background image

A T T E N T I O N  
To install the detector on the base plate, align the guide on the detector with the short guide of the base plate. Then turn the detector clockwise until the 

detector guide is aligned with guide 3 as shown in Figure 2 (A)

.

 

2.3

 

Programming the Detector Address 

The detector provides storing its address within the polling loop for communicating with the PLC in the non-volatile memory. The factory address for the gas part 

of the detector is 126 while the factory address for the thermal part of the detector is 127. 

There are two ways to give an address to an S2000-IPG, the first way is to set a required address and the second way is to change the known address value to the 

required value. Each of these commands can be sent from a network controller or by means of the UProg configuration tool. 

When the command for setting a given address is used (for example, in case when the same address is incorrectly assigned to two different devices into the polling 

loop), together with sending the command within 5 minutes press on the detector’s LED or light it with the beam of a laser test tool. The network controller shall show 
a message about disconnecting the device with an old address and connecting the device with the newly programmed address. In the case when two devices had the 
same address no message about disconnecting the device with the old address is indicated. 

If the current address of the detector is known and should be changed for another address, send the change address command from the network controller with the 

old address and the new address as the parameters. The network controller shall indicate a message about disconnecting the device with the old address and connecting 
the device with the new address. 

Then write the programmed address on the address label provided and stick this label to the detector base. 

2.4

 

Testing 

2.4.1

 

Before  testing  notify  the  proper  authorities  that  the  detector  is  undergoing  maintenance  and  will  be  temporarily  out  of  service.  Disconnect  all  outputs  of 

control devices and executive modules that can run an automated fire-fighting system. 

2.4.2

 

Power on the S2000M panel or Orion Pro Workstation and the PLC and observe steady lighting of the detector’s LED. As soon as communication between 

the detector and the polling loop controller has been established the detector’s LED starts pulsing once per 4 s indicating the Norm condition. 

2.4.3

 

Observing  safety  regulations  spray  a  small  amount  of  test  gas  from  the  aerosol  can  into  the  detector.  The  S2000M panel  or  Orion  Pro  Workstation shall 

display a Fire Alarm for the relevant address. The detector’s LED shall flash doubly with intervals 0.5 s in pairs once per four seconds. 

2.4.4

 

To test the thermal part of the detector, blow it with hot air (for example, from a hairdryer). A Fire Alarm message shall be issued with the relevant address. 

2.4.5

 

The detector can also be tested by pressing on its LED and keeping it pressed for at least 2 s or by lighting it with the laser beam of a laser test tool. This will 

cause the LED to show solid light: if an S2000-KDL of version 1.40 or higher is in use then the network controller (S2000M or Orion Pro Workstation) shall indicate 
Alarm Test or Fire Alarm depending on the test mode. To get more information about light indication of the detector when an S2000-KDL of version 1.30 and higher is 
in use and about testing please refer to user’s manuals for the S2000-KDL, S2000M and Orion Pro software. 

2.4.6

 

When the light emitter is released or the laser test tool is disposed ensure the network controller indicates the Norm condition of the detector. If the S2000M 

panel or Orion Pro software has displayed no messages mentioned above for the address of the detector or the detector’s LED performs in a different way, then the 

detector is unhealthy and must be replaced

.

 

2.4.7

 

After testing, restore all binds between system executive outputs and automated fire-fighting system and notify the proper authorities that the system is back 

in operation. 

2.5

 

Maintenance 

2.5.1

 

Inspect operation of the detector as discussed in Section 2.4 annually. 

2.5.2

 

Inspect operation of the detector when it sends trouble messages. 

W A R N I N G  
1)

 

To avoid contamination of the detector please do not remove the protective cover until the surrounding area is cleaned from dirt and dust. 

2)

 

Do not attempt to remove the detector PCB. Disassembling the detector automatically cancels the warranty. 

3)

 

The detector is not designed to be installed within areas where air velocity exceeds 15 m/s. 

3

 

CERTIFICATES 

3.1

 

S2000-IPG  Analog  Addressable  Combined  Gas  and  Rate-of-Rise  and  Fixed  Temperature  Detector  is  approved  by  Conformity  Certificate 

 C-RU.

ЧС

13.

В

.00542. 

3.2

 

Production of S2000-IPG detectors is certified according to 

ОСТ

 ISO 9001-2011 by Conformity Certificate No.

РОСС

 RU.

ИК

32.

К

00153. 

4

 

PRODUCT ACCEPTANCE CERTIFICATE 

The  S2000-IPG  analog  addressable  combined  gas  and  rate-of-rise  and  fixed  temperature  detector  (the  serial  number  can  be  seen  on  the  detector  enclosure)  is 

qualified as proper for operation and packaged by CJSC NVP “Bolid”. 

Accepted and packaged by 

 
 
 
 

Quality Department    __________________________________         _____________________________________ 

  

Full Name 

Date, Month, Year 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

ZAO NVP Bolid, 4 Pionerskaya Str., Korolev 141070, Moscow Region, Russia; Phone/fax: +7 495 775-7155; Email: 

[email protected]

 

 

Technical Support: 

[email protected]

; Web: 

http://bolid.ru

 

Reviews: