12.5.2
0x603F/0 Error code
Index Sub-index
Meaning
Data type Access Map Def.-Val
0x603F
0
Error code
Unsigned16
ro
No
The object
error code is used to store the last error that occurred.
In DS402, a large number of possible error codes are specified. The following list
shows the relationship between the error code displayed internally by the frequency
inverter and on the KP500 control unit, and the error secured in object
error code.
Error reports
Inverter
Error
DS402
Error code
Meaning
F00 xx
00
00 No error has occurred
Overload
F01 xx
23
10 Frequency inverter has been overloaded
Case
F02 xx
42
10 Case temperature outside the temperature limits
Inside
F03 xx
41
10 Inside temperature outside the temperature limits
Motor connection
F04 xx
43
10 Motor temperature too high or sensor defective
Output current
F05 xx
23
40 Motor phase current above the current limit
DC link voltage
F07 xx
32
10 DC link voltage outside the voltage range
Electronic voltage
F08 xx
51
11 Electronic voltage outside the voltage range
Motor connection
F13 xx
23
30 Earth fault on frequency inverter output
Generic error
Fyy xx
10
00 Other error reports
If the value 1000 (= generic error) appears as the DS402 error code, then the invert-
er error code can be read via parameter
Current error
260 (unsigned16). This pa-
rameter contains the error code in the product-internal format.
The assignment table of the error code
can be taken from the operating instructions.
In the emergency message, the error code of the frequency inverter is transmitted in
bytes 4 ... 7 and the DS402 error code in bytes 0 and 1. Please refer to object
0x1014
COB-ID Emergency Message
for further explanations.
07/13
CM-EtherCAT
71