This  Installation  Manual  provides  instructions  of  how  to  mount  the  S2000-AR2  Rev.02 
Addressable  Double-Input  Module  (hereinafter  referred  to  as  the  module)  and  get  it  ready for 
operation. 

To get information on module’s description and rules of settings and operation please refer to 
its User’s Manual, which can be found online at http://bolid.ru in the section PRODUCTS. 

1  SAFETY PRECAUTIONS 

 

-

 

The module contains no circuits under hazardous voltages. 

-

 

The  design  of  the  module  meets  the  requirements  of  electric  and  fire  safety 
including  emergency  operation  in  accordance  with  Russian  standards  GOST 
12.2.007.0-75 and GOST 12.1.004-91. 

-

 

Do  shut  off  power  from  the  polling  loop  controller  prior  to  mounting  and 
installing the module. 

-

 

Installation and maintenance shall be carried out by personnel qualified for the 
Electrical Safety of Level II or higher. 

2  INSTALLATION 

2.1  The module is to be installed on a wall, above a suspended ceiling, or on another structure 
of the protected premises at a place protected against atmospheric precipitations, mechanical 
damages, and unauthorized access. 

2.2  The  module  should  be  mounted  in  line  with  Regulatory  Document 

РД

 78.145-93  “Fire 

and Intrusion Alarm Installations. Rules for Performance and Acceptance of Works”. 

3  MOUNTING 

3.1  Make sure the wall the module to be connected to is durable, smooth, clean, and dry. 

3.2  Apply the drilling template to the wall (Figure 1) and drill the holes. 

3.3  Insert wall plugs into the holes. 

3.4  Remove the module cover from its base using a flat-head screwdriver (see Figure 2). 

3.5  Put the module to the wall so that to align the fastening holes with the wall plugs. 

3.6  Screw the screws into the holes and fasten the module on the wall. 

Addressable Double-Input Module 

S2000-AR2 Rev.02 

 
 

Installation Manual 

 

Summary of Contents for S2000-AR2

Page 1: ...d out by personnel qualified for the Electrical Safety of Level II or higher 2 INSTALLATION 2 1 The module is to be installed on a wall above a suspended ceiling or on another structure of the protected premises at a place protected against atmospheric precipitations mechanical damages and unauthorized access 2 2 The module should be mounted in line with Regulatory Document РД 78 145 93 Fire and I...

Page 2: ...erall and Mounting Dimensions of S2000 AR2 Rev 02 Figure 2 Opening S2000 AR2 Rev 02 Enclosure Figure 3 Closing S2000 AR2 Rev 02 Enclosure 1 Put one long end of the cover on the enclosure base 2 Snap on the other end of the cover ...

Page 3: ...ed 100 Ohm while the leakage resistance shall be at least 50 kOhm 4 2 3 If a monitored circuit is not in use connect a 10 kOhm termination resistor to its contacts 4 3 Close the module enclosure as shown in Figure 3 КЦ1 ДПЛС КЦ2 AD Addressable Device MC Monitored Circuit D1 A normally closed fire detector D2 A normally open fire detector D3 A normally open intrusion detector D4 A normally closed i...

Page 4: ...o the module s MC1 5 3 4 Place the detector into the normal state The module LED shall start flashing once eve ry four seconds By means of the network controller issue a command to reset alarm from the detector related to MC1 When one monitored circuit is being tested the other circuit shall be in norm 5 3 5 Perform actions 5 3 2 5 3 4 for the monitored circuit MC2 5 3 6 If no Intrusion Fire Alarm...