The selected warning mask application can be read out via the parameter
Actual
Appl. Warning Mask
627. The above operation modes of parameter
Create Appl.
Warning Mask
626 are encoded in the
Actual Appl. Warning Mask
627. The code
results from hexadecimal addition of the individual operation modes and the match-
ing abbreviation.
Warning code
Create Appl. Warning Mask
626
A 003F
-
2 - Activate all Warnings
A 0001
BELT
10 - Warning V-belt
A 0002
SW-LIM CW
11 - Warning pos. SW limit switch
A 0004
SW-LIM CCW 12 - Warning neg. SW limit switch
A 0008
HW-LIM CW
13 - Warning pos. HW limit switch
A 0010 HW-LIM CCW 14 - Warning neg. HW limit switch
A 0020
CONT
15 - Warning position controller
A 0040
Enc
16 - Warning Encoder
A 0080 User 1
17 - Warning User 1
A 0100 User 2
18 - Warning User 2
Output signals
The output of a warning message is signaled.
215 - Warning Mask,
Application
1)
Output of a warning message which is activated in
Cre-
ate Appl. Warning Mask
626.
27 -
2)
1)
For linking with inverter functions
2)
For digital output
Parameter
Warning Application
273 shows the Application Warnings independent
from the created Warning mask.
In the error environment,
Application Warning Status
367 shows the current warn-
ings of the positioning functions independent from the created Warning mask.
15.4
Digital inputs
The assignment of the control signals to the available software functions can be
adapted to the application in question. Depending on the
Configuration
30 selected,
the default assignment or the selection of the operation mode differ. In addition to
the available digital control inputs, further internal logic signals are available as
sources.
Each of the individual software functions is assigned to the various signal sources via
parameterizable inputs. This enables a flexible use of the digital control signals.
Digital Inputs
Function
6 - On
Signal input is switched on.
7 - Off
Signal input is switched off.
13 - Technology Controller
Start
Start command technology controller (configura-
tion 111, 211 or 411).
70 - Inverter Release
Signal on digital input S1IND/STOA (X210A.3)
and S7IND/STOB (X210B.2); the safety function
STO is linked permanently.
71 - S2IND
Signal on digital input S2IND (X210A.4) or re-
mote operation via communication interface.
72 - S3IND
Signal on digital input S3IND (X210A.5) or re-
mote operation via communication interface.
73 - S4IND
Signal on digital input S4IND (X210A.6) or re-
mote operation via communication interface.
1
Refer to the application manual “Safe Torque Off” for further details.
06/13
Operating Instructions ACU
191