174
Operating Instructions ACU
12/16
Analog Operation 553
Function
54 - Pressure
Abs. value of calculated pressure
0.0 kPa ...
Nominal Pressure
398
.
101 to 133
Operation modes in analog operation with signs.
16.2.1.1
Output Characteristic
The voltage range of the output signal at multifunction output 1 can be adjusted. The value range of
the actual value selected via
parameter Analog Operation
553
is assigned to the value range of the
output signal which is adjusted via the parameters
Voltage 100%
551
and
Voltage 0%
552
.
Parameter
Setting
No.
Description
Min.
Max.
Factory setting
551 Voltage 100%
0.0 V
22.0 V
10.0 V
552 Voltage 0%
0.0 V
24.0 V
0.0 V
Analog Operation
553
with abs. actual
value:
Analog Operation
553
with sign:
0
V
+
1
0
V
+
2
4
V
5
0
%
0
%
1
0
0
%
0
V
+
5
V
+
2
4
V
0
%
-1
0
0
%
1
0
0
%
+
1
0
V
With parameters
Voltage 100%
551
and
Voltage 0%
552
the voltage range at 100% and 0% of
the output parameter is set. If the output value exceeds the reference value, the output voltage also
exceeds the value of the parameter
Voltage 100%
551
up to the maximum value of 24 V.
16.2.2
Frequency Output MFO1F
Multifunction output MFO1 can be used as a frequency output by setting parameter
Operation
Mode
550
= “3 - Repetition Frequency”. The DC 24 V output signal is assigned to the absolute
speed/frequency value via parameter
Repetition Freq. Operation
555
. The selection of the
operation modes depends on the extension modules installed as an option.
Repetition Freq. Operation
555
Function
0 - off
Repetition frequency operation MFO1 switched off
1 - Actual frequency
Abs. value of
Actual Frequency
241
.
2 - Stator Frequency
Abs. value of
Stator Frequency
210
.
3 - Frequency Speed Sensor 1 Abs. value of
Encoder 1 Frequency
217
.
5 - Repetition frequency input Abs. value of
Repetition Frequency Input
252
.