User’s Manual
11
3.
I
NSTALLATION
I
NSTRUCTIONS
3.1.
P
RODUCT
I
NSPECTION
Upon receipt of this product, please verify that the product received matches the
product that was ordered and that there is no obvious physical damage to the unit. If
the wrong product was received or the product is damaged in any way, please contact
the supplier from which the product was purchased.
3.2.
S
ITE
S
ELECTION
All units require adequate protection from the elements. Open frame modules
must be mounted within enclosures of suitable rating for the environment.
Adequate clearance should be allowed for easy access to terminals. This will
facilitate inspection and maintenance.
Sufficient circulation of clean, dry air should be provided. Ambient temperatures
should not exceed +40°C (+104°F) nor be less than 0°C (+32°F) and non-
condensing. Ambient air should not be contaminated with harmful chemical vapors
or excessive dust, dirt, or moisture.
The unit requires a minimum clearance of three (3) inches in all directions. Avoid
mounting the unit near heat sources.
3.3.
M
OUNTING
Once the installation site has been selected as outlined above, the unit should be
mounted in place.
Mounting holes should be drilled and mounting studs or anchors installed before
positioning the M3460RD Module. Once the studs or bolts are in place the module
can be mounted. Be sure all mounting hardware is tightened securely.
Refer to Section 6 of this manual to determine the correct mounting dimensions and
provisions for the unit.
3.4.
W
IRING AND
C
USTOMER
C
ONNECTIONS
Table 3-1: Field Wiring Connections
T
ERMINAL
D
ESIGNATION
F
UNCTION
W
IRING
S
PECIFICATION
C
ONNECTION
M
AX
.
T
ORQUE
Drive Bus
–
DC Connection
to Drive
600VAC
3/8" stud
230 lb-in
3460R Output
Bus
–
DC Connection
to M3460R
Module
3.4.1.
P
OWER
W
IRING
WARNING!
Only qualified electricians should perform and maintain the
interconnection wiring of this product. All wiring should be done in
accordance with National Electrical Code or equivalent regulations.
Wire size should be selected in accordance with local codes, according to the
current rating of the M3460R module.
3.4.1.1.
D
RIVE
B
US
–
C
ONNECTION
The Drive Bus should be connected to the negative side of the DC Bus
on the Drive. Connecting to the positive side of the Drive carries a high
risk of damaging drive equipment if energized. Some drives have a
Summary of Contents for M3460RD
Page 4: ...M3460RD 4 This page intentionally left blank ...
Page 6: ...M3460RD 6 This page intentionally left blank ...
Page 16: ...M3460RD 16 This page intentionally left blank ...
Page 18: ...M3460RD 18 This page intentionally left blank ...
Page 25: ...User s Manual 25 NOTES ...
Page 26: ...M3460RD 26 This page intentionally left blank ...
Page 27: ......