M3345
28
A
N
OTE ON
HP
R
ATINGS
The
Braking hp
rating is dependent on the transistors, diodes, snubbers, and fuses
provided with the module. It is a function of the DC bus amp rating and indicates the
maximum hp that the module is designed to dissipate. Modules are able to provide
full
Braking hp
for at least
60 seconds
. Modules can provide less than full Braking
hp for longer times.
The
Continuous hp
rating is a function of package style, heatsinks, and cooling
fans. This rating is always equal to or less than the
Braking hp
rating. For
applications the following must exist:
Continuous Regen hp rating
≥
Required hp rating * Duty Cycle
6.2.
W
ATT
L
OSS
Tables 6-1 thru 6-3 list the maximum Watt/Loss generated by each of the listed
Regen units. When installing Regen units in an additional enclosure, consideration
should be given to internal temperature rise. The Watt/Loss rating in these tables is
based upon the maximum regen capability of each unit. Applications that do not
utilize the full capacity may be calculated as follows:
hp*746*5%+100 = Watt Loss
Where
hp
is the average estimated regen horsepower
6.3.
C
ERTIFICATIONS
There are presently no certifications for the M3345 Regen Unit. If certification is
required, check with your integrator and/or panel shop for full system certification.
The M3345 is constructed with industry guidelines and safety taken into
consideration. If information is required for certification please contact Bonitron with
your request.
6.4.
F
USE
/C
IRCUIT
B
REAKER
S
IZING AND
R
ATING
•
Only replace fuses with original type and rating.
•
Due to the current limit control capability, blown fuses typically indicate internal
device failure or severe transient absorption event.
Table 6-4: Replacement Fuses
R
EGEN
M
ODULE
C
URRENT
R
ATING
A
C
L
INE
I
NPUT
R
EPLACEMENT
F
USE
D
C
B
US
O
UTPUT
R
EPLACEMENT
F
USE
10 Amps
A60Q15
A60Q15
20 Amps
A60Q25
A60Q25
30 Amps (B, S, X chx)
A60Q30
FWP-40
30 Amps (C, Y, Z chx)
FWP-35
FWP-40
45 Amps (B, S, X chx)
A60Q40
FWP-50
45 Amps (C, Y, Z chx)
FWP-50
FWP-60
60 Amps
FWP-70
FWP-80
90 Amps
FWP-100
FWP-100
120 Amps
FWP-125
FWP-125
Summary of Contents for M3345
Page 6: ...M3345 vi This page intentionally left blank ...
Page 12: ...M3345 6 This page intentionally left blank ...
Page 26: ...M3345 20 This page intentionally left blank ...
Page 30: ...M3345 24 This page intentionally left blank ...
Page 36: ...M3345 30 Figure 6 2 M3345 W Chassis Dimensional Outline Dwg 060230 Rev 20070521 ...
Page 37: ...User s Manual 31 Figure 6 3 M3345 V Chassis Dimensional Outline Dwg 070107 Rev 20070521 ...
Page 38: ...M3345 32 Figure 6 4 M3345 B Chassis Dimensional Outline Dwg 920306 Rev 20080310 ...
Page 40: ...M3345 34 Figure 6 6 M3345 C Chassis Dimensional Outline Dwg 950191 Rev 20091229 ...
Page 41: ...User s Manual 35 Figure 6 7 M3345 X Chassis Dimensional Outline Dwg 920322 Rev 20080311 ...
Page 42: ...M3345 36 Figure 6 8 M3345 X Chassis with Fan Dimensional Outline Dwg 940190 Rev 20080311 ...
Page 43: ...User s Manual 37 Figure 6 9 M3345 Y Chassis Dimensional Outline Dwg 950052 Rev 20070928a ...
Page 44: ...M3345 38 Figure 6 10 M3345 Z Chassis Dimensional Outline Dwg 950246 Rev 20000927 mod ...
Page 46: ...M3345 40 This page intentionally left blank ...
Page 49: ...User s Manual 43 NOTES ...
Page 50: ...M3345 44 NOTES ...
Page 51: ......