2.3
Indication
Table 1 shows the performance of the OPZ light-emitting diode located inside its housing at the PCB.
Table 1. Operation Mode Indication
LED Performance
Condition (Event)
Flashes once per four seconds
Norm
Flashes doubly once per four seconds
Sounding is activated
Flashes triply once per four seconds
Trouble
Flashes four times once per four seconds
Programming
2.4
Operating OPZ
The OPZ is controlled by the polling loop controller as a system output and provides switching sounding on (switching off, pulsing) in accordance with the given
control program by control commands received via the polling loop. Also the OPZ provides monitoring external power supplies. Setting and controlling outputs of the
polling loop are described in manuals for the PL controller, S2000M control panel, and Orion Pro Workstation software.
If the OPZ is in the Trouble mode then no program controlling announcement (Switch On / Off) can be changed by the PL controller. When there is no voltage
from external power supplies it is considered as Trouble. If a single power supply is in use then the contact 1, “+U2” and the contact 3, “+U1” of the XT1 terminal
should be coupled by the jumper (see Figure 1).
The OPZ features single-tone and dual-tone sounding modes which are defined by the position of the XP1 jumper located on the OPZ printed circuit board.
Opening the jumper causes the OPZ to operate with single-tone sounding mode.
WARNING: If for any reason the external power supplies have shut down when announcement is active (and thus announcement shuts down too) then
recovering (reconnecting) at least one of the power supplies will result in activating sound alarms suddenly.
2.5
Setting OPZ Address
The OPZ provides storing its polling loop address in its non-volatile memory. The PL addresses range from 1 to 127. The OPZ comes with the factory address of
127.
In order to set the polling loop address, send one of the following commands from the S2000M or PC to the polling loop controller:
–
Set Device Address;
–
Change Device Address.
The command Set Device Address is used when the OPZ should be assigned with an address regardless of which address is given to it currently. This way is
suitable when, for example, the same address is assigned with two or more devices. If so, issue a command to set the required address from the PC or the control panel.
The OPZ LED shall start flashing four times once per four seconds. Then, within 5 minutes max open the OPZ housing and press the tamper switch three times for a
quite long time (from 1 s to 3 s) and once for a short time (shorter than 0.5 s). The panel / PC shall display the events of loss of communication with the device assigned
with an old address and finding a device with the new address. If several devices were assigned with equal addresses then there will be no messages about loss of
communications for old addresses.
If however it is necessary to change the OPZ address which is known in advance then the Change Device Address command shall be used. Send this command
specifying the old address and the new address from the panel / PC. The panel / PC shall display events about loss of communication with the OPZ with the old address
and establishing communications with the OPZ with the new address.
2.6
Testing OPZ
2.6.1
Before testing the S2000-OPZ, please disconnect executive outputs of the system units and actuators that can release extinguishing agent. Notify the
proper authorities that the system is undergoing maintenance.
2.6.2
Remove the cover from the OPZ and observe S2000M or Orion Workstation receiving a Tamper Alarm message from the address of the OPZ. Close the
OPZ housing and ensure the S2000M or Orion Workstation receives a Tamper Restored message not earlier than in 15 seconds after closing the device.
2.6.3
Activate the sounder sending OPZ the relevant command and ensure that the sound pattern corresponds to the used control programm. Then issue a
command to switch the sounder off.
2.6.4
After testing, verify that the OPZ is ready for normal operation. Then restore operability of all the system components disconnected before. Finally, notify
the proper authorities that the system is back in operation.
Prior to testing ensure that all the equipment in use is known as good!
3
MAINTENANCE
3.1
The S2000-OPZ shall be maintained by specialists with at least third electrical safety qualification level. Maintenance works shall include:
–
Checking whether the sounder is mounted securely, its housing is undamaged, and wire terminals are fastened properly;
–
Eliminating dust, debris, and traces of corrosion from the contact joints and the housing of the OPZ;
–
Testing operability of the OPZ as discussed in Section 2.6 of this manual.
3.2
The S2000-OPZ should be maintained annually and on its sending a Trouble message.
4
MANUFACTURER (VENDOR) WARRANTY
4.1
The average lifetime of the S2000-OPZ is at least 10 years.
4.2
Warranty period is 18 months since putting the S2000-OPZ into operation but no more than 24 months from the manufacturer's date of issue.
4.3
In case of any issue related to programming and operating the product
please contact with the technical support: +7 (495) 775-71-55 or e-mail:
4.4
While sending the product for repair, please apply a report describing the potential failure.
Claims shall be submitted to the following address:
NVP BOLID CJSC, 4 Pionerskaya Str., Korolyov city, Moscow region, 141070, Russia
Phone/Fax: +7 (495) 775-71-55 (PBX), +7 (495) 777-40-20, +7 (495) 516-93-72.
E-mail: [email protected], Technical Support: [email protected],
http://bolid.ru
5
CERTIFICATES
5.1
S2000-OPZ is approved by Conformity Certificate
№
C-RU.
ЧС
13.
В
.00515.
5.2
S2000-OPZ is a part of Orion Addressable Fire Alarm System which is approved by Conformity Certificate
№
BY/112 02.01.033 00573.
6
ACCEPTANCE AND PACKAGING CERTIFICATE
S2000-OPZ addressable fire alarm sounders (serial numbers are inside the housings of every OPZ) are accepted in accordance with mandatory requirements of
state standards and actual engineering documentation and approved as ready for operation.
Responsible for acceptance and packaging
ACCEPTED
QCD _____________________________________________
Date, Month, Year