12.5.12
0x6060/0 Modes of operation
Index Sub-index
Meaning
Data type Access Map Def.-Val
0x6060
0
Modes of operation
Integer8
wo
Rx
2
Object works in:
•
o
All modes
Object doesn’t work in:
•
Non motion Control (conf.
≠
x40)
With object
modes of operation, the designated operation mode of the inverter is set.
Depending on the used configuration of the inverter, there are different choices feasi-
ble.
Available values for
modes of operation with inverter in motion control configuration
(p.30 = x40 and 412
Local/Remote
= „1 – Control via Statemachine”):
Modes of operation
Dec.
Hex.
Mode
1
0x01
– Profile position mode
2
0x02
– Velocity mode (Default)
3
0x03
– Profile velocity mode
6
0x06
– Homing mode
7
0x07
– Interpolated position mode
8
0x08
– Cyclic sync position mode
9
0x09
– Cyclic sync velocity mode
-1
0xFF
– Table travel record (manufacturer specific mode)
-2
0xFE
– Move away from Limit switch (manufacturer specific mode)
-3
0xFD
– Electronic Gear: Slave (manufacturer specific mode)
Object 0x6060
modes of operation is limited like described in the table.
Parameter
Setting
No.
Object
Min.
Max.
0x6060/0 Modes of operation
-3 | 0xFD
9
Available value for
modes of operation with inverter in non motion control configuration
(p.30 ≠ x40 or 412
Local/Remote
= „1 – Control via Statemachine”):
Modes of operation
2 – velocity mode
The inverter in non motion control configuration ignores all settings other than “2”.
When accessing via SDO, an SDO fault message is generated, that prompts the invalid
value.
For further information see chapter 14 “Inverter Control”.
80
CM-EtherCAT
07/13