4.3  Connecting Power Supply  

4.3.1  Connect  the  primary  power  supply  to  0V  and  +U1,  and    backup  power  supply  to  0V 
and +U2. When connecting, please take of the polarity.   

 

We  recommend  that  you  should  use  RIP-12  or  RIP-24  battery  backup  power 
supplies manufactured by Bolid  

4.3.2  Insert the panel into the installed base. 

PANEL TEST  

5.1  The  panel  must  be  tested  by  suitably  qualified  personnel  with  the  electrical  safety 
qualification of Level II. 

Conduct  test  in  normal  climate  environments  as  per  Russian  National  Standard  GOST 
15150-69: 

 

Air humidity: (45 – 80)%; 

 

Air temperature: (25 ± 10) °

С

 

Atmosphere pressure:  (630 – 800) millimeters of mercury., (84 – 106.7) kPa 

5.2  Connection and disconnection of external circuits must be provided only when the Panel 
is powered off.  

5.3  Checking  Main Parameters 

5.3.1  The  testing  shall  be  carried  out  as  shown  in  Figure  12.  The  total  time  for  working 
conditions shall not exceed 20 minutes for each panel. 

5.3.2  The preliminary check shall include the following in the order as specified:  

а

) Check the package before unpacking the panel; 

б

) Check the contents of delivery in accordance with User’s Guide; 

в

)  Check for the physical damage of the panel ; 

г

)  Check the panel visually and shake it for the  foreign items inside the panel; 

д

) Check the tightness of the terminals; 

е

) Check  to  see  that  the  Panel's  number  and  manufactured  date  are  the  same  as 

specified in the Data Sheet. 

5.3.3  Before  powering  the  S2000M    on,  please  visually  inspect  the  panel  for  any  short 
circuits, tack discontinuity and  defects on PCB. 

5.3.4  Set the output voltage A1 as (10.2±0.3) V. 

5.3.5  Assemble the testing system as shown in Figure 12. 

5.3.6  Power  the  panel  on.    The  panel  display  will  illuminate  on  and  show  the  Power  On 
message.  The panel will find a connected device during the several seconds.  The panel will 
report on found devices, device rebooting, and power failure (if any) on the panel display   

5.3.7   Power  on  the  printer.    The  printer  is  to  print  events  with  the  last  one  reporting  on 
powering  the  panel  and  printer,  and  finding  devices.    Press  any  key  of  the  panel.    The 
keyboard will illuminate (visible in the low light condition).  Measure the consumption current 
using    an ammeter (PA1).  The measured value shall not exceed 110 mA.  Press each key 
of the panel.  Key pressing shall be accompanied by short beep.       

5.3.8  Turn  off  the  devices.    Set  the  output  voltage  of  A1  power  supply  as  (28.4±0.6)  V.  
Repeat the above test actions.  The measured current consumption shall not exceed 45 mA 

5.3.9  Disconnect  A1  power  supply  from  the  first  power  input  (+U1)  and  connect  it  to  the 
second one (+U2).  Repeat the actions. 

Summary of Contents for S2000M

Page 1: ...maintenance work can be provided only when the panel power supply is OFF Installation and maintenance shall be carried out by personnel qualified for the Electrical Safety of Level Two or higher 2 INSTALLATION The panel shall be installed in secured areas in easy for access locations keeping the panel protected from atmospheric perceptions and mechanical damage Usually the panel is installed on ve...

Page 2: ...nd dry 3 1 2 Apply installation layout to the wall See Figure 13 Drill three holes two upper holes and one of the lower holes as required 3 1 3 Remove the panel base as it is shown in Figure 2 press base latches 1 and 2 and remove the panel body 3 1 4 Insert nail plugs in the drilled holes and secure the panel base using screws Figure 2 Dismounting View A 4 holes ᴓ5 2 1 ...

Page 3: ...ling RS485 line it is recommended using twisted pair cable If RS485 line is 100 meters or longer only a twisted pair must be used 4 1 2 The Bus topology is recommended for the RS485 line see Figure 4 If needed the RS485 trunk can be branched with short branches no longer than 100 meters Longer branches shall be made using S2000 PI interface converter see Fig 6 4 1 3 The maximum length of RS485 lin...

Page 4: ...127 or S2000M panel 1 only 1 RS 485 line twisted pair 2 Potential equalization conductor 3 Screen if screened cable is used RS 485 Line no more than 3 000m A B 0V Device 620 A B 0V Device A B 0V Device 620 2 3 1 Figure 4 Connecting to RS485 Interface Panel S2000M Panel Device Device of Orion security system PI RS485 Interface Converter Repeater w galvanic isolation S2000 PI A B 0V Panel A B GND A ...

Page 5: ...0 B A 0V PI 620 isolated GND A B B A 0V PI 620 isolated GND A B 620 A B 0V Device A B 0V Device 620 A B 0V Device 620 A B 0V Device Figure 6 Star Topology RS485 Network Based on Repeaters Converters 4 2 Connecting RS 232 4 2 1 Connection to RS 232 is shown in Figures 7 11 S2000M Printer COM DB25F GND DTR RxD XT1 3 7 TxD 8 RxD GND 9 Brown White Green 1 7 3 20 GND RxD DTR 7 3 20 Plug DB25M 1 Printer...

Page 6: ...up battery power supply 1 S2000 to PC connection cable 1 2 3 4 GND TxD RxD 5 V XT3 PC COM 1 2 3 A B 0 V XT2 ISOLATED S2000 PI RS 485 to Panels RS 485 to Devices 1 2 3 4 GND TxD RxD 5 V XT3 1 2 3 A B 0 V XT2 ISOLATED S2000 PI 9 8 7 GND RxD TxD XT1 3 5 6 1 A B 0 V S2000M 2 U XT1 2 XT1 1 U1 1 2 GND XT1 PS Subsystem 1 Subsystem 2 To other Subsystems одсистемам Yel Wht Brn Grn 1 ...

Page 7: ...2V 10 12V 9 IP GND 12 2 1 DI 3 DO 4 1 UART X11 Yellow Green Brown White S2000M XT1 3 7 TxD 8 RxD GND 9 RS232 TTL DO DI 12 GND TxD RxD GND RS232 XT2 RDY TTL XT1 Figure 10 TRX 150 Connection to S2000M for Transmission to Orion Radio GND 12 B TRX 150 Transmitting Receiving TRX 150 TRX 150 or TRX 450 radio transmitter RS232 TTL RS232 TTL converter 1 cable ACDR 685611 229 connecting RS232 TTL to TRX 15...

Page 8: ...visually and shake it for the foreign items inside the panel д Check the tightness of the terminals е Check to see that the Panel s number and manufactured date are the same as specified in the Data Sheet 5 3 3 Before powering the S2000M on please visually inspect the panel for any short circuits tack discontinuity and defects on PCB 5 3 4 Set the output voltage A1 as 10 2 0 3 V 5 3 5 Assemble the...

Page 9: ...inter cable ACDR 685611 015 connecting printer to the S2000M panel R1 R2 resistors 220 Ohm 0 125 W to ensure signal attenuation in the line between the panel and a connected device PV1 Voltmeter PА1 Ammeter PV1 PA1 0 V U А1 GND 7 DTR 20 RxD 3 А4 А5 RS 485A RS 485B 12 V 0 V А2 0 V 12 V А3 R1 R2 XT1 1 0 V 1 U1 2 V A XT1 2 5 A 6 B 1 XT1 3 7 TxD 8 RxD GND 9 Figure 12 Panel Test Connection Diagram ...

Page 10: ... panel operation mode over RS 232 as compatible with a device connected to this interface 2 Program a system configuration as required using the PProg application 3 Set a system date and time These and all other settings must be provided as described in the User s Guide Figure 13 Drilling Pattern 4 holes 5 100 74 ...

Reviews: