Accessing data via PROFINET
Operating manual for PROFINET fieldbus | DOC01725815-0003 | 2016-12 | V2.04 EN
25
Continuation
Consec.
no.
Data
type
Available
in SW
vers.
Designation
Unit
Description
37
REAL
03.04
Customer-specific output
variable 3
1
Customer-specific soft PLC
output variable
38
DWORD
03.05
Operating time in seconds
1
Operating time in seconds
39
DWORD
03.05
Power On cycles
1
Power On cycles
40
REAL
03.05
Electric energy Wh
Wh
Total electric energy
41
DWORD
03.05
Digital relay outputs
Control of outputs:
Bit 0 = Dig Out 1
(Parameter 4.150 = 25)
Bit 1 = Dig Out 2
(Parameter 4.170 = 25)
Bit 2 = Relay 1
(Parameter 4.190 = 25)
Bit 3 = Relay 2
(Parameter 4.210 = 25)
Bit 4 = Virt Out 1
(Parameter 4.230 = 25)
42
DWORD*
Application error (at
present)
1
Bit-coded
44
DWORD
Application error (at
present)
1
Bit-coded
Tab.: 3 Process data Out which can be parameterized
*
Data type DWORD corresponds to UINT32
4.2 Cyclic data access
– Process data In
The process data listed below is sent from the PROFINET master to the drive controller.
The data is made up of 6 process variables.
IMPORTANT INFORMATION
Thanks to a corresponding selection, the DGM also makes it possible for you to work with a
process image of only 2 process variables. To do this, the "2 Word Output" module has to be
dragged & dropped from the hardware catalogue to the corresponding slot. Both process
variables involve the control word and the rated rotational speed.