Standalone Addressable Device Programmer

 

 

S2000-APA

 

 

User’s Manual 

 

 

 

 

Summary of Contents for S2000-APA

Page 1: ...ISO 9001 Standalone Addressable Device Programmer S2000 APA User s Manual ...

Page 2: ...nded to help for studying operability principles and maintenance of S2000 APA Standalone Addressable Device Programmer Please read the instructions completely before connecting operating adjusting or maintaining this programmer ...

Page 3: ...ddress of an Addressable Device Using the DPLS Protocol 14 2 3 2 Changing Address of an Addressable Device Using the PA Protocol 17 2 4 Setting Addresses 20 2 5 Reading Data 22 2 5 1 Reading Parameters of an Addressable Device Using the DPLS Protocol 22 2 5 2 Reading the Status of an Addresable Device Using the PA Protocol 24 2 6 Information 26 2 6 1 Programmer Data 26 2 6 2 Manufacturer Data 26 2...

Page 4: ...programmer to high and low ambient temperatures in order to avoid battery failures The programmer is designed for operation in premises with regulated and unregulated climatic conditions The design of the programmer does not provide operating under the influence of aggressive environment Parameter Value Power Voltage 3 6 V from built in batteries Battery Capacity 800 mAh 2 pcs Max Consumed Current...

Page 5: ...addressable devices install the base adapter provided into the base Figure 1 shows the view and the control buttons of the APA Figure 1 Appearance and Controls of the Programmer 1 Base for inserting an analog addressable detector 2 Display 3 Keypad 4 Base adapter with red wire for PL and blue wire for PL 5 Base adapter cover 6 USB port 1 4 1 2 3 4 5 6 ...

Page 6: ...r 4 Indicator of the selected data communication protocol DPLS PA Switch the programmer on off hold the button pushed for 3 seconds Move between menu options Enter the selected menu option Cancel Quit to the main menu The options of the main menu are as follows Change Address Set Addresses Read Parameters Settings Info 1 2 3 4 ...

Page 7: ...ication protocol for the programmer to operate with an addressable device The DPLS protocol S2000 KDL The PA protocol Signal 10 By means of the buttons select the required protocol The selected protocol will be indicated by the icon at the upper right corner of the display For the DPLS protocol and For the PA protocol To save changes and to return to the main menu press To return to the main menu ...

Page 8: ...e main menu with the help of the buttons Then press Use the buttons in the Settings menu to select the option BL Brightness By the buttons adjust brightness level of the backlight To save changes and to return to the main menu press To return to the main menu without saving changes press ...

Page 9: ...in menu by means of the buttons Then press Select the LCD Contrast option of the Settings menu by the buttons Adjust the contrast level of the display by means of the buttons To save settings and return to the main menu press To return to the main menu without saving changes press ...

Page 10: ...ct Settings in the main menu by means of the buttons Then press Use the buttons in the Settings menu to select the option Backlight Off Select the timeout value using the buttons To save changes and to return to the main menu press To return to the main menu without saving changes press ...

Page 11: ...nu by means of the buttons Then press In the Settings menu use the buttons to select the option Auto Power Off Using the buttons select the time for the programmer to shutdown automatically To save changes and to return to the main menu press To return to the main menu without saving changes press ...

Page 12: ...he buttons Then press Select the Sound option in the Settings menu by means of the buttons Then select the required setting by the buttons Sound effects are available or Sound effects are disabled To save changes and to return to the main menu press To return to the main menu without saving changes press ...

Page 13: ...in menu by means of the buttons Then press In the Settings menu by means of the buttons select the option Battery Voltage In the information area of the display the current battery percentage of capacity and battery voltage shall be indicated To quit to the main menu press or ...

Page 14: ...34A 03 base or via the base adapter observing polarity and press In case of incorrect polarity or a short circuit failure a warning shall be issued To quit to the main menu press or Repair the failure and press To stop searching and quit to the main menu press To stop searching as soon as the required device has been found press or wait until the search is completed On completing the operation the...

Page 15: ...ice then use the buttons to select the address to be changed Then press By means of the buttons select the position of the digit to be changed By means of the buttons change the digit values of the address If the new address has been already occupied then the programmer displays a warning To cancel operation and return to the address selecting menu press To confirm changing the address press If th...

Page 16: ...edure of addressable device search will be started On completing the search the display will show the information about the addressable device To quit to the main menu press If the addressable device has not responded the display indicates an error To quit to the main menu press or ...

Page 17: ... 34A 03 base or via the base adapter observing polarity and press In case of incorrect polarity or a short circuit failure a warning shall be issued To quit to the main menu press or Repair the failure and press To stop searching and quit to the main menu press To stop searching as soon as the required device has been found press or wait until the search is completed On completing the operation th...

Page 18: ...r S2000 IP PA Press and hold the LED button on the addressable device Holding the button pressed press Wait until the LED of the addressable device starts illuminating Release the button when the LED of the addressable device has turned off If the address change operation has succeeded then a search procedure shall be started On completing the search the display will show the information about the...

Page 19: ...tors it is necessary to Press the LED button on the addressable device and holding it pressed start the operation of changing address Wait until the detector LED starts illuminating Release the button when the LED has turned off It means that the first address is assigned to the addressable device Start the operation of changing address to assign a required address For an IPR 513 3PAM an address i...

Page 20: ...ange To quit to the main menu press To proceed to setting of the last address of the range press Use the buttons and to define a last address value provided that this value should be more or equal to the first address value To return to the previous step press To start the procedure of setting addresses press Connect an addressable device to the programmer via the DIP 34A 03 base or via the base a...

Page 21: ...one For an addressable device with several addresses the programmer checks whether the device responds from the new addresses automatically takes into account the range of occupied addresses and changes the number for a next one from a given sequence To continue remove the addressable device from the programmer and connect the next addressable device The procedure of setting address shall start au...

Page 22: ... To stop searching as soon as the required device has been found press or wait until the search is completed On completing the operation the result can be seen on the display If no addressable device is found then the display shows the message as follows If the addressable device is found then the display shows its name address es and firmware version If the addressable device is assigned to sever...

Page 23: ...r analog to digital converter value Request for dustiness value Request for voltage value Parameters and units of measurement Analog to digital converter units Dustiness of the smoke chamber of the detector Parts per million 10 6 Degrees Centigrade Percentage Volts ...

Page 24: ...stop searching and quit to the main menu press To stop searching as soon as the required device has been found press or wait until the search is completed On completing the operation the result can be seen on the display If no addressable device is found then the display will be as follows If the addressable device is found then its address will be shown on the display To quit to the main menu pre...

Page 25: ... APA http bolid ru 25 The status can be one of the following The smoke alarm is dusted and requires service Norm Fault Tested Fire Alarm for a smoke or heat detector Manual Fire Alarm for a manual call point ...

Page 26: ...ress Move between menu options or Quit to the main menu 2 6 1 Programmer Data Device Type S2000 APA Firmware version V1 00 Model 0 Revision 5 Date 05 2017 ID 01234567 2 6 2 Manufacturer Data Manufacturer Bolid CJSC 2 6 3 Manufacturer Address Manufacturer address 4 Pionerskaya Str Korolev Moscow Region Russia ...

Page 27: ... phone fax 495 775 71 55 multi channel 777 40 20 2 6 5 Manufacturer Site and E Mail E mail info bolid ru The last version of the firmware along with additional information about operating the programmer are available in Internet at the address of www bolid ru ...

Page 28: ...dicates that charging has been completed If the programmer is turned on then charging mode is indicated by the blinking battery icon in the top right corner of the display When charging is completed the programmer issues a sound and the battery icon stops blinking The icon shows the level of battery charge The icon shows that the programmer is connected to the charger WARNING While the batteries a...

Page 29: ...To switch the programmer to the firmware update mode BootLoader connect the programmer to the PC by means of the USB cable If the programmer is turned on turn it off Then press both the buttons and simultaneously and hold them pressed for at least 3 seconds If the programmer is connected for the first time then a new hardware installation wizard software will be run Wait until installation has bee...

Page 30: ...ISO 9001 30 http bolid ru Wait until updating is completed When updating is completed the programmer will proceed to the operating mode and turns on To quit the program click Close ...

Page 31: ...Cause Remedy The programmer doesn t turn on Low battery Connect the programmer to the charger and recharge the batteries An error while writing or reading the address of a device Faulty programmed device or the device is not properly connected to the programmer no contact Connect an operative addressable device repair the contact ...

Page 32: ...by all kinds of transport in covered vehicles and in sealed aircraft compartments 9 Manufacturer Data The Bolid Company Russia Address 4 Pionerskaya Str Korolev 141070 Moscow Region Russia Tel fax 7 495 775 71 55 multi channel 7 495 777 40 20 7 495 516 93 72 E mail info bolid ru Technical Support support bolid ru http bolid ru 10 Certificates Production of Standalone Addressable Device Programmer ...