2.3

 

Indication 

Table 1 shows the performance of the OPZ light-emitting diode located inside its housing at the PCB. 

Table 1. Operation Mode Indication 

LED Performance 

Condition (Event) 

Flashes once per four seconds 

Norm 

Flashes doubly once per four seconds 

Sounding is activated 

Flashes triply once per four seconds 

Trouble 

Flashes four times once per four seconds 

Programming 

2.4

 

Operating OPZ 

The OPZ is controlled by the polling loop controller as a system output and provides switching sounding on (switching off, pulsing) in accordance with the given 

control program by control commands received via the polling loop. Also the OPZ provides monitoring external power supplies. Setting and controlling outputs of the 
polling loop are described in manuals for the PL controller, S2000M control panel, and Orion Pro Workstation software. 

If the OPZ is in the Trouble mode then no program controlling announcement (Switch On / Off) can be changed by the PL controller. When there is no voltage 

from external power supplies it is considered as Trouble.  If a single power supply is in use then the contact 1, “+U2” and the contact 3, “+U1” of the XT1 terminal 
should be coupled by the jumper (see Figure 1). 

The  OPZ  features  single-tone  and  dual-tone  sounding  modes  which  are  defined  by  the  position  of  the  XP1  jumper  located  on  the  OPZ  printed  circuit  board. 

Opening the jumper causes the OPZ to operate with single-tone sounding mode. 

WARNING:  If  for  any  reason  the  external  power  supplies  have  shut  down  when  announcement  is  active  (and  thus  announcement  shuts  down  too)  then 

recovering (reconnecting) at least one of the power supplies will result in activating sound alarms suddenly. 

2.5

 

Setting OPZ Address 

The OPZ provides storing its polling loop address in its non-volatile memory. The PL addresses range from 1 to 127. The OPZ comes with the factory address of 

127. 

In order to set the polling loop address, send one of the following commands from the S2000M or PC to the polling loop controller: 

 

Set Device Address

 

Change Device Address

The command Set Device Address is used when the OPZ should be assigned with an address regardless of  which address is given to it currently. This way is 

suitable when, for example, the same address is assigned with two or more devices. If so, issue a command to set the required address from the PC or the control panel. 
The OPZ LED shall start flashing four times once per four seconds. Then, within 5 minutes max open the OPZ housing and press the tamper switch three times for a 
quite long time (from 1 s to 3 s) and once for a short time (shorter than 0.5 s). The panel / PC shall display the events of loss of communication with the device assigned 
with  an  old  address  and  finding  a  device  with  the  new  address.  If  several  devices  were  assigned  with  equal  addresses  then  there  will  be  no  messages  about  loss  of 
communications for old addresses. 

If however it is necessary to change the OPZ address which is known in advance then the Change Device Address command shall be used. Send this command 

specifying the old address and the new address from the panel / PC. The panel / PC shall display events about loss of communication with the OPZ with the old address 
and establishing communications with the OPZ with the new address. 

2.6

 

Testing OPZ 

2.6.1

 

Before  testing  the  S2000-OPZ,  please  disconnect  executive  outputs  of  the  system  units  and  actuators  that  can  release  extinguishing  agent.  Notify  the 

proper authorities that the system is undergoing maintenance. 

2.6.2

 

Remove the cover from the OPZ and observe S2000M or Orion Workstation receiving a Tamper Alarm message from the address of the OPZ. Close the 

OPZ housing and ensure the S2000M or Orion Workstation receives a Tamper Restored message not earlier than in 15 seconds after closing the device. 

2.6.3

 

Activate  the  sounder  sending  OPZ  the  relevant  command  and  ensure  that  the  sound  pattern  corresponds  to  the  used  control  programm.  Then  issue  a 

command to switch the sounder off. 

2.6.4

 

After testing, verify that the OPZ is ready for normal operation. Then restore operability of all the system components disconnected before. Finally, notify 

the proper authorities that the system is back in operation. 

Prior to testing ensure that all the equipment in use is known as good! 

3

 

MAINTENANCE 

3.1

 

The S2000-OPZ shall be maintained by specialists with at least third electrical safety qualification level. Maintenance works shall include: 

 

Checking whether the sounder is mounted securely, its housing is undamaged, and wire terminals are fastened properly; 

 

Eliminating dust, debris, and traces of corrosion from the contact joints and the housing of the OPZ; 

 

Testing operability of the OPZ as discussed in Section 2.6 of this manual. 

3.2

 

The S2000-OPZ should be maintained annually and on its sending a Trouble message. 

4

 

MANUFACTURER (VENDOR) WARRANTY 

4.1

 

The average lifetime of the S2000-OPZ is at least 10 years. 

4.2

 

Warranty period is 18 months since putting the S2000-OPZ into operation but no more than 24 months from the manufacturer's date of issue. 

4.3

 

In  case  of  any  issue  related  to  programming  and  operating  the  product

 

please  contact  with  the  technical  support:  +7  (495)  775-71-55  or  e-mail: 

[email protected]. 

4.4

 

While sending the product for repair, please apply a report describing the potential failure. 

Claims shall be submitted to the following address: 
NVP BOLID CJSC, 4 Pionerskaya Str., Korolyov city, Moscow region, 141070, Russia 
Phone/Fax: +7 (495) 775-71-55 (PBX), +7 (495) 777-40-20+7 (495) 516-93-72
E-mail: [email protected],  Technical Support: [email protected], 

http://bolid.ru 

5

 

CERTIFICATES 

5.1

 

S2000-OPZ is approved by Conformity Certificate 

 C-RU.

ЧС

13.

В

.00515. 

5.2

 

S2000-OPZ is a part of Orion Addressable Fire Alarm System which is approved by Conformity Certificate 

 BY/112 02.01.033 00573. 

6

 

ACCEPTANCE AND PACKAGING CERTIFICATE 