1  Safety instructions

Save these instructions

This manual contains important instructions that should be followed during installation 

and maintenance of the battery box and batteries.

An important notice

•  The battery box which is supplied with a factory input plug can be safely connected    

  to the wall receptacle by the user. 

•  This battery box is connected to an UPS. There will be voltage at the output 

  terminals if the UPS is turned on even if the input AC mains is not available. 

•  Make sure that the AC utility outlet is correctly grounded. 

•  Do not try to repair the unit yourself, contact your local supplier or your warranty

   will be void. 

•  Use a certified input power cable with the correct plugs and sockets for the 

  appropriate voltage system. 

•  To eliminate any overheating of the battery box, keep all ventilation openings free

   from obstruction and do not place any foreign objects on top of the battery box.

   Keep the battery box 30 cm away from the wall. 

•  Make sure the battery box is installed within the proper environment as specified.

  (0°C -40°C and 30°C -90% non-condensing humidity).

•  Do not install the battery box under direct sunlight. Your warranty will be void if the

  batteries fail due to overheating.

•  This battery box is designed for indoor use only.

•  This battery box is not designed for use in dusty, corrosive and salty environment. 

•  The warranty for this battery box will be void if water or other liquid is spilt or

   poured directly onto the battery box. Similarly we do not warrant any damage to the

   battery box if foreign objects are deliberately or accidentally inserted into the 

  battery box enclosure. 

•  The battery will discharge naturally if the system is unused for a period of time.

•  It should be recharged every 2-3 months if unused. If this is not done, then the

  warranty will be null and void.  During normal operation, the batteries will be

   automatically remained in charged condition. 

•  Servicing of batteries should be performed or supervised by trained personnel with

   knowledge of batteries and the required precautions.

•  When replacing batteries, replace with the same quantity, type & capacity.

•  CAUTION - Do not dispose of battery or batteries in an open fire. 

  The battery may explode.

•  CAUTION - Do not open or mutilate the batteries. The electrolyte from the batteries

   is toxic and harmful to the skin and eyes. 

•  CAUTION - Risk of electric shock - battery circuit is not isolated from AC, hazardous

   voltage may exist between battery terminals and ground. Test before touching with

   bare hands.

•  CAUTION - A battery can present a risk of electrical shock and high short circuit 

  current. The following precaution should be observed when working on batteries:

  A. Remove watches, rings, or other metal objects.

  B. Use tools with insulated handles.

  C. Wear rubber gloves and boots.

  D. Do not lay tools or metal parts on top of batteries.

  E.  Disconnect charging source prior to connecting or disconnecting battery terminals.

Battery box 

Summary of Contents for GALILEO UPS

Page 1: ...www borri it Battery box ...

Page 2: ......

Page 3: ...Page 1 Box batteria Borri Galileo UPS 1 Safety instructions 2 2 Introduction to the panel 3 3 Installation and operation 5 4 Battery box specification 8 Index page ...

Page 4: ...or this battery box will be void if water or other liquid is spilt or poured directly onto the battery box Similarly we do not warrant any damage to the battery box if foreign objects are deliberately or accidentally inserted into the battery box enclosure The battery will discharge naturally if the system is unused for a period of time It should be recharged every 2 3 months if unused If this is ...

Page 5: ...please put the position of the breaker in O position In case there is 2nd or next battery box connected with the battery box the DC voltage from the UPS Bat will flow through without any interruption to the 2nd battery box 2 UPS battery To the UPS DC connected 3 External battery To the DC connected of the 2nd or next battery box connector connected 1 1 2 2 3 3 ...

Page 6: ...e breaker in O position In case there is 2nd or next battery box connected with the battery box the DC voltage from the UPS Bat will flow through without any interruption to the 2nd Battery Box 2 UPS battery To the UPS DC terminal or the next battery box 3 External Battery To the DC terminal of the 2nd or next battery box connector connected ...

Page 7: ...n accordance with the battery box working specifications to avoid overheat and excessive moisture Do not place the battery box in a dusty or corrosive environment or near any flammable objects This battery box is not designed for outdoor use The packing condition and the external outlook of the unit must be inspected carefully before installation Retain the packing material for future use Unpackin...

Page 8: ...Page 6 Battery box Installation supports of Rack Tower units Installation instructions Tower Use with UPS ...

Page 9: ...x UPS Storage instructions For extended storage through moderate climate 15 C to 30 C 5 F to 86 F the batteries should be charged for 12 hours every 6 months by plugging the UPS power cord into the wall receptacle Repeat this every 3 months under high temperature 30 C to 45 C 86 F to 113 F environment ...

Page 10: ...Max UPS charge current Standard 2 2 A 1 4 A 1 A External charger 5 2 A 4 4 A 4 A Connector color Red Black Green Gnd Dimensions W x D x H mm Unit 144 x 367 x 236 151 x 444 x 322 151 x 444 x 322 Shipping 304 x 398 x 527 304 x 484 x 604 6 304 x 484 x 604 6 Weight kg Unit 14 7 39 0 39 0 Shipping 15 9 40 5 40 5 Battery box requires an external 250 W battery charger for charging the batteries cod MUPSA...

Page 11: ...nt Standard 1 5 A 1 A 1 A External charger 4 5 A 4 A 4 A Connector color Red Black Green Gnd Dimensions W x D x H mm Unit 440 x 650 x 88 440 x 650 x 88 440 x 650 x 88 Shipping 560 x 833 x 228 560 x 833 x 228 560 x 833 x 228 Weight kg Unit 28 6 28 6 37 4 Shipping 30 30 39 Battery box GALILEO RT specification Contact your local recycling or hazardous waste center for information on proper disposal o...