system  with  the  use  of  a  pressure  tank,  the  lowest
pressure  range  setting  recommended  is  30-50  psi
(2.07 and 3.45bar).

Connecting the pressure relief valve (PRV)

A  listed  pressure  relief  valve  must  be  installed  at  the
time of installation. 

No valve is to be placed between

the  PRV  and  the  heater

.  No  reducing  coupling  or

other restriction may be installed in the discharge line.
The  discharge  line  must  be  a  minimum  of  4”  above  a
drain and installed such that it allows complete drainage
of both the PRV and the line.
The location of the PRV must be readily accessible for
servicing or replacement, and be mounted as close to
the water heater as possible. See Fig. 16. To install the
PRV, a suitable fitting connected to an extension on a
“T” fitting can be sweated to the hot water line.
Support all piping.

Fig. 16 Plumbing  Connections  and  Pressure  Relief

Valve

6720608032-13.1Av

1

6720608036-02.2Av

Summary of Contents for 520-HN-L

Page 1: ... or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier In the Commonwealth of Massachusetts this product must be installed by a licensed plumber or gas fitter Upon completion of the installation these instructions should be handed to the user of the appliance for future reference What to do if you smell gas...

Page 2: ...ppears when hot water is turned on but pilot and burners will not ignite 19 6 4 Pilot lights but burners will not come on 20 6 5 Main burners go out during hot water use 20 6 6 Hot water temperature fluctuates at tap 21 6 7 Water is too hot 21 6 8 Water is not hot enough 22 6 9 Low hot water pressure 22 6 10 Noise when heater is running 22 6 11 Burners do not burn cleanly yellow flames when operat...

Page 3: ...tivate heater 0 5 gallon minute 1 9 l m Minimum recommended water pressure 30 PSI 2 07 bar Connections Bottom of heater Temperature rises 1 45F rise 4 1 gpm 50F rise 3 7 gpm 55F rise 3 4 gpm 65F rise 2 8 gpm 77F rise 2 4 gpm 90F rise 2 0 gpm Dimensions Depth in 8 66 220 mm Width in 16 73 425 mm Height in 25 75 655 mm Weight 35 pounds 16 kg Gas types Natural Gas LP Gas Safety devices Flame failure ...

Page 4: ... with local codes or in the absence of local codes the National Fuel Gas Code ANSI Z223 1 NFPA 54 In Canada The Installation must conform with CGA B149 1 2 INSTALLATION CODES and or local installation codes 2 Carefully plan where to install the heater Proper clearances must be followed 3 The appliance must be isolated from the gas supply piping system by closing its individual manual gas shutoff v...

Page 5: ...37 Mounting holes 38 Exhaust pipe union 39 Draft diverter with flue gas sensor 40 Gas valve Fig 4 Minimum clearances 39 38 4 5 23 11 40 H 6720608036 01 2Av 8 66 220 E F G 4 92 125 D 2 50 63 5 1 97 50 3 82 97 A B 37 10 26 35 34 20 36 C Model 520 HN TOP A 12 inches 306 mm FRONT B 4 inches 100 mm BACK 0 inches SIDES 4 inches 100 mm BOTTOM C 12 inches 306 mm Dimensions inches mm 520 HN A 16 73 425 B 2...

Page 6: ...ntal venting An AQ4 powervent with a proof of draft safety interlock device is required and is available for sidewall venting Contact your dealer In the Commonwealth of Massachusetts power vented applications must utilize proof of draft safety interlock device and comply with regulations established for all side wall horizontally vented gas fueled equipment 3 3 2 Vertical venting B A 5 inch diamet...

Page 7: ...ance with Fig 7 and table 2 provided they are at least 8 feet 2 4 m from a vertical wall or similar obstruction All other gas vents that are not able to terminate within the minimum specified height allowed must terminate not less than 2 feet 0 6 m above the highest point where it passes through the roof and at least 2 feet 0 6 m higher than any vertical wall or similar obstruction within 10 feet ...

Page 8: ...k local codes for clarification The lining material must be listed for use only with naturally drafting draft hood equipped gas appliances Follow manufacturer s instructions for installation of listed lining material You may not vent any other fuel burning appliances into any free space remaining in the chimney The minimum vertical gas vent length within the masonry chimney must be no less than 5 ...

Page 9: ...2 inches of the bottom of the enclosure Each opening must have a minimum free area of one square inch per 1000 Btu hr if all air is taken from inside the building 2000 Btu hr if all air is taken from the outside by horizontal ducts 4000 Btu hr if all air is taken from the outside by direct openings or vertical ducts Or the confined space must be provided with one permanent opening or duct that is ...

Page 10: ... either 1x4 s or 1 2 minimum plywood first be attached across a pair of studs and then the heater should be attached to the support boards See Fig 11 B Install the two included L shaped hooks to wall studs or support board 13 apart See Fig 11 B Hang heater on two L shaped hooks See Fig 12 Fig 10 Remove front cover Fig 11 Support board Fig 12 Secure heater to wall Warning B Do not install this appl...

Page 11: ... for leaks HIGH ALTITUDE INSTALLATION The pressure regulator provided with the heater has been adjusted to deliver the proper gas pressure as indicated on the rating plate and in the manual for altitude up to 2000 feet 660 meters above sea level On appliances being installed above 2000 ft 660 meters elevation the inlet gas pressure should be adjusted at installation to the value shown below Note T...

Page 12: ... Pressure Drop of 0 5 Inch Water Column EHD Equivalent Hydraulic Diameter The greater the value of EHD the greater the gas capacity of the tubing Nominal Iron Pipe Internal Size Diameter inches inches 10 20 30 40 50 60 70 80 90 100 125 150 175 200 3 4 0 824 278 190 152 130 115 105 96 90 84 79 72 64 59 55 1 1 049 520 350 285 245 215 195 180 170 160 150 130 120 110 100 1 1 4 1 380 1050 730 590 500 4...

Page 13: ...odes if more stringent Never sweat any rigid piping directly to or beneath the water connections or damage can occur to the internal water valve from heating of the pipe Plastics or other PEX type plumbing line materials are not allowed for connecting directly to the water heater Keep water inlet and outlet pipes to no less than 12 7mm diameter to allow the full flow capacity It is recommended tha...

Page 14: ...on for lighting the pilot and main burners When turning the heater on follow these instructions exactly B Before operating the unit set the On Off button to the On position The On Off button is located on the front panel Smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS B Clos...

Page 15: ...lot flame will extinguish a few seconds after the burners come on The burners will remain on until the hot water tap is turned off Note The 520 HN operates in two modes See SETTING THE WATER TEMPERATURE 4 3 To turn off appliance B Set the ON OFF switch to the position OFF Fig 19 B Close installer supplied manual gas shutoff valve on the supply line to the heater 4 4 Adjusting the water temperature...

Page 16: ...ob clockwise sup plies less gas to the burners and lowers the water temperature Fig 22 B Turning the power adjustment knob counter clock wise supplies more gas to the burners and raises the water temperature Fig 23 Maximum temperature The maximum temperature is achieved by turning the left power adjustment knob fully counter clockwise and the right flow control knob fully clockwise 4 6 Draining th...

Page 17: ...by removing the retaining clip on water valve assembly and pulling the pipe free from the water valve Loosen the two set screws underneath the water valve where it connects to the gas valve If the set screws are seized STOP and call Bosch tech support before proceeding Forcing and breaking seized set screws may damage the water valve and gas valve assemblies Remove the water valve by pulling it to...

Page 18: ...e pressure from the plumbing system 3 Drain water from the unit by disconnecting inlet and outlet water connections 4 Connect the line A from the outlet of the circulating pump installer supplied to the inlet water fitting on the water heater 5 Using another line B connect to the water outlet fitting on the water heater Route the other end of this line into a descaling reservoir 6 Using a 3rd line...

Page 19: ...lean wire connections in heater a wire from ignition unit to spark electrode b wires to flue gas sensor on draft diverter c wires to overheat sensor on outlet pipe d wires to overheat sensor on heat exchanger e wires to microswitch f ground wire connection between ignition unit and fixing screw 8 If a powervent and spill switch are installed check the reset button on the spill switch installed on ...

Page 20: ... the pilot orifice may be dirty or clogged See chapter 5 3 on how to clean the pilot and orifice 3 If sparking does not stop when pilot is lit the flame sensor may not be recognizing pilot flame Verify that wire connection clip on wire from the bottom of the flame sensor is secure If flame sensor is fully engulfed by the pilot flame it may be dirty Clean entire surface area of flame sensor with a ...

Page 21: ...rning the gas control knob clockwise for lower hot water temperatures See chapter 4 5 If the problem persists go to www boschpro com for service bulletin CT 07 4 The water heater is designed to modulate gas flow to the burners when water flow varies If the water pressure in the home is erratic and the water flow is not consistent while a tap is opened then the temperature of the hot water will flu...

Page 22: ...e unit Place a gallon jug under hot water outlet to catch water Open cold water supply and measure flow rate out of the unit With temperature adjustment knob set all the way clockwise the flow rate should be close to 2GPM filling the jug in 30 seconds or less If the flow rate is not adequate inspect and clean inlet filter screen See chapter 5 2 2 Confirm that the incoming water pressure to the uni...

Page 23: ...out the disposal of recyclable products Saving water resources B Make sure you close all the taps after any use Avoid leaving the taps dripping Repair any leaking tap B Define the temperature you want This way you have the precise water flow needed mixing cold water to regulate temperature will increase the water flow with consequent waste of water For increased safety shut off the appliance from ...

Page 24: ...list 8 1 Interior components Fig 27 Functional scheme 4 Heat exchanger 5 Burner 9 Ignition unit 10 Flow control knob 11 Water valve 20 Gas connection 21 Flexible cold inlet 22 Flexible hot outlet 26 Power adjustment knob 30 Pilot burner 51 on off button 4 5 11 20 10 22 26 51 9 30 6720608036 04 3AL 21 ...

Page 25: ...agram parts list 25 8 2 Components diagram Fig 28 Components Diagram 12 50 40 10 11 8 6 7 21 22 42 35 31 33 36 39 45 20 19 15 14 13 16 17 18 43 46 47 36 48 49 2 1 3 5 4 28 29 30 6720608036 05 3 JF 53 23 24 38 41 34 32 37 27 25 26 44 51 52 54 ...

Page 26: ...ressure regulator NG 8 707 406 084 0 23 Water valve 8 707 006 344 0 24 Watervalve pushrod 8 703 204 051 0 25 Diaphragm 8 700 503 084 0 26 Inlet water connection 8 700 306 110 0 27 Selector screw 8 708 500 304 0 28 Ignition unit 8 707 207 272 0 29 Cable 8 704 404 060 0 30 Flue gas sensor 8 707 206 446 0 31 Heat exchanger washer 8 700 103 658 0 32 Threaded bushing 8 700 306 148 0 33 Connector 8 700 ...

Page 27: ...upplying the replacement part s Bosch Thermotechnology Corporation will provide ground service delivery for these parts Expedited or upgraded shipping will be charged to the customer Service Labor Costs This warranty does not cover any labor costs associated with service removal or re installation of part s All such costs must be borne by the Purchaser Additionally this warranty does not cover any...

Page 28: ... side panel Gas Pressure Reading Static__________ Operating__________ Building Water Pressure __________ Range if on Well system __________ Average Winter Temperature __________ Average Summer Temperature __________ Installing Company _____________________________________________ Installer name _____________________________________________ Address _____________________________________________ Phon...

Reviews: