LED Display
7–1
1070 073 822-104 (02.06) GB
7
LED Display
RESET pushbutton
A RESET pushbutton and a horizontal array of 5 LEDs are located on the
backside. They have the following functions:
LED
Display
Meaning
Remedial measure
V
in
LED green
Standard operation
–
LED off
No 230/115V
AC
mains
power or 24 V
DC
is pre-
sent at power supply
Check IPC power supply
for power.
VOut
LED green
Standard operation
–
LED off
In5 V and +12 V
voltages are not present
Check IPC power supply
for power.
Temp
LED off
Standard operation
–
LED
flashes red
Internal housing temp.
above 50
°
C, shutdown
will occur if temperature
continues to rise
Reduce internal IPC
housing temperature.
Check/verify fan func-
tions.
UPS
LED off
Standard operation
–
LED red
IPC currently in battery
mode, i.e., no mains
power present!
Restore mains power to
IPC. Initiate controlled
IPC restart.
LED
flashes red
Battery pack discharged,
defective or not connec-
ted
Check battery charge.
Maintain 5-hour charging
cycle!
Control/
Display
Meaning
Remedial measure
RESET
pushbutton
Initiates reboot of the PC
–
LED red
RESET pushbutton has
been pressed
–
Summary of Contents for IPC
Page 1: ...Antriebs und Steuerungstechnik IPC IPC300 Connectivity Manual Industrial PC 104 Edition ...
Page 12: ...Safety Instructions 1 8 1070 073 822 104 02 06 GB Notes ...
Page 18: ...IPC System Overview 2 6 1070 073 822 104 02 06 GB Notes ...
Page 70: ...Interfaces Ports Connectors 6 22 1070 073 822 104 02 06 GB Notes ...
Page 72: ...LED Display 7 2 1070 073 822 104 02 06 GB Notes ...
Page 75: ...Maintenance and Replacement 8 3 1070 073 822 104 02 06 GB IPC300 Fuse ...
Page 88: ...Maintenance and Replacement 8 16 1070 073 822 104 02 06 GB Notes ...