NOTE
The values are entered automatically into the EEPROM on the controller. If values
are to be written cyclically, there must be no entry into the EEPROM, as it only has a
limited number of admissible writing cycles (about 1 million cycles). If the number of
admissible writing cycles is exceeded, the EEPROM is destroyed.
To avoid this, cyclically written data can be entered exclusively into the RAM without a
writing cycle taking place on the EEPROM. The data are volatile, i.e., they are lost on
power-off and have to be written again after power-on.
12.3.2.1
Example Writing an index parameter
Typically an index parameter is written during commissioning or regularly at simple
positioning applications.
Writing Parameter 1202
Target Position / Distance
(Typ long), in Index 1 into RAM
(
index 34 for write access) with Parameter value 30000.
Index = 1200 + 0x2000 = 0x24B0, Value (int) = 34 = 0x0022
Index = 1202 + 0x2000 = 0x24B2, Value (long) = 30000 = 0x0000 7530
COB ID
CB
Index
Sub-index
Data
Write Request P. 1200 to Index 34
0x601
0x2B
0xB0 0x24
0x05
0x22 0x00
Response
0x581
0x60
0xB0 0x24
0x05
0x00 0x00
Write Request P. 1202 to 30000 u
0x601
0x23
0xB2 0x24
0x00
0x30 0x75 0x00 0x00
Response
0x581 0x60
0xB2 0x24 0x00
0x00 0x00 0x00 0x00
If several parameter of an index should be changed, it is sufficient to set the index
access parameter 1200 once at the beginning.
12.3.2.2
Example Reading an index parameter
To read an index parameter, first the index access parameter has to be set to the
corresponding index. After that, the parameter can be read out.
Reading Parameter 1202
Target Position / Distance
(Typ long), in Index 1 with Pa-
rameter value 123000.
Index = 1201 + 0x2000 = 0x24B1, Value (int) = 1 = 0x0001
Index = 1202 + 0x2000 = 0x24B2, Value (long) = 123000 = 0x0001 E078
COB ID
CB
Index
Sub-index
Data
Write Request P. 1201 to Index 1
0x601
0x2B
0xB1 0x24
0x05
0x01 0x00
Response
0x581
0x60
0xB1 0x24
0x05
0x00 0x00
Read Request P. 1202
0x601
0x40
0xB2 0x24
0x00
0x00 0x00 0x00 0x00
Response
0x581 0x43
0xB2 0x24 0x00
0x78 0xE0 0x01 0x00
If several parameter of an index should be read, it is sufficient to set the index access
parameter 1201 once at the beginning.
84
CM-CAN ACU
04/13