2.2
Auxiliary LED Performance
There is an auxiliary green LED on the PCB which indicates the S2000-OST status as shown in table below.
Flashes once per four seconds
Norm
Flashes four times once per four seconds
The S2000-OST is being programmed with an address
Solid light
The S2000-OST is waiting for establishing communication with the KDL.
A proper combination of presses on the button to change address has been
performed
Others
Trouble
2.3
Assigning an Address
The S2000-OST stores its polling loop address in its non-volatile memory. The factory value of the loop address of the S2000-
OST is 127. To assign a new polling loop address to the S2000-OST, one of the following commands should be given to the KDL
from the S2000M panel or PC:
–
Program Device with Address;
–
Change Device Address.
The command Program Device with Address provides assigning a polling loop address to an S2000-OST without regards to which
address is assigned to it at the time. It can be required when the same address is assigned to two or more addressable devices. Give a
command for assigning the specific address from the S2000M panel or PC. Then within no more than 5 minutes perform on the
S2000-OST PCB a combination of three long presses (between 1 s and 3 s) and one short press (less than 0.5 s) on the button – (long-
long-long-short). In this case the panel or PC displays events about missing the device with an old address and connecting the device
with the new address. If several devices had the same address before assigning then no messages about missing devices with the old
address is displayed.
If it is necessary to change address of a device which address is known then the Change Device Address command should be
selected. Give a command to change address specifying the old and new addresses as parameters from the S2000M panel or PC. The
panel or PC shall display events of loss of communication with the device with the old address and connecting the device with the
given address.
2.4
Testing
2.4.1
Before testing notify the proper authorities that the equipment is undergoing maintenance and will be temporarily out of
service. Disconnect all outputs of control devices and executive modules that can run an automated fire-fighting system.
2.4.2
Apply power to the KDL and to the S2000M panel or PC. Remove the front cover from the S2000-OST and ensure the
auxiliary LED on the PCB shows solid light. When communication with the KDL has been established the auxiliary LED starts
flashing once per four seconds indicating normal conditions.
2.4.3
Simplified testing is carried out by pressing on the button on the S2000-OST PCB three times for a short time (shorter than
0.5 s) and then for a longer time (between 1 s and 3 s) – (short-short-short-long). After that the auxiliary LED shall flash 10 times.
2.4.4
Then test operation of the S2000-OST as part of the system by giving the S2000-OST output control commands. The system
shall integrate an S2000M control panel or a PC with Orion Pro software installed and a KDL polling loop controller.
2.4.5
When testing has been completed ensure that the S2000-OST is ready for operation. Restore all binds between system
executive outputs and automated fire-fighting systems and notify the proper authorities that the system is back in operation.
When testing, please be sure all the equipment is known to be operable.
3
MANUFACTURER DATA
The Bolid Company, Russia
Address: 4 Pionerskaya Str., Korolev 141070, Moscow Region, Russia
Tel./fax: +7 (495) 775-71-55 (multi-channel), +7 (495) 777-40-20, +7 (495) 516-93-72
E-mail:
; Technical Support:
;
http://bolid.ru
4
CERTIFICATES
4.1
S2000-OST Addressable LED Emergency Sign Board is approved by Conformity Certificate No. C-RU.
ЧС
13.
В
.00516.
4.2
Conformity Certificate
ТС
№
RU
Д
-RU.
МЕ
61.
В
.00610 certifies that S2000-OST Addressable LED Emergency Sign Board
meets the requirements of Technical Regulations of Custom Union TR CU 020/2011.
4.3
Production of S2000-OST Addressable LED Emergency Sign Board is certified according to
ГОСТ
ISO 9001-2011 by a
conformity certificate No.
РОСС
RU.
ИК
32.
К
00153.
5
PRODUCT ACCEPTANCE CERTIFICATE
The S2000-OST Addressable LED Emergency Sign Board (marked with its serial number on its case) is
qualified as proper for
operation and is packaged by CJSC NVP “Bolid”
.
Responsible for acceptance and packaging
QCD ________________________________ ________________________
Full Name
Date, Month, Year