background image

2.2

 

Auxiliary LED Performance 

There is an auxiliary green LED on the PCB which indicates the S2000-OST status as shown in table below. 
Flashes once per four seconds 

Norm 

Flashes four times once per four seconds 

The S2000-OST is being programmed with an address 

Solid light 

The S2000-OST is waiting for establishing communication with the KDL. 
A proper combination of presses on the button to change address has been 
performed 

Others 

Trouble 

2.3

 

Assigning an Address 

The S2000-OST stores its polling loop address in its  non-volatile  memory. The  factory  value of the loop address of the S2000-

OST is 127. To assign a new polling loop address to the S2000-OST, one of the following commands should be given to the KDL 
from the S2000M panel or PC: 

 

Program Device with Address

 

Change Device Address

The command Program Device with Address provides assigning a polling loop address to an S2000-OST without regards to which 

address is assigned to it at the time. It can be required when the same address is assigned to two or more addressable devices. Give a 
command  for  assigning  the  specific  address  from  the  S2000M  panel  or  PC.  Then  within  no  more  than  5 minutes  perform  on  the 
S2000-OST PCB a combination of three long presses (between 1 s and 3 s) and one short press (less than 0.5 s) on the button – (long-
long-long-short). In this case the panel or PC displays events about missing the device with an old address and connecting the device 
with the new address. If several devices had the same address before assigning then no messages about missing devices with the old 
address is displayed. 

If  it  is  necessary  to  change  address  of  a  device  which  address  is  known  then  the  Change  Device  Address  command  should  be 

selected. Give a command to change address specifying the old and new addresses as parameters from the S2000M panel or PC. The 
panel or PC shall display events of loss of communication  with the device  with the old address and connecting the device  with the 
given address. 

2.4

 

Testing 

2.4.1

 

Before  testing  notify  the  proper  authorities  that  the  equipment  is  undergoing  maintenance  and  will  be  temporarily  out  of 

service. Disconnect all outputs of control devices and executive modules that can run an automated fire-fighting system. 

2.4.2

 

Apply  power  to  the  KDL  and  to  the  S2000M  panel  or  PC.  Remove  the  front  cover  from  the  S2000-OST  and  ensure  the 

auxiliary  LED  on  the  PCB  shows  solid  light.  When  communication  with  the  KDL  has  been  established  the  auxiliary  LED  starts 
flashing once per four seconds indicating normal conditions. 

2.4.3

 

Simplified testing is carried out by pressing on the button on the S2000-OST PCB three times for a short time (shorter than 

0.5 s) and then for a longer time (between 1 s and 3 s) – (short-short-short-long). After that the auxiliary LED shall flash 10 times. 

2.4.4

 

Then test operation of the S2000-OST as part of the system by giving the S2000-OST output control commands. The system 

shall integrate an S2000M control panel or a PC with Orion Pro software installed and a KDL polling loop controller. 

2.4.5

 

When  testing  has  been  completed  ensure  that  the  S2000-OST  is  ready  for  operation.  Restore  all  binds  between  system 

executive outputs and automated fire-fighting systems and notify the proper authorities that the system is back in operation. 

When testing, please be sure all the equipment is known to be operable. 

3

 

MANUFACTURER DATA 

The Bolid Company, Russia 
Address: 4 Pionerskaya Str., Korolev 141070, Moscow Region, Russia 
Tel./fax: +7 (495) 775-71-55 (multi-channel), +7 (495) 777-40-20, +7 (495) 516-93-72 
E-mail: 

[email protected]

; Technical Support: 

[email protected]

http://bolid.ru

 

4

 

CERTIFICATES 

4.1

 

S2000-OST Addressable LED Emergency Sign Board is approved by Conformity Certificate No. C-RU.

ЧС

13.

В

.00516. 

4.2

 

Conformity Certificate 

ТС

 

 RU 

Д

-RU.

МЕ

61.

В

.00610 certifies that S2000-OST Addressable LED Emergency Sign Board 

meets the requirements of Technical Regulations of Custom Union TR CU 020/2011. 

4.3

 

Production  of  S2000-OST  Addressable  LED  Emergency  Sign  Board  is  certified  according  to 

ГОСТ

  ISO  9001-2011  by  a 

conformity certificate No.

РОСС

 RU.

ИК

32.

К

00153. 

5

 

PRODUCT ACCEPTANCE CERTIFICATE 

The S2000-OST Addressable LED Emergency Sign Board (marked with its serial number on its case) is 

qualified as proper for 

operation and is packaged by CJSC NVP “Bolid”

Responsible for acceptance and packaging

 

 
 
 
 

QCD    ________________________________           ________________________ 
 

Full Name 

Date, Month, Year 